29
UNT-SVX10G-E4
Installation
Table 10 - Minimum airflow (m3/h) in order to not damage heating elements - FCD
Size
101
103
203
204
304
306
406
408
508
512
612
721
500 W
100
100
80
80
80
80
750 W
150
120
120
120
120
1000 W
160
160
160
160
1500 W
240
240
240
190
190
265
265
375
2000 W
320
320
250
250
350
350
500
3000 W
375
375
525
525
750
4000 W
500
700
700
1000
Table 11 - Minimum airflow (m3/h) in order to not damage heating elements - FED
Unit size
100
200
300
400
500
600
500W
80
80
80
750W
120
120
1000W
160
160
160
160
160
1500W
240
240
240
240
2000W
320
320
320
320
3000W
480
480
480
The minimum airflow is ensured for the fan speed selection using the Trane selection tool.
CAUTION! Measure airflow above the minimum airflow in the above tables when selecting, on site, a lower speed than those
defined from the factory.