UNT-SVX10G-E4
Installation
Speed at ESP = 0Pa
Unit size
101
103
203
204
304
306
406
408
508
512
612
721
Airflow (1)
(m3/h)
188
271
321
415
438
642
642
1004
1110
1329
1411
2031
Standard coil,
cooling mode
Air inlet conditions : 27°C/47%, Water : 7/12°C, Constant delta T°
Total/sensible
cooling capacity (1)
(kW)
1.3/0.97
1.7/1.3
1.6/ 1.3
1.9/1.6
2.8/2.1
3.7/2.8
4.1/3.1
5.5/4.3
4.9/3.8
5.5/4.4
8.8/6.6
11.1/1.5
EER/Eurovent
Energy class (2)
50/F
53/E
45/F
45/F
53/E
58/E
65/E
58/E
50/F
33/G
49/F
39/F
Water flow (1)
(l/s)
0.062
0.081
0.076
0.091
0.13
0.18
0.2
0.26
0.24
0.26
0.42
0.53
Water pressure
drop (1)
(kPa)
16
24.8
5.8
8
13
21.6
25.3
42.9
45.8
55.3
40.9
42.5
Water content
(l)
0.5
0.5
0.6
0.6
1.3
1.3
1.5
1.5
1.5
1.5
2.8
3.3
Water connection
1/2" ISO R7 female gas
3/4" ISO R7 female gas
Standard coil,
heating mode
Air inlet : 20°C, Water inlet : 50°C, Water flow from cooling mode
Heating capacity (1)
(kW)
1.5
1.9
2.3
2.8
3.5
4.8
5.2
7.3
6.8
7.8
10.2
14.2
COP/Eurovent
Energy class (2)
55/E
59/E
66/E
63/E
67/E
75/D
78/D
72/D
64/E
45/F
54/E
49/F
Water flow (1)
(l/s)
0.062
0.081
0.076
0.091
0.13
0.18
0.2
0.26
0.24
0.26
0.42
0.53
Water pressure
drop (1)
(kPa)
13.1
20.7
4.8
6.7
13.6
23
20.6
35.2
38.7
46.8
35.6
39.5
Electric heater
(option)
Electric heater
(W)
NA
500
500/750
500/1000
500/1500
500/1500
500/1500
1500/4000
1500/3000 1500/4000
1500/4000
1500/4000
Power supply
(V-Ph-Hz)
230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
Power absorbed
(speeds 1/3/5)
(W)
11/16/27
18/25/40
19/26/41
23/37/54
26/42/61
36/58/82
36/59/82
53/87/118
53/87/124 118/139/164 119/145/171 152/184/289
Absorbed current
(min/max)
(A)
-
2.2
2.2/3.3
2.2/4.3
2.2/6.5
2.2/6.5
2.2/6.5
6.5/17.4
6.5/13
6.5/17.4
6.5/17.4 6.5/17.4
Fan motor
Maximun external
static pressure
(Pa)
40
60
60
60
90
90
90
90
90
90
90
90
Sound levels
Sound power level
(speeds 2/3/5) (3)
(dB(A))
28/32/42 40/47/54 41/47/54 39/49/ 56 38/47/53 43/53/59 46/55/61 45/54/60 45/56/61 52/59/64 50/58/63 49/64/53
Sound pressure level
(speeds 2/3/5) (4)
(dB(A))
19/23/33 31/38/45 32/38/45 30/40/47 29/38/44 34/44/50 37/46/52 36/45/51 36/47/52 43/50/55 41/49/54 40/55/44
NR Level
(speeds 2/3/5) (4)
17/17/25 28/34/40 29/34/40 27/37/43 25/34/40 30/41/47 34/43/48 31/40/46 32/43/48 36/45/51 35/43/49 36/50/39
NC Level
(speeds 2/3/5) (4)
16/15/23 26/33/39 27/33/39 26/35/41 23/32/39 29/39/45 32/41/46 29/38/44 30/41/46 35/44/49 34/41/47 34/49/38
Speed 1/3/5 -> speed low/medium/high
(1) At high speed acc. to Eurovent conditions
(2) EER Eurovent ratio and class definition (speed low/medium/high)
(3) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent FC Certification
(4) Values calculated from sound levels with hypothetical acoustic attenuation of 9dB
General data
Table 1 - General data - FCD without air connections
230V/50Hz/1pH, Reversible coil, 2 Pipes
UNT-SVX10G-BAT1_Mise en page 1 7/26/2013 2:41 PM Page 7