SS-PRC003-EN
15
Performance
Data
System
Table PD-2 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit with TWE100A Air Handler
(I-P)
Ambient Temperature (°F)
85
95
105
115
Enter.
Dry
Entering Wet Bulb (°F)
CFM
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
Airflow
(°F)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
75
82.1
66.3
90.5
55.2
99.3
36.7
79.5
65.0
87.6
54.0
95.9
35.6
76.2
63.4
84.0
52.6
92.0
34.3
72.3
61.5
80.0
51.0
87.6
32.8
2550
80
82.6
77.8
90.7
63.7
99.4
48.7
80.0
76.5
87.8
62.5
96.1
47.5
76.9
75.0
84.1
60.8
92.2
46.1
73.3
73.2
80.1
59.1
87.9
44.5
85
85.2
85.2
90.8
75.0
99.6
60.5
83.0
83.0
87.9
73.7
96.3
59.2
80.2
80.2
84.4
72.2
92.5
57.8
77.1
77.1
80.4
70.5
88.1
56.3
90
89.5
89.5
91.3
86.6
99.7
72.2
87.1
87.1
88.5
85.3
96.3
70.7
84.3
84.3
85.1
83.8
92.5
69.2
81.1
81.1
81.2
81.2
88.2
67.6
75
83.7
69.7
92.2
54.1 100.8 37.5
81.0
68.4
89.1
52.8
97.4
36.2
77.6
66.7
85.4
51.3
93.3
34.8
73.7
64.9
81.3
49.7
88.8
33.2
2850
80
84.5
82.4
92.2
66.7 101.0 50.5
81.9
81.2
89.2
65.4
97.6
49.2
78.6
78.6
85.5
63.8
93.6
47.8
75.3
75.3
81.4
62.1
89.2
46.2
85
88.1
88.1
92.4
79.2 101.2 63.4
85.7
85.7
89.4
77.9
97.7
62.1
82.8
82.8
85.8
76.4
93.8
60.7
79.5
79.5
81.8
74.6
89.4
59.2
90
92.5
92.5
93.3
92.0 101.2 75.9
90.1
90.1
90.1
90.1
97.8
74.6
87.1
87.1
87.2
87.2
93.9
73.1
83.7
83.7
83.8
83.8
89.5
71.4
75
85.1
72.9
93.5
56.0 102.0 38.0
82.2
71.6
90.3
54.8
98.5
36.8
78.8
69.9
86.6
53.3
94.4
35.4
74.8
68.0
82.3
51.6
89.8
33.8
3150
80
86.0
86.0
93.6
69.7 102.3 52.1
83.6
83.6
90.4
68.3
98.7
50.9
80.6
80.6
86.7
66.7
94.7
49.5
77.3
77.3
82.5
64.9
90.2
47.9
85
90.5
90.5
93.8
83.3 102.5 66.2
88.0
88.0
90.8
82.0
98.9
64.9
85.0
85.0
87.1
80.4
94.8
63.2
81.6
81.6
83.0
78.6
90.4
61.5
90
95.1
95.1
95.2
95.2 102.5 79.6
92.5
92.5
92.6
92.6
99.0
78.3
89.4
89.4
89.5
89.5
95.1
76.8
85.9
85.9
86.0
86.0
90.6
75.1
75
86.2
76.0
94.6
57.9 103.1 38.6
83.3
74.6
91.3
56.6
99.4
37.3
79.9
73.0
87.5
55.1
95.3
35.9
75.9
71.1
83.0
53.1
90.6
34.3
3450
80
88.0
88.0
94.7
72.5 103.3 53.7
85.5
85.5
91.5
71.1
99.7
52.5
82.5
82.5
87.7
69.5
95.7
51.1
79.0
79.0
83.4
67.7
91.1
49.5
85
92.7
92.7
95.1
87.2 103.4 68.6
90.1
90.1
92.0
85.9
99.8
67.2
86.9
86.9
88.3
84.3
95.8
65.7
83.4
83.4
84.2
82.5
91.3
64.0
90
97.4
97.4
97.4
97.4 103.6 83.2
94.6
94.6
94.7
94.7 100.0 81.9
91.4
91.4
91.5
91.5
96.0
80.4
87.8
87.8
87.9
87.9
91.5
78.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (kW) TTA075A Condensing Unit with TWE100A Air Handler
(SI)
Ambient Temperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Entering Wet Bulb (°C)
m
3
/h
Bulb
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
23.9
24.0
19.4
26.5
16.2
29.1
10.8
23.3
19.0
25.6
15.8
28.1
10.4
22.3
18.6
24.6
15.4
26.9
10.0
21.2
18.0
23.4
14.9
25.7
9.6
4332
26.7
24.2
22.8
26.6
18.7
29.1
14.3
23.4
22.4
25.7
18.3
28.1
13.9
22.5
22.0
24.6
17.8
27.0
13.5
21.5
21.4
23.5
17.3
25.7
13.0
29.4
25.0
25.0
26.6
22.0
29.1
17.7
24.3
24.3
25.7
21.6
28.2
17.3
23.5
23.5
24.7
21.1
27.1
16.9
22.6
22.6
23.5
20.6
25.8
16.5
32.2
26.2
26.2
26.7
25.3
29.2
21.1
25.5
25.5
25.9
25.0
28.2
20.7
24.7
24.7
24.9
24.5
27.1
20.3
23.7
23.7
23.8
23.8
25.8
19.8
23.9
24.5
20.4
27.0
15.8
29.5
11.0
23.7
20.0
26.1
15.5
28.5
10.6
22.7
19.5
25.0
15.0
27.3
10.2
21.6
19.0
23.8
14.5
26.0
9.7
4842
26.7
24.7
24.1
27.0
19.5
29.6
14.8
24.0
23.8
26.1
19.2
28.6
14.4
23.0
23.0
25.0
18.7
27.4
14.0
22.0
22.0
23.8
18.2
26.1
13.5
29.4
25.8
25.8
27.1
23.2
29.6
18.6
25.1
25.1
26.2
22.8
28.6
18.2
24.3
24.3
25.1
22.4
27.5
17.8
23.3
23.3
23.9
21.8
26.2
17.3
32.2
27.1
27.1
27.3
26.9
29.6
22.2
26.4
26.4
26.4
26.4
28.6
21.8
25.5
25.5
25.5
25.5
27.5
21.4
24.5
24.5
24.5
24.5
26.2
20.9
23.9
24.9
21.4
27.4
16.4
29.9
11.1
24.1
21.0
26.4
16.0
28.8
10.8
23.1
20.5
25.3
15.6
27.6
10.4
21.9
19.9
24.1
15.1
26.3
9.9
5352
26.7
25.2
25.2
27.4
20.4
29.9
15.3
24.5
24.5
26.5
20.0
28.9
14.9
23.6
23.6
25.4
19.5
27.7
14.5
22.6
22.6
24.2
19.0
26.4
14.0
29.4
26.5
26.5
27.5
24.4
30.0
19.4
25.8
25.8
26.6
24.0
29.0
19.0
24.9
24.9
25.5
23.5
27.8
18.5
23.9
23.9
24.3
23.0
26.5
18.0
32.2
27.8
27.8
27.9
27.9
30.0
23.3
27.1
27.1
27.1
27.1
29.0
22.9
26.2
26.2
26.2
26.2
27.8
22.5
25.1
25.1
25.2
25.2
26.5
22.0
23.9
25.2
22.3
27.7
17.0
30.2
11.3
24.4
21.9
26.7
16.6
29.1
10.9
23.4
21.4
25.6
16.1
27.9
10.5
22.2
20.8
24.3
15.6
26.5
10.0
5862
26.7
25.8
25.8
27.7
21.2
30.3
15.7
25.0
25.0
26.8
20.8
29.2
15.4
24.2
24.2
25.7
20.3
28.0
15.0
23.1
23.1
24.4
19.8
26.7
14.5
29.4
27.1
27.1
27.8
25.5
30.3
20.1
26.4
26.4
26.9
25.1
29.2
19.7
25.5
25.5
25.8
24.7
28.1
19.2
24.4
24.4
24.6
24.2
26.7
18.7
32.2
28.5
28.5
28.5
28.5
30.3
24.4
27.7
27.7
27.7
27.7
29.3
24.0
26.8
26.8
26.8
26.8
28.1
23.5
25.7
25.7
25.7
25.7
26.8
23.0
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity