49
SS-PRC003-EN
Electrical
Data
Table ED-4 — Unit Wiring — Air Handler
Minimum
Maximum Fuse
Unit
Unit Operating
Circuit
Size or Maximum
Model No.
Voltage Range
Ampacity
Circuit Breaker
TWE050
380/415
4
15
TWE075
380/415
5
15
TWE100
380/415
5
15
TWE155
380/415
6
15
TWE200
380/415
10
15
Table ED-1 — Unit Wiring — Condensing Units
Minimum
Maximum Fuse Size
Unit
Unit Operating
Circuit
or Maximum Circuit
Model No.
Voltage
Ampacity
Breaker
TTA075A
380/415
15.6
25
TTA085A
380/415
19.1
25
TTA100A
380/415
22.5
35
TTA100B
380/415
23.9
30
TTA125B
380/415
28.1
35
TTA155B
380/415
28.4
35
TTA155C
380/415
28.4
35
TTA200B
380/415
41.0
50
TTA200F
380/415
48.8
60
Table ED-2 — Electrical Characteristics — Motors — Condensing Units
Compressor Motor
Condenser Fan Motor
Amps
Amps
Unit
RLA
LRA
FLA
LRA
Model No.
No.
Phase
(Ea.)
(Ea.)
No.
Phase
(Ea.)
(Ea.)
TTA075A
1
3
11.2
94.9
1
1
1.6
4.0
TTA085A
1
3
13.1
100.0
1
1
2.7
9.3
TTA100A
1
3
15.8
124.0
1
1
2.7
9.3
TTA100B
2
3
9.4
63.0
1
1
2.7
9.3
TTA125B
2
3
11.3
75.0
2
1
2.7
9.3
TTA155B
2
3
11.2
94.9
2
1
1.6
4.0
TTA155C
1
3
11.2
94.9
2
1
1.6
4.0
TTA200B
2
3
15.8
124.0
2
1
2.7
9.3
TTA200F
2
3
20.0
118.0
2
1
1.9
5.8
NOTE:
1. Electrical characteristics reflect nameplate values and are calculated in accordance with UL and ARI specifications.
Table ED-3 — Electrical Characteristics — Motors — Air Handler
Standard Fan Motor
Oversized Fan Motor
Unit
Amps
Amps
Model No.
Volts
Phase
FLA
LRA
Phase
FLA
LRA
TWE050
380/415
3
2.9
8.2
3
1.8
21.6
TWE075
380/415
3
3.8
19.7
3
4.0
27.5
TWE100
380/415
3
4.0
27.5
3
5.3
37.5
TWE155
380/415
3
4.5
36.2
3
6.9
39.2
TWE200
380/415
3
7.6
45.0
3
9.0
65.1