48
SS-PRC003-EN
Performance
Data
Table PD-41 — Auxiliary Electric Heat Capacity — Air Handler
No.
Stage 1
Stage 2
Total
Unit
Total
of
kW
Btu
kW
Btu
kW
Btu
Model No.
kW
Stages
Input
Output
Input
Output
Input
Output
5.00
1
5.00
17,065
—
—
5.00
17,065
TWE050/075/100AD
9.96
1
9.96
33,993
—
—
9.96
33,993
TWE100BD
14.96
1
14.96
51,058
—
—
14.96
51,058
24.92
2
14.96
51,058
9.96
33,993
24.92
85,051
TWE075, 100AD
TWE100BD
34.88
2
19.92
67,987
14.96
51,058
34.88
119,045
10.00
1
10.00
34,130
—
—
10.00
34,130
TWE155,200B, 200E
19.92
1
19.92
67,987
—
—
19.92
67,987
29.92
2
19.92
67,987
10.00
34,130
29.92
102,117
49.84
2
29.92
102,117
19.92
67,987
49.84
170,104
*Heaters are rated at 400v. For other than rated voltage,
Capacity =
Voltage
2
x Rated Capacity and kW =
Voltage
2
Rated kW.
(
Rated Voltage
)
(
Rated Voltage
)