Air handler units shall be completely
factory assembled including coil,
condensate drain pan, fan motor(s),
filters, and controls in an insulated
casing that can be applied in either
vertical or horizontal configuration. Units
shall be rated and tested in accordance
with ARI standard 210/240, 340/360.

Casing

Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Casing shall be completely insulated
with cleanable, foil faced, fire- retardant,
permanent, odorless glass fiber material.
All insulation edges shall be either
captured or sealed. Knockouts shall be
provided for unit electrical power and
refrigerant piping connections. Captive
screws shall be standard on all access
panels.

Refrigeration System

The TWE050A, TWE075A, TWE100A  units
shall have a single refrigeration circuit
and  the TWE050B, TWE075B, TWE100B,
TWE155B, TWE200B units shall have
dual refrigeration circuits. Each
refrigeration circuit is controlled by a
factory installed thermal expansion
valve.

Evaporator Coil

Configured aluminum fin surface shall
be mechanically bonded to 

3

/

8

” (10 mm)

internally enhanced copper tubing and
factory pressure and leak tested at 450
psig (3103 kPa). Coil is arranged for draw-
thru airflow and shall provide a double
sloped condensate drain pan constructed
of PVC plastic. The drain pan shall be
removable for cleaning. The condensate
drain pan can be installed in any of four
positions allowing for vertical or
horizontal application and providing
external connections on either side of the
unit.

Evaporator Fan

Double inlet, double width, forward
curved, centrifugal-type fan(s) with
adjustable belt drive shall be standard.
Thermal overload protection shall be
standard on motor. Fan and motor
bearings shall be permanently
lubricated. Oversized motors shall be
available as an option for high static
application.

Controls

Magnetic evaporator fan contactor, low
voltage terminal strip, check valve(s), and
single point power entry shall be
included. All necessary controls shall be
factory-installed and wired. Evaporator
defrost control shall be included to
prevent compressor slugging by
temporarily interrupting compressor
operation when low evaporator coil
temperatures are encountered.

Filters

One inch, throwaway filters shall be
standard on TWE050A,  TWE075A,
TWE100A and TWE100B model air
handlers. Filters shall be accessible from
the side coil access panel. Filter rack can
be field converted to two-inch capability.
Two-inch throwaway filters shall be
standard  on TWE155B, TWE200B  and
TWE200E models.

Accessories
Electric Heaters

 — Approved electric

heat modules shall be available for
installation directly on fan discharge.
Electric heaters shall be available in a
wide range of capacities with one or
two-stage control, single-point electric
power connection and terminal strip
connections. Electric heater elements
shall be constructed on heavy-duty
nickel chromium elements internally
wye connected on 480/600 volt, three
phase and delta connected on 208/240
volt, three phase. Each 208/240 volt,

three phase heater shall have pilot duty
with secondary backup fuse links for
automatic reset of high limit controls.
Each 480/600 volt heater shall have
automatic line break high limit controls.

Discharge Plenums and Grilles

 —

Accessory discharge plenums shall be
available for vertical, free discharge
applications. Plenums shall be
constructed of heavy-gauge, zinc coated,
galvanized steel finished with baked
enamel to match the air handler unit.
Grilles shall be satin finished aluminum
and have four-way adjustable louvers.

Return Air Grilles

 — Accessory return air

grille shall be provided for vertical front,
free return applications. Grilles shall be
installed in place of the front lower side
panel. Grille shall be satin finished
aluminum with non-adjustable louvers.

Mounting Subbase

 — This accessory

shall be available for vertical floor mount
configurations. Subbase shall be
constructed of heavy gauge, zinc coated,
galvanized steel with baked enamel
finish to match air handler unit. Subbase
is required in the vertical air flow
application for condensate drain
trapping and when isolators are
required.

Vibration Isolators

 — This accessory

shall reduce transmission of noise and
vibration to building structures,
equipment, and adjacent spaces.
Packages shall be available in either
neoprene-in shear or spring-flex types in
floor or suspended mountings.

Oversized Motors

 — Field installed

oversized motors shall be available for
high static pressure applications.

Control Options
Standard Indoor Thermostats

 — Two

stage heating and cooling operation or
one stage heating and cooling
thermostats shall be available in either
manual or automatic changeover.

Programmable Electronic Night Setback
Thermostat

 

— The option shall provide

heating setback and cooling setup with
7-day programming capability.

Содержание TTA075A

Страница 1: ...Split System Cooling Units 7 5 to 20Tons Air Handlers 7 5 to 20Tons 50 Hz SplitSystem CoolingUnits June 2006 SS PRC003 EN...

Страница 2: ...nels Odyssey units feature time saving colored and numbered wiring and removable panels which allow complete access to all major components and controls All outdoor units feature external high and low...

Страница 3: ...Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Cooling Performance Fan Performance Electrical Controls Dimension andWeights Mechanical...

Страница 4: ...light load conditions only one compressor functions to maintain the space comfort thus reducing the need for energy Trane split systems have been specified in thousands of applications and you ll find...

Страница 5: ...Thermostats OutdoorThermostat Odyssey Lowers Installation Costs Your installation costs are reduced with Odyssey Both outdoor units and air handlers are factory packaged and assembled so jobsite insta...

Страница 6: ...o special tools to run the unit through its paces during testing Simply place a jumper betweenTest 1 andTest 2 terminals on the LowVoltageTerminal Board and the unit will walk through its operational...

Страница 7: ...unit receives a 100 unit run test before leaving the production line to make sure it lives up to rigorousTrane requirements We test designs at our factory not on our customers QualityAnd ReliabilityTe...

Страница 8: ...clearances identified with unit dimensions should be maintained to assure adequate serviceability maximum capacity and peak operating efficiency Actual clearances which appear inadequate should be rev...

Страница 9: ...in 250 Pa filter already Therefore the actualTotal Static Pressure is 1 10 0 10 1 00 in 275 25 250 Pa With 3000 cfm 5097 m3 h and 1 00 inches 250 Pa Table PD 29 shows a 1 17 bhp 0 8 kW Note The formu...

Страница 10: ...rs R22 D 1 Refrigerant Circuit R410A E 2 Refrigerant Circuits R410A F Manifold Scroll Compressors R410A Digit 11 Minor Design Sequence B Second T T A 1 2 0 A 4 0 0 E A 1 2 3 4 5 6 7 8 9 10 11 12 Digit...

Страница 11: ...0 33 25 0 75 56 0 75 56 0 75 56 Motor RPM 925 925 975 975 R 22 Refrigerant Charge lb7 kg 16 0 7 26 19 0 8 62 19 0 8 62 21 0 9 53 Notes 1 Cooling Performance is rated at 95 F 35 C ambient 80 F 26 7 C...

Страница 12: ...btu kW M atched Air Handler 1 1 3 000 33 09 1 34 000 39 24 1 66 000 48 60 1 67 000 48 90 220 000 64 42 220 000 64 42 Condensing Unit Only2 1 1 3 000 33 09 1 30 000 38 06 1 66 000 48 60 1 67 000 48 90...

Страница 13: ...ished Yes Yes Yes Yes No 1 1 3 4 4 Recommended Size in mm 16x20x1 20x20x1 16x25x1 16x25x1 16x25x1 406 4x508x25 4 406 4x635x25 4 406 4x635x25 4 406 4x635x25 4 508x508x25 4 Notes 1 ARI certified with va...

Страница 14: ...door fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC SensibleHeatCapacity Table PD 1 Gross Cooling Capacities MBh TTA075A Condensing Unit withTW...

Страница 15: ...ing capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC SensibleHeatCapacity Table PD 2 Gross Cooling Capacities kW TTA075A Condensing Unit withTWE100AAir Handler SI AmbientTemper...

Страница 16: ...eat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC SensibleHeatCapacity Table PD 3 Gross Cooling Capacities MBh TTA085A Condensing Unit withTWE075AAir H...

Страница 17: ...ered indoor fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC SensibleHeatCapacity Table PD 4 Gross Cooling Capacities kW TTA085A Condensing Unit...

Страница 18: ...al capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC SensibleHeatCapacity T...

Страница 19: ...apacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC...

Страница 20: ...Capacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SH...

Страница 21: ...obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC SensibleHeatCapacity Table PD 8 Gross Cooling Capacities kW Single Compressor TTA100C Condensing Unit withT...

Страница 22: ...t Capacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity S...

Страница 23: ...able In this case the Sensible Heat Capacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat...

Страница 24: ...left is not applicable In this case the Sensible Heat Capacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtrac...

Страница 25: ...s case the Sensible Heat Capacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total G...

Страница 26: ...left is not applicable In this case the Sensible Heat Capacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtrac...

Страница 27: ...SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacities subtract indoor fan heat TGC Total Gross Cooling Capacity SHC Sensibl...

Страница 28: ...own to the left is not applicable In this case the Sensible Heat Capacity SHC is the total capacity All capacities shown are gross and have not considered indoor fan heat To obtain net cooling capacit...

Страница 29: ...6 62 3 62 1 62 5 62 4 67 4 53 5 59 1 58 9 59 2 58 9 63 2 52 3 24 62 9 56 1 68 5 39 1 74 6 20 9 60 0 54 9 65 3 37 8 71 0 20 0 56 8 53 5 61 7 36 4 67 1 18 9 53 3 52 0 57 7 34 6 62 7 17 3 27 64 1 63 9 6...

Страница 30: ...2 8 76 8 91 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 17 Cooling Performance kW TTA075A Condensing Unit Only SI ODTemp Suction ReferenceTemperature C C 1 1 1 7 4 4...

Страница 31: ...8 81 8 97 9 13 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 18 Cooling Performance kW TTA085A Condensing Unit Only SI ODTemp Suction ReferenceTemperature C C 1 1 1 7...

Страница 32: ...1 28 11 54 11 79 12 05 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 19 Cooling Performance kW TTA100A Condensing Unit Only SI ODTemp Suction ReferenceTemperature C C...

Страница 33: ...66 10 98 11 33 11 70 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 20 Cooling Performance kW TTA100B Condensing Unit Only SI ODTemp Suction ReferenceTemperature C C 1...

Страница 34: ...6 12 0 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Performance Data Condensing Unit Table PD 21 Gross Cooling Capacities kW Both Compressors SI TTA100C Condensing Unit Only...

Страница 35: ...t KW 4 9 5 0 5 1 5 2 5 3 5 5 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 22 Gross Cooling Capacities kW Single Compressor SI TTA100C Condensing Unit Only ODTemp Suct...

Страница 36: ...ance Data Calculated at 15 deg subcooling and 15 deg superheat Performance Data Condensing Unit Table PD 23 Cooling Performance kW TTA125B Condensing Unit Only SI ODTemp Suction ReferenceTemperature C...

Страница 37: ...84 17 14 17 45 17 81 18 20 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 24 Cooling Performance kW TTA155B Condensing Unit Only SI ODTemp Suction ReferenceTemperature...

Страница 38: ...72 4 OD Unit KW 16 5 16 8 17 1 17 4 17 8 18 1 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 25 Gross Cooling Capacities kW Both Compressors SI TTA155C Condensing Unit...

Страница 39: ...Unit KW 7 9 7 9 8 0 8 1 8 2 8 2 Performance Data Calculated at 15 deg subcooling and 15 deg superheat Table PD 26 Cooling Performance kW Single Compressor SI TTA155C Condensing Unit Only ODTemp Suctio...

Страница 40: ...mance Data Calculated at 15 deg subcooling and 15 deg superheat Performance Data Condensing Unit Table PD 27 Cooling Capacities MBh TTA200B Condensing Unit Only SI ODTemp Suction ReferenceTemperature...

Страница 41: ...acity MBH 140 1 154 3 169 0 184 1 199 6 215 3 Unit KW 19 43 19 83 20 23 20 64 21 05 21 46 Table PD 28 Gross Cooling Capacities MBH 20 Ton TTA200F Condensing Unit Only SI Outdoor Air Temperature C 1 1...

Страница 42: ...n a wet coil and 1 inch 25 4 mm throwaway filters 2 Tabulated brake horsepower is the motor shaft output required 3 Factory setting of motor sheave is 1 5 turns open Adjustments are made in 0 5 turn i...

Страница 43: ...6 3547 453 0 34 499 0 39 546 0 43 592 0 47 638 0 51 684 0 55 730 0 59 771 0 63 798 0 67 825 0 72 3755 463 0 37 510 0 41 556 0 45 602 0 5 649 0 54 695 0 59 742 0 63 776 0 68 804 0 72 831 0 77 3964 473...

Страница 44: ...00 1 20 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 5 HP Standard Motor and Low Static Drive 2600 460 0 32 493 0 39 527 0 47 565 0 55 603 0 63 641 0...

Страница 45: ...m throwaway filters 2 Tabulated brake horsepower is the motor shaft output required 3 Factory setting of motor sheave is 1 5 turns open Adjustments are made in 0 5 turn increments Table PD 35 Evaporat...

Страница 46: ...and 2 inch 51mm throwaway filters 2 Tabulated brake horsepower is the motor shaft output required 3 Factory setting of motor sheave is 1 5 turns open Adjustments are made in 0 5 turn increments 4 Low...

Страница 47: ...may be established by multiplying throw distances in table above by throw factor Terminal Velocity Throw Factor 50 fpm 25 m s x 1 50 100 fpm 51 m s x 75 150 fpm 76 m s x 50 Performance Data Table PD...

Страница 48: ...TWE100BD 14 96 1 14 96 51 058 14 96 51 058 24 92 2 14 96 51 058 9 96 33 993 24 92 85 051 TWE075 100AD TWE100BD 34 88 2 19 92 67 987 14 96 51 058 34 88 119 045 10 00 1 10 00 34 130 10 00 34 130 TWE155...

Страница 49: ...densing Units Compressor Motor Condenser Fan Motor Amps Amps Unit RLA LRA FLA LRA Model No No Phase Ea Ea No Phase Ea Ea TT A075A 1 3 11 2 94 9 1 1 1 6 4 0 TT A085A 1 3 13 1 100 0 1 1 2 7 9 3 TTA100A...

Страница 50: ...AYHTRL415A 14 96 TWE100AD TWE100BD 1 25 25 BAYHTRL425A 29 92 2 38 40 BAYHTRL435A 34 88 2 52 60 BAYHTRM410A 10 00 1 19 20 BAYHTRM420A 19 92 TWE155BD 1 32 35 BAYHTRM430A 29 92 2 46 50 BAYHTRM450A 49 84...

Страница 51: ...utdoor section B TTA075A TWE075A TTA085 TWE075A TTA085 TWE100A TTA100A TWE100A FieldWiring A 3 power wires line voltage B 3 power wires line voltage for 3 phase 2 wires for single phase C Coolingonlyt...

Страница 52: ...52 SS PRC003 EN Typical Wiring Air Handler Air Handler Typicalwiringdiagram Forspecific wiring see isee wire diagram manual online...

Страница 53: ...53 SS PRC003 EN Typical Wiring Condensing Unit Air Handler Typical unit wiring diagram For specific wiring see see wire diagram manual online...

Страница 54: ...54 SS PRC003 EN Typical Wiring Condensing Unit CondensingUnit SingleCompressor Typicalwiringdiagram Forspecific wiring seewirediagrammanualon line...

Страница 55: ...55 SS PRC003 EN Typical Wiring Condensing Unit CondensingUnit Single Compressor Typicalwiringdiagram Forspecific wiring seewirediagrammanualon line...

Страница 56: ...56 SS PRC003 EN Typical Wiring Condensing Unit CondensingUnit DualCompressor Typicalwiringdiagram Forspecific wiring seewirediagrammanualon line...

Страница 57: ...57 SS PRC003 EN Typical Wiring CondensingUnit DualCompressor Typicalwiringdiagram Forspecific wiring seewirediagrammanualon line...

Страница 58: ...58 SS PRC003 EN Figure DD 1 TTA075 Condensing Units All dimensions are in inches and millimeters Dimensional Data...

Страница 59: ...59 SS PRC003 EN Dimensional Data Figure DD 2 TTA085A and 100A Condensing Units All dimensions are in inches and millimeters...

Страница 60: ...60 SS PRC003 EN Dimensional Data Figure DD 3 TTA100C Condensing Units All dimensions are in inches and millimeters...

Страница 61: ...61 SS PRC003 EN Dimensional Data Figure DD 4 TTA100B and TTA125B Condensing Units All dimensions are in inches and millimeters...

Страница 62: ...62 SS PRC003 EN Dimensional Data Figure DD 5 TTA155B Condensing Unit All dimensions are in inches and millimeters...

Страница 63: ...63 SS PRC003 EN Dimensional Data Figure DD 6 TTA155C Condensing Units All dimensions are in inches and millimeters...

Страница 64: ...64 SS PRC003 EN Dimensional Data Figure DD 7 TTA200B Condensing Unit All dimensions are in inches and millimeters...

Страница 65: ...65 SS PRC003 EN Dimensional Data Figure DD 8 TTA200F Condensing Unit All dimensions are in inches and millimeters...

Страница 66: ...nal Data Table DD 1 Air Handler Dimensions in mm Model No A B C D E F G H TWE050A 48 38 22 8 19 1 2 26 15 7 8 14 1 8 1219 20 965 20 558 80 203 20 495 30 660 40 403 23 358 78 Table DD 1 Continued Model...

Страница 67: ...25 19 3 4 22 3 8 22 17 3 4 1371 60 1612 90 635 00 501 65 568 33 558 80 450 85 TWE100B 54 63 1 2 25 19 3 4 22 3 8 22 20 1 8 16 1371 60 1612 90 635 00 501 65 568 33 558 80 511 18 406 40 Table DD 2 Conti...

Страница 68: ...el No L M N P R T X Z TWE050A 34 5 8 2 7 8 35 5 8 12 1 4 32 1 4 12 1 2 7 5 8 2 879 48 73 03 904 88 311 15 819 15 317 50 193 68 50 80 TWE075A 36 7 8 6 5 8 45 1 8 16 1 8 41 3 4 16 1 4 6 7 8 1 3 4 936 63...

Страница 69: ...69 SS PRC003 EN Dimensional Data Figure DD 12 TWE155B and 200B Air Handlers All dimensions are in inches and millimeters...

Страница 70: ...3 114 30 787 40 711 20 1317 63 1501 78 460 38 Table DD 4 Continued Model No L M N P R S T U V W TWE155B 19 1 2 77 1 4 1 1 4 48 35 35 2 7 8 73 7 8 3 3 4 3 3 8 495 30 1962 15 31 75 1219 20 889 00 889 00...

Страница 71: ...G H J K L M N P R TWE200E 717 8 925 8 301 2 187 8 41 2 281 2 28 517 8 591 8 181 8 207 8 891 4 13 4 507 8 391 8 1826 2353 775 479 114 724 711 1318 1502 460 530 2267 45 1292 994 Table DD 5 Continued Mo...

Страница 72: ...SS PRC003 EN Figure DD 15 Electric Heater for TWE050 075 100 Air Handlers All dimensions are in inches and millimeters Figure DD 16 Electric Heater for TWE155 and 200 Air Handlers Dimensional Data 18...

Страница 73: ...349 5 771 5 Table DD 6 Discharge Plenum And Grille Dimensions in mm Model Model No A B C TWE050 BAYPLNM015 377 8 217 8 28 962 555 6 71 1 2 TWE075 BAYPLNM016 471 2 25 28 1206 5 635 71 1 2 TWE100 BAYPLN...

Страница 74: ...308 0 196 88 9 193 87 5 144 65 3 146 66 2 TTA155C 764 346 6 679 308 0 196 88 9 193 87 5 144 65 3 146 66 2 TT A200B 948 430 0 863 391 5 247 112 0 244 110 7 185 83 9 187 84 8 TT A200F 920 418 835 379 29...

Страница 75: ...4 185 83 9 TWE200E 857 390 787 357 109 50 262 119 154 70 262 119 192 87 229 104 130 59 236 107 NOTE 1 If application requires steam or hot water heating coils field supplied isolators must be utilized...

Страница 76: ...l finish Units surface shall be tested 500 hours in salt spray test Units shall have removable end panels which allow access to all major components and controls Refrigeration System Single Compressor...

Страница 77: ...for mounting a fused disconnect device A choice of microprocessor or electro mechanical controls shall be available The 24 volt electro mechanical control circuit shall include control transformer and...

Страница 78: ...throwaway filters shall be standard onTWE050A TWE075A TWE100A andTWE100B model air handlers Filters shall be accessible from the side coil access panel Filter rack can be field converted to two inch...

Страница 79: ...ecifications without notice Literature Order Number SS PRC003 EN File No PL UN SS PRC003 EN 0606 Supersedes PL UN SS PRC003 EN 0104 StockingLocation ElectronicOnly Trane A business of American Standar...

Отзывы: