18
SS-PRC003-EN
Table PD-5 — Gross Cooling Capacities (MBh) TTA100A Condensing Unit with TWE100A Air Handler
(I-P)
Ambient Temperature (°F)
85
95
105
115
Enter.
Dry
Entering Wet Bulb (°F)
CFM
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
Airflow
(°F)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
75
104.7
81.7 115.8 68.5 127.7 46.8
100.9
79.7 111.5 66.8 123.0 45.1
96.8
77.7 107.1 65.0 118.1 43.5
92.4
75.5 102.5 63.2 112.9 41.7
3025
80
105.2
95.0 116.1 78.6 127.8 61.1
101.5
93.1 111.9 76.8 123.2 59.3
97.5
91.1 107.5 75.0 118.3 57.5
93.3
89.0 102.9 73.0 113.3 55.6
85
106.9
106.9 116.3 92.0 128.1 74.9
103.8
103.8 112.1 90.1 123.5 73.1 100.4 100.4 107.7 88.1 118.7 71.3
96.9
96.9 103.1 86.1 113.7 69.5
90
112.3
112.3 116.8 105.4 128.4 88.7
109.1
109.1 112.7 103.5 123.8 86.9 105.7 105.7 108.4 101.6 119.0 85.1 102.1 102.1 104.1 99.7 113.8 82.9
75
106.8
85.3 118.0 67.1 129.8 47.6
102.8
83.3 113.6 65.3 124.9 46.0
98.6
81.2 109.0 63.4 119.8 44.2
94.2
79.1 104.3 61.5 114.5 42.4
3350
80
107.5
99.9 118.3 82.1 130.0 63.0
103.7
98.0 113.9 80.3 125.2 61.2
99.6
96.0 109.4 78.4 120.2 59.4
95.4
93.9 104.5 76.0 115.0 57.5
85
110.4
110.4 118.4 96.5 130.3 78.1
107.1
107.1 114.1 94.6 125.5 76.3 103.7 103.7 109.6 92.6 120.6 74.5 100.0 100.0 104.9 90.5 115.4 72.6
90
116.1
116.1 119.2 111.2 130.5 93.1
112.7
112.7 115.0 109.3 125.6 90.9 109.1 109.1 110.7 107.4 120.7 89.0 105.4 105.4 106.3 105.4 115.6 87.0
75
108.6
88.8 119.7 69.3 131.5 48.5
104.5
86.8 115.2 67.4 126.5 46.8 100.2 84.7 110.6 65.5 121.2 44.9
95.6
82.4 105.7 63.5 115.8 43.0
3675
80
109.5
104.7 120.1 85.4 131.7 64.8
105.6
102.7 115.4 83.2 126.8 63.1 101.6 100.7 110.8 81.2 121.7 61.2
97.0
97.0 105.9 79.1 116.4 59.3
85
113.5
113.5 120.3 100.8 132.1 81.1
110.1
110.1 115.8 98.8 127.2 79.3 106.4 106.4 111.2 96.8 122.1 77.5 102.6 102.6 106.5 94.8 116.8 75.6
90
119.4
119.4 121.4 116.8 132.2 96.8
115.8
115.8 117.2 114.9 127.3 94.9 112.1 112.1 112.2 112.2 122.3 92.9 108.2 108.2 108.3 108.3 117.0 90.9
75
110.1
92.1 121.2 71.3 132.9 49.2
105.9
90.0 116.6 69.4 127.8 47.4 101.5 87.9 111.9 67.5 122.4 45.5
96.9
85.7 106.9 65.6 116.8 43.6
4000
80
111.4
109.2 121.4 88.2 133.2 66.6
107.5
107.3 116.9 86.2 128.2 64.8 103.1 103.1 112.1 84.2 123.0 63.0
99.3
99.3 107.2 82.0 117.6 61.1
85
116.3
116.3 121.9 105.0 133.6 84.0
112.7
112.7 117.4 103.0 128.6 82.2 108.9 108.9 112.7 101.0 123.4 80.4 105.0 105.0 107.9 98.9 117.8 78.0
90
122.3
122.3 123.5 122.3 133.8 100.7
118.6
118.6 118.7 118.7 128.8 98.7 114.7 114.7 114.8 114.8 123.7 96.8 110.7 110.7 110.8 110.8 118.3 94.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-5 — Gross Cooling Capacities (kW) TTA100A Condensing Unit with TWE100A Air Handler
(SI)
Ambient Temperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Entering Wet Bulb (°C)
m
3
/h
Bulb
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
24
30.7
23.9
33.9
20.1
37.4
13.7
29.5
23.3
32.7
19.6
36.0
13.2
28.3
22.7
31.4
19.0
34.6
12.7
27.1
22.1
30.0
18.5
33.1
12.2
5139
27
30.8
27.8
34.0
23.0
37.4
17.9
29.7
27.3
32.8
22.5
36.1
17.4
28.5
26.7
31.5
22.0
34.6
16.8
27.3
26.1
30.1
21.4
33.2
16.3
29
31.3
31.3
34.0
26.9
37.5
21.9
30.4
30.4
32.8
26.4
36.2
21.4
29.4
29.4
31.5
25.8
34.7
20.9
28.4
28.4
30.2
25.2
33.3
20.3
32
32.9
32.9
34.2
30.9
37.6
26.0
31.9
31.9
33.0
30.3
36.2
25.5
30.9
30.9
31.8
29.8
34.8
24.9
29.9
29.9
30.5
29.2
33.3
24.3
24
31.3
25.0
34.5
19.7
38.0
13.9
30.1
24.4
33.3
19.1
36.6
13.5
28.9
23.8
31.9
18.6
35.1
12.9
27.6
23.1
30.5
18.0
33.5
12.4
5692
27
31.5
29.3
34.6
24.0
38.1
18.5
30.3
28.7
33.4
23.5
36.7
17.9
29.2
28.1
32.0
23.0
35.2
17.4
27.9
27.5
30.6
22.3
33.7
16.8
29
32.3
32.3
34.7
28.3
38.1
22.9
31.4
31.4
33.4
27.7
36.8
22.3
30.3
30.3
32.1
27.1
35.3
21.8
29.3
29.3
30.7
26.5
33.8
21.3
32
34.0
34.0
34.9
32.6
38.2
27.2
33.0
33.0
33.7
32.0
36.8
26.6
31.9
31.9
32.4
31.4
35.3
26.1
30.9
30.9
31.1
30.9
33.8
25.5
24
31.8
26.0
35.1
20.3
38.5
14.2
30.6
25.4
33.7
19.7
37.0
13.7
29.3
24.8
32.4
19.2
35.5
13.2
28.0
24.1
30.9
18.6
33.9
12.6
6244
27
32.1
30.6
35.2
25.0
38.6
19.0
30.9
30.1
33.8
24.4
37.1
18.5
29.7
29.5
32.4
23.8
35.6
17.9
28.4
28.4
31.0
23.2
34.1
17.4
29
33.2
33.2
35.2
29.5
38.7
23.7
32.2
32.2
33.9
28.9
37.2
23.2
31.2
31.2
32.6
28.4
35.8
22.7
30.0
30.0
31.2
27.8
34.2
22.1
32
35.0
35.0
35.6
34.2
38.7
28.3
33.9
33.9
34.3
33.7
37.3
27.8
32.8
32.8
32.8
32.8
35.8
27.2
31.7
31.7
31.7
31.7
34.3
26.6
24
32.2
27.0
35.5
20.9
38.9
14.4
31.0
26.4
34.2
20.3
37.4
13.9
29.7
25.7
32.8
19.8
35.8
13.3
28.4
25.1
31.3
19.2
34.2
12.8
6796
27
32.6
32.0
35.6
25.8
39.0
19.5
31.5
31.4
34.2
25.2
37.5
19.0
30.2
30.2
32.8
24.6
36.0
18.4
29.1
29.1
31.4
24.0
34.4
17.9
29
34.0
34.0
35.7
30.7
39.1
24.6
33.0
33.0
34.4
30.2
37.7
24.1
31.9
31.9
33.0
29.6
36.1
23.5
30.7
30.7
31.6
29.0
34.5
22.8
32
35.8
35.8
36.2
35.8
39.2
29.5
34.7
34.7
34.8
34.8
37.7
28.9
33.6
33.6
33.6
33.6
36.2
28.3
32.4
32.4
32.4
32.4
34.6
27.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Performance
Data
System