27
SS-PRC003-EN
Performance
Data
System
Table PD-14 — Gross Cooling Capacities (MBh) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (I-P)
Ambient Temperature (°F)
85
95
105
115
Enter.
Dry
Entering Wet Bulb (°F)
CFM
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
Airflow
(°F)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
75
94.3
92.3 103.0 67.8 112.7 43.8
91.7
91.0
99.8
66.5 108.7 42.4
88.2
88.2
96.0
64.8 104.3 41.0
84.6
84.6
91.6
62.9
99.3
39.4
4500
80
99.4
99.4 103.6 87.7 113.5 63.2
96.8
96.8 100.4 86.4 109.6 61.8
93.7
93.7
96.6
84.8 105.3 60.1
90.0
90.0
92.3
83.0 100.6 58.3
85
105.3
105.3 105.4 105.4 114.2 83.1
102.5
102.5 102.6 102.6 110.4 81.7
99.2
99.2
99.3
99.3 106.1 80.1
95.4
95.4
95.5
95.5 101.4 78.3
90
111.3
111.3 111.5 111.5 114.8 103.2
108.4
108.4 108.5 108.5 111.2 101.9 104.9 104.9 105.0 105.0 107.0 100.3 100.9 100.9 101.0 101.0 102.3 98.5
75
95.8
95.8 104.2 72.0 113.7 43.9
93.3
93.3 100.9 70.8 109.5 42.6
90.1
90.1
97.0
69.3 105.0 41.1
86.4
86.4
92.5
65.6 100.0 39.5
5000
80
101.8
101.8 104.9 92.4 114.9 66.6
99.1
99.1 101.6 91.1 110.9 65.3
95.8
95.8
97.8
89.5 106.5 63.9
92.0
92.0
93.4
87.6 101.6 62.3
85
107.9
107.9 108.0 108.0 115.4 87.3
105.0
105.0 105.0 105.0 111.6 85.9 101.5 101.5 101.6 101.6 107.2 84.3
97.6
97.6
97.6
97.6 102.3 82.5
90
114.1
114.1 114.3 114.3 116.3 109.4
111.0
111.0 111.1 111.1 112.6 108.1 107.4 107.4 107.5 107.5 108.4 106.5 103.3 103.3 103.4 103.4 103.5 103.5
75
97.7
97.7 105.2 73.3 114.5 44.7
95.0
95.0 101.8 71.9 110.2 43.4
91.8
91.8
97.8
70.2 105.6 41.9
88.0
88.0
93.2
68.2 100.4 40.3
5500
80
103.8
103.8 106.0 97.0 115.8 69.3
101.0
101.0 102.7 95.6 111.8 68.0
97.6
97.6
98.8
94.0 107.3 66.5
93.6
93.6
94.4
92.1 102.4 64.9
85
110.1
110.1 110.2 110.2 116.4 91.5
107.0
107.0 107.1 107.1 112.5 90.0 103.4 103.4 103.5 103.5 108.1 88.4
99.4
99.4
99.4
99.4 103.1 86.5
90
116.5
116.5 116.6 116.6 117.6 115.4
113.3
113.3 113.4 113.4 113.5 113.5 109.5 109.5 109.6 109.6 109.7 109.7 105.3 105.3 105.4 105.4 105.5 105.5
75
99.3
99.3 106.0 75.9 115.1 45.5
96.6
96.6 102.6 74.5 110.7 44.1
93.2
93.2
98.5
72.7 106.1 42.6
89.3
89.3
93.9
70.7 100.8 41.0
6000
80
105.6
105.6 107.0 101.4 116.6 71.8
102.6
102.6 103.7 100.0 112.5 70.5
99.1
99.1
99.8
98.3 107.9 69.1
95.1
95.1
95.1
95.1 103.0 67.5
85
112.0
112.0 112.1 112.1 117.2 95.5
108.9
108.9 109.0 109.0 113.3 94.0 105.2 105.2 105.2 105.2 108.8 92.3 101.0 101.0 101.0 101.0 103.9 90.5
90
118.5
118.5 118.6 118.6 118.7 118.7
115.2
115.2 115.3 115.3 115.4 115.4 111.4 111.4 111.5 111.5 111.5 111.5 107.0 107.0 107.1 107.1 107.2 107.2
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-14 — Gross Cooling Capacities (kW) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (SI)
Ambient Temperature (°C)
29.4
35.0
40.6
46.1
Enter.
Dry
Entering Wet Bulb (°C)
m
3
/h
Bulb
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
16.1
19.4
22.8
Airflow
(°C)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
24
27.6
27.0
30.2
19.9
33.0
12.8
26.8
26.7
29.2
19.5
31.8
12.4
25.8
25.8
28.1
19.0
30.5
12.0
24.8
24.8
26.8
18.4
29.1
11.6
7646
27
29.1
29.1
30.3
25.7
33.2
18.5
28.4
28.4
29.4
25.3
32.1
18.1
27.4
27.4
28.3
24.8
30.8
17.6
26.3
26.3
27.0
24.3
29.4
17.1
29
30.8
30.8
30.9
30.9
33.4
24.3
30.0
30.0
30.1
30.1
32.3
23.9
29.1
29.1
29.1
29.1
31.1
23.4
27.9
27.9
28.0
28.0
29.7
22.9
32
32.6
32.6
32.6
32.6
33.6
30.2
31.7
31.7
31.8
31.8
32.6
29.8
30.7
30.7
30.7
30.7
31.3
29.4
29.6
29.6
29.6
29.6
30.0
28.9
24
28.0
28.0
30.5
21.1
33.3
12.9
27.3
27.3
29.6
20.7
32.1
12.5
26.4
26.4
28.4
20.3
30.8
12.0
25.3
25.3
27.1
19.2
29.3
11.6
8495
27
29.8
29.8
30.7
27.1
33.6
19.5
29.0
29.0
29.8
26.7
32.5
19.1
28.0
28.0
28.6
26.2
31.2
18.7
26.9
26.9
27.3
25.7
29.8
18.2
29
31.6
31.6
31.6
31.6
33.8
25.6
30.7
30.7
30.8
30.8
32.7
25.2
29.7
29.7
29.7
29.7
31.4
24.7
28.6
28.6
28.6
28.6
30.0
24.2
32
33.4
33.4
33.5
33.5
34.0
32.0
32.5
32.5
32.5
32.5
33.0
31.6
31.4
31.4
31.5
31.5
31.7
31.2
30.2
30.2
30.3
30.3
30.3
30.3
24
28.6
28.6
30.8
21.5
33.5
13.1
27.8
27.8
29.8
21.1
32.3
12.7
26.9
26.9
28.6
20.6
30.9
12.3
25.8
25.8
27.3
20.0
29.4
11.8
9345
27
30.4
30.4
31.0
28.4
33.9
20.3
29.6
29.6
30.1
28.0
32.7
19.9
28.6
28.6
28.9
27.5
31.4
19.5
27.4
27.4
27.6
27.0
30.0
19.0
29
32.2
32.2
32.3
32.3
34.1
26.8
31.3
31.3
31.4
31.4
32.9
26.4
30.3
30.3
30.3
30.3
31.6
25.9
29.1
29.1
29.1
29.1
30.2
25.3
32
34.1
34.1
34.1
34.1
34.4
33.8
33.2
33.2
33.2
33.2
33.2
33.2
32.1
32.1
32.1
32.1
32.1
32.1
30.8
30.8
30.9
30.9
30.9
30.9
24
29.1
29.1
31.0
22.2
33.7
13.3
28.3
28.3
30.0
21.8
32.4
12.9
27.3
27.3
28.8
21.3
31.1
12.5
26.1
26.1
27.5
20.7
29.5
12.0
10194
27
30.9
30.9
31.3
29.7
34.1
21.0
30.1
30.1
30.4
29.3
32.9
20.6
29.0
29.0
29.2
28.8
31.6
20.2
27.8
27.8
27.9
27.9
30.1
19.8
29
32.8
32.8
32.8
32.8
34.3
28.0
31.9
31.9
31.9
31.9
33.2
27.5
30.8
30.8
30.8
30.8
31.9
27.0
29.6
29.6
29.6
29.6
30.4
26.5
32
34.7
34.7
34.7
34.7
34.7
34.7
33.7
33.7
33.8
33.8
33.8
33.8
32.6
32.6
32.6
32.6
32.7
32.7
31.3
31.3
31.4
31.4
31.4
31.4
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity