8
Tips for a Successful Installation
IMPORTANT INSTALLATION INFORMATION
•
Read this Installation Manual to understand how all components are to
be located and properly installed.
•
The vehicle’s cargo area must be designed and built for refrigeration
applications with insulated walls, ceilings and floors. All cargo doors
must close and seal tightly.
•
The vehicle’s exterior roof must be able to adequately support the
combined weight of the rooftop mounted components. Additional
supports (installer supplied) may be required. See “Dimensions and
Weight - Model 50 SPECTRUM” on page 12.
Model 50 SPECTRUM Refrigeration, Power Pack and Condenser
Modules - approximate weight 86 kg (190 lbs.)
•
The vehicle’s interior ceiling must be able to adequately support the
weight of two (2) ES300 evaporators. Additional internal structural
supports (installer supplied) may be required. See “Dimensions and
Weight - ES300 Host Evaporator” on page 13.
ES300 HOST (Frozen Compartment) Evaporator - approximate
weight 18 kg (40 lbs.)
ES300 REMOTE (Fresh Compartment) Evaporator with
accumulator - approximate weight 33 kg (72 lbs.)
•
Thermo King recommends securely installing steel support plates with
mounting studs or threaded inserts (installer supplied) to the truck’s
interior roof structure to mount the V-520 RT refrigeration module,
condenser module and the ES500 evaporator prior to insulating and
finishing the cargo area.
ES300 HOST - Allow a minimum distance of 152 mm (6.00 in.)
from the cargo area wall to the rear of the evaporator for refrigerant
hose and drain hose connections.
ES300 REMOTE - Allow a minimum distance of 152 mm
(6.00 in.) from the cargo area wall to the rear of the accumulator
assembly for refrigerant hose and drain hose connections.
•
The V-520 RT must be installed with the refrigeration module facing
towards the front of the vehicle.
•
Verify tools and special equipment required for the installation are
available and in good operating condition before beginning the
installation.
•
Verify all measurements before drilling holes in vehicle.
•
Verify there is no interference with OEM electrical wiring, internal
supports, etc. before drilling holes in vehicle.
•
Provide protection to vehicle's finish to prevent damage during the
installation process.
•
Install all components using the correct hardware for your particular
application and tighten securely.
•
All access holes through the cargo area must be sealed with a neutral/
alcohol cure silicone sealant to prevent moisture from entering and air
from escaping.
•
Always use protective grommets when routing electrical harnesses or
refrigeration hoses through sheet metal floors or walls.
•
Always keep electrical harness and refrigeration hoses from rubbing or
chafing against sharp metal objects or rotating components.
•
The fabrication and installation (by the installer) of protective covers
for any exposed refrigerant hoses, drain hoses and electrical wiring
inside or outside the cargo area is recommended.
•
Verify the air outlet of each ES300 evaporator is facing the correct
direction for proper airflow before installing.
•
ES300 evaporator drain hoses should be installed and routed correctly
with no kinks or sharp bends to provide for proper drainage.
REFRIGERATION HOSES
•
Always keep refrigeration system fittings capped and sealed until the
installation of the refrigeration hoses.
•
Only cut refrigerant hoses with the correct hose cutting tool (204-677).
NEVER USE A SAW!
•
Always use the correct hose fitting tool (204-1045 or 204-1128) when
assembling refrigerations hoses.
Содержание Thermo King ES300
Страница 12: ...11 Required Tools ...
Страница 18: ...17 Dimensions Condenser Module Mounting Holes ...
Страница 19: ...18 Dimensions HMI A 140 mm 5 50 in B 46 mm 1 80 in C 12 mm 50 in ...
Страница 20: ...19 BLANK PAGE ...
Страница 24: ...23 Installation 2 ES300 Evaporators Alternative Installation Method Preferred Installation Method ...
Страница 26: ...25 Installation Refrigeration Module Alternative Installation Method Preferred Installation Method ...
Страница 28: ...27 Installation Power Pack Module Alternative Installation Method Preferred Installation Method ...
Страница 30: ...29 Installation Condenser Module Preferred Installation Method Alternative Installation Method ...
Страница 38: ...37 Important Suction Line Routing and P Trap Formation NOT ACCEPTABLE From Unit ...
Страница 40: ...39 Installation Refrigeration Tubes to Compressor ...
Страница 46: ...45 System Leak Check and Evacuation ...
Страница 48: ...47 Installation Electrical Connections ...
Страница 50: ...49 Electrical Connections Evaporator s ...
Страница 52: ...51 Installation Standby Power Receptacle ...
Страница 54: ...53 Installation Drain Hoses REMOTE Evaporator HOST Evaporator Defrost Heater Wires ...
Страница 56: ...55 Installation HMI ...
Страница 62: ...61 System Charging AMOUNT OF REFRIGERANT PER MODEL Model 50 5 00 lbs ...