background image

RLC-SVX19J_SHORT-GB

7

Installation Requirements

Installation Responsibilities

Generally contractor must do the following items when 
installing an RTAF unit:

1. 

Install the unit on a fl at foundation strong enough to 
support unit loading and level (within 5 mm across 
the length and width of the unit).

2.  Install the units as per instructions contained in this 

manual.

3. Where 

specifi ed, provide and install valves in 

the water piping upstream and downstream of 
the evaporator water connections, to isolate the 
evaporator for maintenance, and to balance and trim 
the system.

4.  Furnish and install a water fl ow prove device and/or 

auxiliary contacts to prove chiller water fl ow.

5.  Furnish and install water pressure gauges in the inlet 

and outlet of the evaporator water box.

6.  Supply and install an air vent cock to the top of the 

evaporator water box.

7. 

Furnish and install strainers ahead of all pumps and 
automatic modulating valves.

8.  Provide and install fi eld wiring according to 

schematics provided in the control panel.

9.  Install heat tape and insulate the chilled water lines 

and any other portion of the system, as required, to 
prevent sweating under normal operating conditions 
or freezing during low ambient temperature 
conditions.

10.  Ensure that the compressor and oil separator 

heaters have been operating for a minimum of 
24 hours before starting. Failure to do so may 
result in equipment damage.

11.  Start the unit under supervision of a qualifi ed service 

technician.

Nameplates

The RTAF outdoor unit nameplates are applied to the 
exterior of the control panel. A compressor nameplate is 
located on each compressor.

Unit Nameplate

The unit nameplate provides the following information:

• 

Unit model and size description

• 

Unit serial number

• Identifi es unit electrical requirements

• 

Lists correct operating charges of R-134a and 
refrigerant oil 

• 

Lists unit test pressures

Compressor Nameplate

The compressor nameplate provides following 
information:

• 

Compressor model number.

• 

Compressor serial number.

• 

Compressor electrical characteristics.

• Utilization 

range

• Recommended 

refrigerant

Storage

 

Extended storage of the unit prior to the installation 
requires the following precautions:

1. 

Store the unit in a secured area, to avoid intentional 
damages.

2.  Close the suction, discharge and liquid-line isolation 

valves.

3.  At least every three months, connect a gauge and 

manually check the pressure in the refrigerant circuit. 
If the refrigerant pressure is below 13 Bar at 20°C (or 
10 Bar at 10°C), call a qualifi ed service organization 
and the appropriate Trane sales offi ce.

Note: 

if the unit is stored before servicing near a 

construction site it is highly recommended to protect 
micro channel coils from any concrete and iron element. 
Failure to do so may considerably reduce reliablity of 
the unit.

Lifting and Moving Instructions

A specifi c lifting method is recommended, which can be 
described as follow:

1. 

Lifting points are built into the unit, see lifting 
instruction label on the unit.

2.  Slings and spreader bar must be provided by crane 

operator and attached on the lifting points.

3.  Use the 4 or 8 rigging points (according to unit size) 

which are built into the unit.

4.  The minimum lifting capacity of each sling as well as 

the spreader bar must be higher than the tabulated 
unit shipping weight.

5.  CAUTION! Lift and handle with care. Avoid shocks 

while handling.

Содержание Sintesis RTAF HE

Страница 1: ...kW July 2020 Confidential and proprietary Trane information Original instructions Sintesis chillers are part of theTraneTechnologies EcoWise portfolio of products that are designed to lower their envi...

Страница 2: ...er to the general sales conditions of your localTRANE sales office Note Unit inspection in France Delay to send registered letter in case of visible and concealed damage is only 72 hours Loose Parts I...

Страница 3: ...e shipment Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur after delivery Noti...

Страница 4: ...n relays and wiring Water piping Flow switch Taps for thermometers and gauges Thermometers Water flow pressure gauges Isolation and balancing valves in water piping Vents and drain Waterside pressure...

Страница 5: ...sonal Short XSS Digit 13 Agency listing C CE Marking Digit 14 Pressure vessel code 2 PED Pressure equipment directive D Australian code Digit 15 Acoustic level X Standard noise SN L Low noise LN A AC...

Страница 6: ...stant delta P T Variable Speed Pump Constant deltaT Digit 38 Open for future use X Digit 39 Open for future use X Digit 40 Power socket X None P Included 230V 100W Digit 41 Factory tests X No final pe...

Страница 7: ...ssor nameplate is located on each compressor Unit Nameplate The unit nameplate provides the following information Unit model and size description Unit serial number Identifies unit electrical requirem...

Страница 8: ...ed for operation maintenance panel access and airflow NO OBSTRUCTIONS ABOVE UNIT 2 For installations with obstructions or multiple units refer toTrane office for Close Spacing and Restricted Airflow a...

Страница 9: ...ting bolts at this time See the isolators submittals for isolators location maximum weights and isolators diagrams 2 Align the mounting holes in the base of the unit with the threaded positioning pins...

Страница 10: ...l freeze To avoid free cooling coil damage If the building loop needs to be charged with water for testing purposes isolate free cooling coils by closing free cooling service shut off valve and modula...

Страница 11: ...eliminators Shutoff isolation valves Thermometers if desired temperature readings available on chiller controller display Clean out tees Pipe strainer Pi Pressure gauge FT Water Flow Switch T1 Evapor...

Страница 12: ...terbox prevents vacuum by removing air from evaporator for complete drainage Drain connections and vents are also provided on header pipes for use when free cooling option Evaporator configuration var...

Страница 13: ...essure Relief Valves Install a water pressure relief valve in the evaporator inlet piping between evaporator and the inlet shutoff valve Water vessels with close coupled shutoff valves have high poten...

Страница 14: ...valve Temperature sensor Note A pressure switch device to detect lack of water is not included in the pump package Installation of this type of device is highly recommended to avoid sealing damage due...

Страница 15: ...conditions It may vary from 30 C to 61 C For details performance consult Order Write Up Flow switch The flow switch is fitted on water line to monitor a to low water flow through theTotal Heat Recover...

Страница 16: ...e cooling will be enabled whenever the outdoor temperature is below the evaporator entering water temperature The operating logic is described below The free cooling system operates combined with the...

Страница 17: ...ree Cooling Figure 8 Flow chart Free Cooling Direct free cooling version Note glycol free cooling chilled water setpoint should be in the range of 4 C 20 C Water Glycol mixture is filled on the free c...

Страница 18: ...e Cooling offset is an adjustable parameter to make free cooling active If free cooling function is enabled free cooling becomes the 1st stage of cooling Free cooling is the first stage to engage for...

Страница 19: ...the customer and installed at the unit inlet Unit is shipped without glycol content on the free cooling circuit Free cooling loop venting must be performed by using Manual override mode to run the fre...

Страница 20: ...Direct Free Cooling option Glycol percentage should be based on freeze avoidance requirements The glycol solution requires an inhibitor package to be carefully chosen with the aid of a qualified water...

Страница 21: ...during monthly maintenance operation when free cooling is continuously OFF to avoid possible glycol cristalization Pump Override function is located inTD7 via Button Settings Manual Control Settings...

Страница 22: ...endent on past running conditions and present temperature measured ON if entering OR leaving water temperature LWTC for 16 2 C sec OFF again if water temperature LWTC for 30 min OR 2 Freeze inhibitor...

Страница 23: ...see Adaptive Frequency Drive AFD3 Capacitor Discharge and BAS SVX19B E4 Hazardous Voltage Pressurized Burning Fluid Before removing compressor terminal box cover for servicing or servicing power side...

Страница 24: ...mps Starting Amps of the largest compr RLA of 2nd compr RLA of all fans control Compressor Power factor Disconnect switch size A Short Circuit Rating for all sizes 35 kA For the control of every unit...

Страница 25: ...Supply The evaporator shell is insulated from ambient air and protected from freezing for temperature down to 20 C by two thermostatically controlled immersion heaters combined with evaporator pumps a...

Страница 26: ...Installer Supplied Components Alarm and Status Relay Outputs Programmable Relays See RTAF User Guide for alarm and status relay outputs EDLS and ECWS Analog Input Signal Wiring Details See RTAF User G...

Страница 27: ...e service valve 9 Liquid shut off valve 10 Filter drier 11 Electronic expansion valve 12 Sight glass 13 Relief valve 14 Service valve 15 Oil line solenoid valve 16 Oil filter 17 Suction service valve...

Страница 28: ...ndensed inside the microchannel states 2b to 3b Refrigerant flow through the system is balanced by an electronic expansion valve states 3b to 4 Refrigerant Cycle with Economizer Liquid refrigerant eit...

Страница 29: ...crochannel tubes and two refrigerant manifolds Coils can be cleaned with high pressure water see Condenser Coils MCHE maintenance for instructions The condenser coil has an integral subcooling circuit...

Страница 30: ...s specific information you need on a day to day basis like setpoints limits diagnostic information and reports Day to day operational information is presented at the display Logically organized groups...

Страница 31: ...air temperature based on wind speed lower than 2m s Maximum ambient operation is for unit at 12 C 7 C operating conditions It is not possible to have a unit operating low and high ambient For specifi...

Страница 32: ...n 10 Reapply power to complete the procedures 11 Prove all Interlock and Interconnecting Wiring Interlock and External as described in the Electrical Installation section 12 Check and set as required...

Страница 33: ...is will damage the shaft seal Always fill the system with diluted solution Maximum concentration of glycol is 45 for unit with pump package If the chiller is installed in a humid environment or a loca...

Страница 34: ...user guide for instruction on settings CAUTION To prevent compressor damage do not operate the unit until all refrigerant valves and oil line service valves are opened IMPORTANT A clear sight glass a...

Страница 35: ...that is stuck open A restriction in the line can sometimes be identified by a noticeable temperature differential between the two sides of the restriction Frost will often form on the line at this poi...

Страница 36: ...ot contain glycol to prevent any risk of evaporator freeze up Refer to charts 1 and 2 Extended Shutdown Procedure The following procedure is to be followed if the system is to be taken out of service...

Страница 37: ...llowing recommendedTrane operation maintenance and service procedures with specific attention to the following 1 Refrigerant used in any type of air conditioning or refrigerating equipment should be r...

Страница 38: ...peration water fl ow to be within allowed operating range A fully loaded chiller is highly recommended for a successful operation In case the technician is not able to ensure a 2 circuit fully loaded...

Страница 39: ...see general data table 9 Install the new filter element in the filter housing 10 Inspect the flange gasket and replace it with a new one if damaged 11 Install the flange and torque the bolts to 19 22...

Страница 40: ...the need for oil charge 1 Some services procedures may result in loss of small quantities of oil that must be replaced oil analysis compressor filter replacement re tubing the evaporator and so forth...

Страница 41: ...the required amount of oil into the unit Note the compressor filter has an internal shutoff valve that will prevent oil from entering the compressor while the compressor is not running Therefore there...

Страница 42: ...a service valve on the suction line and on the evaporator Use these valves to vacuum the compressor 10 Open the oil line shutoff valve Sever damage to the compressor can result if the oil line shutof...

Страница 43: ...ing remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized Failure to disconnect power before servicing could result in death...

Страница 44: ...r must be cleaned and checked regularly Lubrication The pump shaft seal does not require any special maintenance Visual leakage check are however required Distinctly visible leakage will require an ex...

Страница 45: ...1A Running Status Starts Running Time Hr min Oil Pressure kPa Compressor 1B Running Status Starts Running Time Hr min Oil Pressure kPa Motor 1A Active Demand Limit Setpoint Average Motor Current Perc...

Страница 46: ...x x x x xxx 7 x x x x x xxx 8 x x x x x xxx 9 x x x x x xxx 10 x x x x x xxx x over 10 every year every year every year 2 x every year 3 every year every 3 years 40 000 h This timetable is applicable...

Страница 47: ...e period designated The inspections will be conducted at agreed upon intervals andTrane Service First will submit a written report to the customer after each inspection These reports will indicate any...

Страница 48: ...n please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice We are...

Отзывы: