RLC-SVX19J_SHORT-GB

41

Periodic Maintenance

Figure 18 GP2 Compressor

Figure 19: GP4 Compressor

Remaining Oil Charge

1. 

Add 0.95 litres (0.9kg) of oil to the motor cavity or 
suction line prior to installing the compressor into 
the chiller.

2.  If the unit is not equipped with suction-line isolation 

valves, it should contain no charge. If it has isolation 
valves, then the charge may be trapped in the 
evaporator. In either case, the high side of the system 
should not be pressurized.

3.  The oil-line shutoff valve must be open to allow the 

oil to pass into the oil lines and the oil separator.

4.  The oil charging port is a 6mm (¼”) fl are fi tting with 

a schraeder valve that is on the side of the oil fi lter 
housing. This is the port that must be used to add oil 
into the compressor so that the fi lter and lines are full 
at the fi rst start of the compressor.

5.  On single-compressor circuits, all the oil should be 

put into the circuit through the oil-charging port on 
the compressor fi lter housing. On two-compressor 
circuits, put approximately ½ of the oil into the unit 
through each of the two oil-charging ports on the two 
compressors.

6.  Oil may be put into the unit using either of two 

methods:

• Have the unit in vacuum. Note that the vacuum 

connection should be made on the unit at the 
service valve that is on the discharge line. 
Hook up one end of the oil-charging fi tting and 
immerse the other end into the oil container. Let 
the vacuum draw the required amount of oil into 
the unit

• Have the unit at the same pressure as the oil. 

Hook up one end of the oil-charging hose to the 
oil charging fi tting and the other end to an oil 
pump. Use the pump to the draw oil out of the 
oil container and push the required amount of oil 
into the unit 

Note: 

the compressor fi lter has an internal shutoff valve 

that will prevent oil from entering the compressor while 
the compressor is not running. Therefore, there is no 
concern about fl ooding the compressor with oil.

 

CAUTION!

 Use only Trane Oil 00048E in RTAF SE HE 

and XE chillers and Trane OIL 00317 for HSE version in 
the RTAF units to avoid any catastrophic damage to the 
compressor or unit. Deduct from fi nal charge, all charge 
added for prelubrifi cation to avoid over-charging.

Field Oil-Charging Procedure

Use the initial charging procedure under the following 
circumstances;

• When virtually all of the oil has been removed

• If the oil charge is removed from the compressor 

and oil system only, and the unit has been run for 
more than 15 minutes 

• If the oil charge is removed from the compressor 

and oil system only, and the unit has been run 
for more than 15 minutes. However, reduce the 
amount of oil added to the unit by the normal 
quantity of oil in the refrigeration system 

Note: 

this procedure can be followed event with the 

refrigerant charge isolated in the evaporating section of 
the unit.

If small quantities of oil were removed to service 
refrigeration components,

 such as the evaporator, 

replace the oil that was removed back into the serviced 
component prior to vacuum and recharge of the 
refrigerant.

If oil was removed to service a compressor or change 
the fi lter

 follow this procedure:

1. 

If the compressor is a new compressor or has 
been removed from the system and reworked, add 
0.95 litre (0.90kg) of oil to the motor cavity prior to 
installing the compressor into the chiller.

2.  Install the compressor in the system. Make sure that 

the fi lter shutoff valve is closed. Other compressor 
isolation valves may also be closed depending 
upon the service that was completed. For example, 
changing the oil fi lter would require the compressor 

Содержание Sintesis RTAF HE

Страница 1: ...kW July 2020 Confidential and proprietary Trane information Original instructions Sintesis chillers are part of theTraneTechnologies EcoWise portfolio of products that are designed to lower their envi...

Страница 2: ...er to the general sales conditions of your localTRANE sales office Note Unit inspection in France Delay to send registered letter in case of visible and concealed damage is only 72 hours Loose Parts I...

Страница 3: ...e shipment Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur after delivery Noti...

Страница 4: ...n relays and wiring Water piping Flow switch Taps for thermometers and gauges Thermometers Water flow pressure gauges Isolation and balancing valves in water piping Vents and drain Waterside pressure...

Страница 5: ...sonal Short XSS Digit 13 Agency listing C CE Marking Digit 14 Pressure vessel code 2 PED Pressure equipment directive D Australian code Digit 15 Acoustic level X Standard noise SN L Low noise LN A AC...

Страница 6: ...stant delta P T Variable Speed Pump Constant deltaT Digit 38 Open for future use X Digit 39 Open for future use X Digit 40 Power socket X None P Included 230V 100W Digit 41 Factory tests X No final pe...

Страница 7: ...ssor nameplate is located on each compressor Unit Nameplate The unit nameplate provides the following information Unit model and size description Unit serial number Identifies unit electrical requirem...

Страница 8: ...ed for operation maintenance panel access and airflow NO OBSTRUCTIONS ABOVE UNIT 2 For installations with obstructions or multiple units refer toTrane office for Close Spacing and Restricted Airflow a...

Страница 9: ...ting bolts at this time See the isolators submittals for isolators location maximum weights and isolators diagrams 2 Align the mounting holes in the base of the unit with the threaded positioning pins...

Страница 10: ...l freeze To avoid free cooling coil damage If the building loop needs to be charged with water for testing purposes isolate free cooling coils by closing free cooling service shut off valve and modula...

Страница 11: ...eliminators Shutoff isolation valves Thermometers if desired temperature readings available on chiller controller display Clean out tees Pipe strainer Pi Pressure gauge FT Water Flow Switch T1 Evapor...

Страница 12: ...terbox prevents vacuum by removing air from evaporator for complete drainage Drain connections and vents are also provided on header pipes for use when free cooling option Evaporator configuration var...

Страница 13: ...essure Relief Valves Install a water pressure relief valve in the evaporator inlet piping between evaporator and the inlet shutoff valve Water vessels with close coupled shutoff valves have high poten...

Страница 14: ...valve Temperature sensor Note A pressure switch device to detect lack of water is not included in the pump package Installation of this type of device is highly recommended to avoid sealing damage due...

Страница 15: ...conditions It may vary from 30 C to 61 C For details performance consult Order Write Up Flow switch The flow switch is fitted on water line to monitor a to low water flow through theTotal Heat Recover...

Страница 16: ...e cooling will be enabled whenever the outdoor temperature is below the evaporator entering water temperature The operating logic is described below The free cooling system operates combined with the...

Страница 17: ...ree Cooling Figure 8 Flow chart Free Cooling Direct free cooling version Note glycol free cooling chilled water setpoint should be in the range of 4 C 20 C Water Glycol mixture is filled on the free c...

Страница 18: ...e Cooling offset is an adjustable parameter to make free cooling active If free cooling function is enabled free cooling becomes the 1st stage of cooling Free cooling is the first stage to engage for...

Страница 19: ...the customer and installed at the unit inlet Unit is shipped without glycol content on the free cooling circuit Free cooling loop venting must be performed by using Manual override mode to run the fre...

Страница 20: ...Direct Free Cooling option Glycol percentage should be based on freeze avoidance requirements The glycol solution requires an inhibitor package to be carefully chosen with the aid of a qualified water...

Страница 21: ...during monthly maintenance operation when free cooling is continuously OFF to avoid possible glycol cristalization Pump Override function is located inTD7 via Button Settings Manual Control Settings...

Страница 22: ...endent on past running conditions and present temperature measured ON if entering OR leaving water temperature LWTC for 16 2 C sec OFF again if water temperature LWTC for 30 min OR 2 Freeze inhibitor...

Страница 23: ...see Adaptive Frequency Drive AFD3 Capacitor Discharge and BAS SVX19B E4 Hazardous Voltage Pressurized Burning Fluid Before removing compressor terminal box cover for servicing or servicing power side...

Страница 24: ...mps Starting Amps of the largest compr RLA of 2nd compr RLA of all fans control Compressor Power factor Disconnect switch size A Short Circuit Rating for all sizes 35 kA For the control of every unit...

Страница 25: ...Supply The evaporator shell is insulated from ambient air and protected from freezing for temperature down to 20 C by two thermostatically controlled immersion heaters combined with evaporator pumps a...

Страница 26: ...Installer Supplied Components Alarm and Status Relay Outputs Programmable Relays See RTAF User Guide for alarm and status relay outputs EDLS and ECWS Analog Input Signal Wiring Details See RTAF User G...

Страница 27: ...e service valve 9 Liquid shut off valve 10 Filter drier 11 Electronic expansion valve 12 Sight glass 13 Relief valve 14 Service valve 15 Oil line solenoid valve 16 Oil filter 17 Suction service valve...

Страница 28: ...ndensed inside the microchannel states 2b to 3b Refrigerant flow through the system is balanced by an electronic expansion valve states 3b to 4 Refrigerant Cycle with Economizer Liquid refrigerant eit...

Страница 29: ...crochannel tubes and two refrigerant manifolds Coils can be cleaned with high pressure water see Condenser Coils MCHE maintenance for instructions The condenser coil has an integral subcooling circuit...

Страница 30: ...s specific information you need on a day to day basis like setpoints limits diagnostic information and reports Day to day operational information is presented at the display Logically organized groups...

Страница 31: ...air temperature based on wind speed lower than 2m s Maximum ambient operation is for unit at 12 C 7 C operating conditions It is not possible to have a unit operating low and high ambient For specifi...

Страница 32: ...n 10 Reapply power to complete the procedures 11 Prove all Interlock and Interconnecting Wiring Interlock and External as described in the Electrical Installation section 12 Check and set as required...

Страница 33: ...is will damage the shaft seal Always fill the system with diluted solution Maximum concentration of glycol is 45 for unit with pump package If the chiller is installed in a humid environment or a loca...

Страница 34: ...user guide for instruction on settings CAUTION To prevent compressor damage do not operate the unit until all refrigerant valves and oil line service valves are opened IMPORTANT A clear sight glass a...

Страница 35: ...that is stuck open A restriction in the line can sometimes be identified by a noticeable temperature differential between the two sides of the restriction Frost will often form on the line at this poi...

Страница 36: ...ot contain glycol to prevent any risk of evaporator freeze up Refer to charts 1 and 2 Extended Shutdown Procedure The following procedure is to be followed if the system is to be taken out of service...

Страница 37: ...llowing recommendedTrane operation maintenance and service procedures with specific attention to the following 1 Refrigerant used in any type of air conditioning or refrigerating equipment should be r...

Страница 38: ...peration water fl ow to be within allowed operating range A fully loaded chiller is highly recommended for a successful operation In case the technician is not able to ensure a 2 circuit fully loaded...

Страница 39: ...see general data table 9 Install the new filter element in the filter housing 10 Inspect the flange gasket and replace it with a new one if damaged 11 Install the flange and torque the bolts to 19 22...

Страница 40: ...the need for oil charge 1 Some services procedures may result in loss of small quantities of oil that must be replaced oil analysis compressor filter replacement re tubing the evaporator and so forth...

Страница 41: ...the required amount of oil into the unit Note the compressor filter has an internal shutoff valve that will prevent oil from entering the compressor while the compressor is not running Therefore there...

Страница 42: ...a service valve on the suction line and on the evaporator Use these valves to vacuum the compressor 10 Open the oil line shutoff valve Sever damage to the compressor can result if the oil line shutof...

Страница 43: ...ing remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized Failure to disconnect power before servicing could result in death...

Страница 44: ...r must be cleaned and checked regularly Lubrication The pump shaft seal does not require any special maintenance Visual leakage check are however required Distinctly visible leakage will require an ex...

Страница 45: ...1A Running Status Starts Running Time Hr min Oil Pressure kPa Compressor 1B Running Status Starts Running Time Hr min Oil Pressure kPa Motor 1A Active Demand Limit Setpoint Average Motor Current Perc...

Страница 46: ...x x x x xxx 7 x x x x x xxx 8 x x x x x xxx 9 x x x x x xxx 10 x x x x x xxx x over 10 every year every year every year 2 x every year 3 every year every 3 years 40 000 h This timetable is applicable...

Страница 47: ...e period designated The inspections will be conducted at agreed upon intervals andTrane Service First will submit a written report to the customer after each inspection These reports will indicate any...

Страница 48: ...n please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice We are...

Отзывы: