Optional Free-Cooling
Glycol Free-cooling
Free-Cooling Bypass Valve Settings
Position 1:
0% - Closed – Free-cooling
Position 2:
10%
Position 3:
20%
…..
Position 10: 100% - Fully Open – No Free-cooling
Open position:
Water flow is directed to evaporator and
there will not be any free-cooling.
Closed position:
All the water flow is directed to free-
cooling exchanger or de coupling bottle. In Free-cooling
mode water flow will see highest pressure drop.
Slightly open:
0% to 30% will direct the some portion of
water through free-cooling exchanger and the remaining
to evaporator.
Refer the settings table for more details.
Table 18 – Direct Free-Cooling Setting
DIRECT FC
80
90
100
110
130
140
150
165
180
190
% Open
0%
0%
0%
0%
20%
30%
30%
30%
40%
40%
Position
1/2*
1/2
1/2
1/2
3
4
4
4
5
5
Table 19 – Glycol Free Free-Cooling Setting
DIRECT FC
80
90
100
110
130
140
150
165
180
190
% Open
0%
0%
0%
0%
20%
20%
20%
30%
30%
30%
Position
1/2
1/2
1/2
1/2
3
3
4
4
4
4
Note for maintenance:
Check glycol circuit pressure before free-cooling operation season starts. Run glycol pump
few minutes in manual override during monthly maintenance operation when free-cooling is continuously OFF to
avoid possible glycol crystallization. Pump Override function is located in TD7 via Button Settings -> Manual Control
Settings -> Free-cooling Pump Override.
Содержание Sintesis Advantage CGAF 100 SE
Страница 34: ...34 CG SVX039C GB Top view Typical CGAF CXAF Components location ...
Страница 35: ...CG SVX039C GB 35 Typical CGAF CXAF Components location ...
Страница 36: ...36 CG SVX039C GB Typical CGAF CXAF Components location ...
Страница 85: ......
Страница 86: ......
Страница 87: ......