![Trane Sintesis Advantage CGAF 100 SE Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/trane/sintesis-advantage-cgaf-100-se/sintesis-advantage-cgaf-100-se_installation-operation-and-maintenance_1149706026.webp)
26
CG-SVX039C-GB
CXAF
CXAF
CXAF
CXAF
CXAF
CXAF
130
140
150
165
180
190
SE
SE
SE
SE
SE
SE
Twin pump - Standard head pressure option
Max available Head Pressure
(kPa)
157
141
143
182
163
154
Motor Power
(kW)
7.5
7.5
7.5
11
11
11
Rated Amps
(A)
14.4
14.4
14.4
20.8
20.8
20.8
Twin pump - High head pressure option
Max available Head Pressure
(kPa)
232
252
258
249
230
221
Motor Power
(kW)
11
15
15
15
15
15
Rated Amps
(A)
20.8
28
28
28
28
28
Expansion Tank Volume
(l)
50
50
50
50
50
50
Max User water loop Volume for factory
mounted expansion tank (1)
(l)
1750
1750
1750
1750
1750
1750
Optional water Buffer tank volume
(l)
607
777
777
777
777
777
Antifreeze Heater without pump package
and without buffer tank
(W)
520
640
640
640
640
640
Antifreeze Heater with pump package and
without buffer tank (Single Water Pump
digit 24=2 or 4 / Dual Water Pump digit
24=1 or 3)
(W)
1060 / 1220
1340 / 1400
1340 / 1400
1340 / 1400
1340 / 1400
1340 / 1400
Antifreeze Heater with pump package
and with buffer tank (Single Water Pump
digit 24=2 or 4 / Dual Water Pump digit
24=1 or 3)
(W)
2040 / 2100
2790/ 2850
2790/ 2850
2790/ 2850
2790/ 2850
2790/ 2850
Condenser
Type
Fin-tube heat exchanger
Quantity of coil
#
8
10
10
10
12
12
Face area per circuit
(m²)
9.29
11.61
11.61
11.61
13.93
13.93
Condenser Fan
Quantity
#
8
10
10
10
12
12
Diameter
(mm)
800
800
800
800
800
800
Digit 56=1
#
Fan / motor Type
#
#
#
#
#
#
#
Airflow per fan
m3/h
17976
18047
18010
17966
18018
17980
Max Power Input per Motor
Kw
1.4
1.4
1.4
1.4
1.4
1.4
Max Amps per Motor
A
2.8
2.8
2.8
2.8
2.8
2.8
Motor RPM
(rpm)
900
900
900
900
900
900
Digit 56=2
#
Fan / motor Type
#
#
#
#
#
#
#
Airflow per fan
m3/h
18983
17562
18378
18974
17959
18987
Max Power Input per Motor
Kw
1.55
1.55
1.55
1.55
1.55
1.55
Max Amps per Motor
A
2.5
2.5
2.5
2.5
2.5
2.5
Motor RPM
(rpm)
950
880
920
950
900
950
Digit 56 =3
#
Fan / motor Type
#
#
#
#
#
#
#
Airflow per fan
m3/h
19201
17868
18533
19191
18307
19204
Max Power Input per Motor
Kw
1.82
1.82
1.82
1.82
1.82
1.82
Max Amps per Motor
A
2.9
2.9
2.9
2.9
2.9
2.9
Motor RPM
(rpm)
880
820
850
880
840
880
Dimensions
Unit Length
(mm)
4520
5645
5645
5645
6770
6770
Unit Width
(mm)
2200
2200
2200
2200
2200
2200
Std Unit Height
(mm)
2526
2526
2526
2526
2526
2526
Pump Package Option - (Additional length
configuration)
(mm)
562
562
562
562
562
562
Weights (6)
Shipping Weight (6)
(kg)
3141
3768
3944
3984
4438
4507
Option Additional shipping weight (6)
#
Single pump - Standard head pressure
(kg)
264
287
287
351
401
401
Single pump - High head pressure
(kg)
301
363
363
363
413
413
Twin pump - Standard head pressure
(kg)
363
386
386
495
545
545
Twin pump - High head pressure
(kg)
425
521
521
521
571
571
XLN option
(kg)
114
145
145
145
145
145
Pump VFD option
(kg)
70
70
70
70
70
70
Water Buffer tank option
(kg)
286
379
379
379
379
379
Table 6 – General data CXAF 130 -190 Standard Efficiency (continued)
General Data
Содержание Sintesis Advantage CGAF 100 SE
Страница 34: ...34 CG SVX039C GB Top view Typical CGAF CXAF Components location ...
Страница 35: ...CG SVX039C GB 35 Typical CGAF CXAF Components location ...
Страница 36: ...36 CG SVX039C GB Typical CGAF CXAF Components location ...
Страница 85: ......
Страница 86: ......
Страница 87: ......