CG-SVX039C-GB
19
Table 4 – General data CGAF 090-150 Standard Efficiency – Shell & Tube
CGAF
CGAF
CGAF
CGAF
CGAF
CGAF
90
100
110
130
140
150
SE
SE
SE
SE
SE
SE
Net Cooling Capacity (1)
(kW)
322.4
352.4
390.9
425.0
494.5
522.5
Net Total Power input in cooling (1)
(kW)
101.8
116.1
133.6
153.1
163.8
179.0
Unit electrical data (1) (2) (3) (4)
Short Circuit Unit Capacity
(kA)
15
15
15
15
15
15
Power Cable Cross Section (max)
mm²
1*240
1*240
1*240
1*240
2*300
2*300
Disconnect switch size
(A)
400
400
500
500
630
630
Digit 56=1
Maximum Power input
(kW)
142.0
161.1
175.3
189.5
220.8
240.0
Unit rated amps
(A)
233.4
261.9
289.7
317.5
360.6
389.1
Unit start up amps (w/o soft starter - digit 54=A)
(4)
(A)
466.6
495.1
628.0
655.8
593.8
622.3
Unit start up amps (with soft starter - Digit 54=B)
(4)
(A)
349.0
377.5
462.8
490.6
476.2
504.7
Displacement power factor (dpf)
(dpf)
0.88
0.89
0.87
0.86
0.88
0.89
Digit 56=2
Maximum Power input
(kW)
142.9
162.0
176.2
190.4
222.0
241.2
Max. amps
(A)
231.6
260.1
287.9
315.7
358.2
386.7
Unit start up amps (w/o soft starter - Digit 54=A)
(4)
(A)
464.8
493.3
626.2
654.0
591.4
619.9
Unit start up amps (with soft starter - Digit 54=B)
(4)
(A)
347.2
375.7
461.0
488.8
473.8
502.3
Displacement power factor (dpf)
(dpf)
0.89
0.90
0.88
0.87
0.89
0.90
Digit 56=3
Maximum Power input
(kW)
144.5
163.6
177.9
192.1
224.2
243.3
Max. amps
(A)
234.0
262.5
290.3
318.1
361.4
389.9
Unit start up amps (w/o soft starter - Digit 54=A)
(4)
(A)
467.2
495.7
628.6
656.4
594.6
623.1
Unit start up amps (with soft starter - Digit 54=B)
(4)
(A)
349.6
378.1
463.4
491.2
477.0
505.5
Displacement power factor (dpf)
(dpf)
0.89
0.90
0.88
0.87
0.90
0.90
Compressor
Compressor Number per Circuit
#
2
2
2
2
3
3
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Model Circuit 1 / Circuit 2
kW
25+30/25+30 30+30/30+30 30+40/30+40 40+40/40+40
25+30+30/
25+30+30
30+30+30/
30+30+30
Max Comp Power input Circuit 1 / Circuit 2
kW
28.4+38.2
38.2+38.2/
38.2+38.2
38.2+45.2/
38.2+45.2
45.2+45.2/
45.2+45.2
28.4+38.2+38.2/
28.4+38.2+38.2
38.2+38.2+38.2/
38.2+38.2+38.2
Rated Amps Circuit 1 / Circuit 2
(A)
47+61/
47+61
61+61/
61+61
61+75/
61+75
75+75/
75+75
47+61+61/
47+61+61
61+61+61/
61+61+61
Locked Rotor Amps Circuit 1 / Circuit 2 (direct
start - Digit 54=A)
(A)
260+294/
260+294
294+294/
294+294
294+413/
294+413
413+413/
413+413
260+294+294/
260+294+294
294+294+294/
294+294+294
Locked Rotor Amps Circuit 1 / Circuit 2 (Soft
starter - Digit 54=B)
(A)
156+176/
156+176
176+176/
176+176
176+248/
176+248
248+248/
248+248
156+176+176/
156+176+176
176+176+176/
176+176+176
Motor RPM
(rpm)
2900
2900
2900
2900
2900
2900
Oil sump heater Circuit 1 / Circuit 2
(W)
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90/
90+90
90+90+90/
90+90+90
90+90+90/
90+90+90
Evaporator
Quantity
#
1
1
1
1
1
1
Type
Shell & Tube Heat exchanger
Evaporator model
3511
3511
3511
3511
3519
3519
Evaporator Water Content volume
(l)
--
--
--
--
--
--
Unit Connections
Without pump package and no strainer
Inlet / Outlet
8" / 8"
8" / 8"
8" / 8"
8" / 8"
8" / 8"
8" / 8"
Without pump package but strainer
Inlet / Outlet
4" / 8"
4" / 8"
4" / 8"
4" / 8"
5" / 8"
5" / 8"
With pump package but no balance valve
Inlet / Outlet
4" / 8"
4" / 8"
4" / 8"
4" / 8"
5" / 8"
5" / 8"
With pump package and balance valve
Inlet / Outlet
4" / 4"
4" / 4"
4" / 4"
4" / 4"
5" / 5"
5" / 5"
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure
(kPa)
124
109
147
130
122
107
Motor Power
(kW)
5.5
5.5
7.5
7.5
7.5
7.5
Rated Amps
(A)
11
11
14.4
14.4
14.4
14.4
General Data
Содержание Sintesis Advantage CGAF 100 SE
Страница 34: ...34 CG SVX039C GB Top view Typical CGAF CXAF Components location ...
Страница 35: ...CG SVX039C GB 35 Typical CGAF CXAF Components location ...
Страница 36: ...36 CG SVX039C GB Typical CGAF CXAF Components location ...
Страница 85: ......
Страница 86: ......
Страница 87: ......