SS-SVX09A-EN
51
Installation
Controls using 24 VAC
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before installing any connecting wiring, refer to
Figure 3
to
Figure 8
for the electrical access
locations provided on the unit and
Table 9
for AC conductor sizing guidelines, and;
1.
Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the controls and the unit’s termination point does
not exceed three (3) ohms/conductor for the length of the run.
NOTICE
Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient
AC voltage supply.
3. Be sure to check all loads and conductors for grounds, shorts, and miswiring.
4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
Typical Low voltage components may include:
zone thermostat wiring (AC & DC wiring);
system control switch wiring (VAV units);
night setback relay wiring (VAV units);
economizer actuator circuit wiring (VAV units);
discharge air sensor wiring (VAV units);
chilled water temperature sensor (EVP units);
jumpers for hot gas bypass operation.
Controls using DC Analog Input/Outputs
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before installing any connecting wiring between the unit and components utilizing a DC analog
input\output signal, refer to
Figure 3
to
Figure 8
for the electrical access locations provided on the
unit.
Table 9.
AC Conductors
Distance from
Unit to Control
Recommended
Wire Size
000 - 460 feet
18 gauge
461 - 732 feet
16 gauge
733 - 1000 feet
14 gauge
Содержание RAUC-C20
Страница 10: ...10 SS SVX09A EN Installation Figure 3 RAUC C20 Unit Dimensional Data Recommended Clearances...
Страница 11: ...SS SVX09A EN 11 Installation Figure 4 RAUC C25 Unit Dimensional Data Recommended Clearances...
Страница 12: ...12 SS SVX09A EN Installation Figure 5 RAUC C30 Unit Dimensional Data Recommended Clearances...
Страница 13: ...SS SVX09A EN 13 Installation Figure 6 RAUC C40 Unit Dimensional Data Recommended Clearances...
Страница 14: ...14 SS SVX09A EN Installation Figure 7 RAUC C50 Unit Dimensional Data Recommended Clearances...
Страница 15: ...SS SVX09A EN 15 Installation Figure 8 RAUC C60 Unit Dimensional Data Recommended Clearances...
Страница 55: ...SS SVX09A EN 55 Installation Field Connection Diagram Notes for all System Control Options...
Страница 67: ...SS SVX09A EN 67 Installation Figure 33 6RT1 Discharge Air Sensor Assembly...
Страница 96: ...96 SS SVX09A EN System Start Up Figure 47 20 Ton Pressure Curve...
Страница 97: ...SS SVX09A EN 97 System Start Up Figure 48 25 Ton Pressure Curve...
Страница 98: ...98 SS SVX09A EN System Start Up Figure 49 30Ton Pressure Curve...
Страница 99: ...SS SVX09A EN 99 System Start Up Figure 50 40 Ton Pressure Curve per Circuit...
Страница 100: ...100 SS SVX09A EN System Start Up Figure 51 50 Ton Pressure Curve per Circuit...
Страница 101: ...SS SVX09A EN 101 System Start Up Figure 52 60 Ton Pressure Curve per Circuit...