46
SS-SVX09A-EN
Installation
Main Unit Power Wiring
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Table 7
lists the field connection wire ranges for both the main power terminal block 1TB1 and the
optional main power disconnect switch 1S1. The unit electrical data is listed in
Table 8
. The
electrical service must be protected from over current and short circuit conditions in accordance
with NEC requirements. Protection devices must be sized according to the electrical data on the
nameplate. Refer to the “Power Wire Sizing & Protection Device Equations”, for determining;
a. the appropriate electrical service wire size based on “Minimum Circuit Ampacity” (MCA),
b. the “Maximum Over current Protection” (MOP) device.
c. the “Recommended Dual Element fuse size” (RDE).
1.
If the unit is not equipped with an optional factory installed nonfused disconnect switch, a field
supplied disconnect switch must be installed at or near the unit in accordance with the National
Electrical Code (NEC latest edition). Refer to the “Power Wire Sizing & Protection Device
Equations” (DSS calculation), for determining the correct size.
2. Complete the unit’s power wiring connections onto either the main terminal block 1TB1, or the
factory mounted nonfused disconnect switch 1S1, inside the unit control panel. Refer to the
customer connection diagram that shipped with the unit for specific termination points.
3. Provide proper grounding for the unit in accordance with local and national codes.
Содержание RAUC-C20
Страница 10: ...10 SS SVX09A EN Installation Figure 3 RAUC C20 Unit Dimensional Data Recommended Clearances...
Страница 11: ...SS SVX09A EN 11 Installation Figure 4 RAUC C25 Unit Dimensional Data Recommended Clearances...
Страница 12: ...12 SS SVX09A EN Installation Figure 5 RAUC C30 Unit Dimensional Data Recommended Clearances...
Страница 13: ...SS SVX09A EN 13 Installation Figure 6 RAUC C40 Unit Dimensional Data Recommended Clearances...
Страница 14: ...14 SS SVX09A EN Installation Figure 7 RAUC C50 Unit Dimensional Data Recommended Clearances...
Страница 15: ...SS SVX09A EN 15 Installation Figure 8 RAUC C60 Unit Dimensional Data Recommended Clearances...
Страница 55: ...SS SVX09A EN 55 Installation Field Connection Diagram Notes for all System Control Options...
Страница 67: ...SS SVX09A EN 67 Installation Figure 33 6RT1 Discharge Air Sensor Assembly...
Страница 96: ...96 SS SVX09A EN System Start Up Figure 47 20 Ton Pressure Curve...
Страница 97: ...SS SVX09A EN 97 System Start Up Figure 48 25 Ton Pressure Curve...
Страница 98: ...98 SS SVX09A EN System Start Up Figure 49 30Ton Pressure Curve...
Страница 99: ...SS SVX09A EN 99 System Start Up Figure 50 40 Ton Pressure Curve per Circuit...
Страница 100: ...100 SS SVX09A EN System Start Up Figure 51 50 Ton Pressure Curve per Circuit...
Страница 101: ...SS SVX09A EN 101 System Start Up Figure 52 60 Ton Pressure Curve per Circuit...