Figure 4-4 (Continued)
40, 50 & 55 Ton Supply Fan Performance with Inlet Guide Vanes
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
0
2000
4000
6000
8000
10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000
CFM
STATIC PRESSURE, Inc
h
e
s
w.c
.
40% w
o
cf
m
50%
60%
70%
1200 RPM
500 RPM
600 RPM
700 RPM
800 RPM
900 RPM
1000 RPM
1100 RPM
5 HP
7.5 HP
10 HP
15 HP
20 HP
25 HP
30 HP
40 HP
S_HFC40, C50, C55
Dual 20 X 20 Fans
Entrance Losses
- with Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 7.5
- Maximum Motor HP
C40, C50 & C55 = 30 HP
- Maximum RPM
7.5 - 15 HP = 1141
20 - 30 HP = 1170
- Maximum CFM
C40 = 18,000
C50 = 22,500
C55 = 24,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
90%
80%
60, 70 & 75 Ton Supply Fan Performance with Inlet Guide Vanes
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
0
3000
6000
9000
12000
15000
18000
21000
24000
27000
30000
33000
36000
CFM
STATIC PRESSURE, Inches w
.c.
S_HFC60, C70, C75
Dual 22 X 22 Fans
Entrance Losses
- with Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 10
- Maximum Motor HP = 40
- Maximum RPM = 1130
- Maximum CFM
C60 = 27,000
C70 & C75 = 30,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
1000 RPM
900 RPM
800 RPM
700 RPM
600 RPM
500 RPM
1100 RPM
1200 RPM
7.5 HP
10 HP
15 HP
20 HP
25 HP
30 HP
40 HP
50 HP
90% wocfm
80%
50%
40%
w
o
c
fm
70%
60%
Содержание INTELLIPAK RT-SVX10C-EN
Страница 16: ...15 Figure 3 1 Minimum Operation and Service Clearances for Single Multiple Unit Installation...
Страница 17: ...16 Figure 3 2A SAHF Cooling Only Units 20 thru 75 Ton...
Страница 19: ...18 Figure 3 2B SEHF SFHF SLHF SSHF SXHF Units 20 thru 75 Ton...
Страница 21: ...20 Figure 3 2C S_HG Cooling Heating Units 90 through 130 Ton...
Страница 25: ...24 Figure 3 4 Typical Unit Rigging Figure 3 5 Unit Base Roof Curb Section...
Страница 38: ...37 Figure 3 13 Steam Coil Piping 20 through 30 Ton Units Steam Coil Piping 40 through 130 Ton Units...
Страница 41: ...40 Figure 3 14 Continued Typical Field Power Wiring 90 thru 130 Ton Table 3 6 Customer Connection Wire Range...
Страница 52: ...51 Field Connection Diagram Notes for 20 through 130 Ton CV or VAV Applications...
Страница 86: ...84 Figure 4 6 Compressor Locations...
Страница 103: ...101 Service Maintenance Continued Table 5 3 Unit Internal Fuse Replacement Data VFD Factory Settings...
Страница 117: ...115...
Страница 118: ...116...