Table 4-1
Service Test Guide for Component Operation
COMPONENT
COMPONENT CONFIGURATION
Occ
BEING TESTED
Supply Exhaust Condenser Heat Stages
Compressor Stage
Econo Exhaust
VFD
Unocc
Fan
Fan
Fans
1
2
3
1
2
3
4
Damper Damper
IGV
Output Relay
* COMPRESSOR
20 thru 30 Ton
A
Off
Off
A-Off/B-On
Off Off Off K10-Off K11-On
N/A
N/A
Closed
Closed Closed
0%
Default
B
Off
Off
A-On/B-Off
Off Off Off K10-On K11-Off
N/A
N/A
Closed
Closed Closed
0%
Default
40 thru 60 Ton
1A
Off
Off
1A-Off/1B-On Off Off Off K11-Off K3-Off K12-On K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1B
Off
Off
1A-On/1B-Off Off Off Off K11-On K3-Off K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed
Closed Closed
0%
Default
2A-Off/2B-On
2B
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-On/2B-Off
0%
70 thru 105 Ton
1A & 1B
Off
Off
1A-Off/1B-On Off Off Off K11-Off K3-Off K12-On K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1C
Off
Off
1A-On/1B-Off Off Off Off K11-On K3-Off K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A & 2B
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed
Closed Closed
0%
Default
2A-Off/2B-On
2C
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-On/2B-Off
115 thru 130 Ton
1A & 1B
Off
Off
1A-Off/1B-On Off Off Off K11-Off K3-Off K12-On K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1C & 1D
Off
Off
1A-On/1B-Off Off Off Off K11-On K3-Off K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A & 2B
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed
Closed Closed
0%
Default
2A-Off/2B-On
2C & 2D
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-On/2B-Off
** CONDENSER FANS
20 Ton
A-2B1
Off
Off
A-On/B-Off
Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
B-2B2
Off
Off
A-Off/B-On
Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
25 - 30 Ton
A-2B1
Off
Off
A-On/B-Off
Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
B-2B2/2B3
Off
Off
A-Off/B-On
Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
40 Ton
1A-2B1
Off
Off
1A-On/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1B-2B2
Off
Off
1A-Off/1B-On Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A-2B4
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-On/2B-Off
2B-2B5
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-On
50 & 55 Ton
1A-2B1
Off
Off
1A-On/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1B-2B2/2B3
Off
Off
1A-Off/1B-On Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A-2B4
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-On/2B-Off
2B-2B5/2B6
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-On
60 thru 75 Ton
1A-2B1
Off
Off
1A-On/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1B-2B2/2B3
Off
Off
1A-Off/1B-On Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A-2B4
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-On/2B-Off
2B-2B5/2B6
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-On
Refer to the next page for applicable notes.
Содержание INTELLIPAK RT-SVX10C-EN
Страница 16: ...15 Figure 3 1 Minimum Operation and Service Clearances for Single Multiple Unit Installation...
Страница 17: ...16 Figure 3 2A SAHF Cooling Only Units 20 thru 75 Ton...
Страница 19: ...18 Figure 3 2B SEHF SFHF SLHF SSHF SXHF Units 20 thru 75 Ton...
Страница 21: ...20 Figure 3 2C S_HG Cooling Heating Units 90 through 130 Ton...
Страница 25: ...24 Figure 3 4 Typical Unit Rigging Figure 3 5 Unit Base Roof Curb Section...
Страница 38: ...37 Figure 3 13 Steam Coil Piping 20 through 30 Ton Units Steam Coil Piping 40 through 130 Ton Units...
Страница 41: ...40 Figure 3 14 Continued Typical Field Power Wiring 90 thru 130 Ton Table 3 6 Customer Connection Wire Range...
Страница 52: ...51 Field Connection Diagram Notes for 20 through 130 Ton CV or VAV Applications...
Страница 86: ...84 Figure 4 6 Compressor Locations...
Страница 103: ...101 Service Maintenance Continued Table 5 3 Unit Internal Fuse Replacement Data VFD Factory Settings...
Страница 117: ...115...
Страница 118: ...116...