RT-SVX072A-EN
49
Figure 28.
Steam coil piping (20 to 36 ton)
2-Way Modulating Valve
(Field Installed)
Air Vent
Strainer
Strainer
OUTLET
INLET
Steam Trap
(Float and Thermostatic Type)
Supply
Steam
Return
Gate Valve
Type NS
Steam Coil
(ARI Listed)
Figure 29.
Steam coil piping (40 to 130 ton)
2-Way
Modulating
Valve
Vacuum Breaker
(2 locations)
Use same size pipe
as Trap Connections
(3 locations)
Return Main
Type
NS
Stea
m Coil
s
(ARI Listed)
Steam Main
IN
(2 locations)
OUT
(2 locations)
12” Minimum
(both outlets)
Steam Trap
(Float & Thermostatic Type)
(3 locations)
Strainer
(3 locations)
Use same size pipe
as Coil Connection
(2 locations)
Use same size pipe
as Steam Main
Gas Valve
(3 locations)
Disconnect Switch with External
Handle
Units ordered with a factory mounted disconnect
switch comes equipped with an externally mounted
handle. This allows the operator to disconnect power
from the unit without having to open the control panel
door. The handle has three positions:
•
“ON” - Indicates that the disconnect switch is
closed, allowing the main power supply to be
applied at the unit.
•
“OFF” - Indicates that the disconnect switch is
open, interrupting the main power supply to the
unit controls.
•
“RESET/LOCK” - Turning the handle to this position
resets or disconnects the device. To disconnect, the
handle must be turned to the Reset/Lock position.
Pulling the spring-loaded thumb key out, so the lock