Table 60.
Startup checklist for 90–130 ton air-cooled units (continued)
Completed?
4
Verify compressor operation, voltage and amperage matches name plate information (please document on log
sheet)
Yes
No
5
Operating log completed
Yes
No
6
All panels & doors secured
Yes
No
7
Complete all required documentation
Yes
No
Critical Control Parameters and Dry Bulb Changeover Map
Table 61.
Critical control parameters
Description
Suggested
Parameter
Economizer Settings
Region
1
Region
2
Region
3
Region
4
Region
5
Region
6
Region
7
Supply Air Temperature Control Setpoint
55°F
Supply Air Temperature Deadband
8°F
Supply Air Pressure Setpoint
1.8" w.c.
Supply Air Pressure Deadband
0.1" w.c.
Building Static Pressure Setpoint
0.03" w.c.
Building Static Pressure Deadband
0.04" w.c.
Standby Freeze Avoidance
20%
Relief Enable Setpoint
10%
Economizer Minimum Position Setpoint
10%
Fixed Dry Bulb Economizer C/O Type a
(Moist)*
TOA >
65°F
TOA >
65°F
TOA >
65°F
TOA >
65°F
TOA >
70°F
TOA >
70°F
TOA >
70°F
Fixed Dry Bulb Economizer C/O Type b (Dry)
*
TOA > 75°F
Fixed Dry Bulb Economizer C/O Type c
(Marine)*
TOA >
75°F
TOA >
75°F
TOA >
75°F
Fixed Reference (Enthalpy Changeover)
HOA > 28 Btu
Differential Comparative (Enthalpy
Changeover)
HOA > HRA
Notes:
1
.
See map in next figure for dry bulb changeover.
Examples:
- Minneapolis, Minnesota is in “Region 6" and resides in “Moist” subregion, thus designation is 6b. Economizer changeover setting should be
75°F.
- Charleston, South Carolina is in “Region 3" and resides in “Moist” subregion, thus the designation is 3c. Economizer changeover setting
should be 65°F.
2
.
Go to SETUP menu and input setting for parameters listed in the table above.
3
.
Use the Dry bulb changeover map to determine region of country based on unit site location.
4
.
Fixed speed compressor units 8°F deadband.
5
.
eFlex™ compressor units 4°F deadband.