RT-SVX072A-EN
113
Table 48.
O/A Damper travel adjustment
Position of
Connecting Rod
Damper Crank Arm Hole
Configuration
Standard and
Low Leak F/A
Dampers
(
)
Ultra Low Leak
F/A Dampers
(
)
Position #1
2–3
1–6
Position #2
2–4
2–6
Position #3
2–5
3–7
Position #4
2–6
4–8
Position #5
1–8
5–9
Position #6
1–7
5–7
Use
to select the appropriate crank
arm hole configuration based on the following:
•
specific unit
•
operating CFM
•
and return static pressure
Table 49.
Outside air damper pressure drop (inches
w.c.) — air-cooled
CFM
Damper Position
#1
#2
#3
#4
#5
#6
20, 25 Ton
4000
0.03
0.04
0.06
0.13
0.16
0.33
6000
0.03
0.04
0.10
0.20
0.30
0.90
8000
0.19
0.21
0.32
0.52
0.75
1.75
9000
0.30
0.35
0.48
0.76
1.08
2.40
10000
0.45
0.51
0.70
1.05
1.57
-
11000
0.62
0.71
0.95
1.42
2.15
-
30
6000
0.03
0.04
0.07
0.15
0.20
0.43
8000
0.03
0.05
0.11
0.21
0.30
0.90
10000
0.15
0.19
0.26
0.43
0.62
1.50
11000
0.20
0.25
0.37
0.60
0.85
1.85
12000
0.31
0.36
0.50
0.79
1.10
2.40
13000
0.42
0.48
0.62
0.97
1.42
-
40, 48 Ton
8000
0.03
0.04
0.08
0.16
0.21
0.52
10000
0.03
0.05
0.11
0.21
0.30
0.90
12000
0.10
0.13
0.21
0.38
0.55
1.40
14000
0.20
0.25
0.37
0.60
0.85
1.85
16000
0.41
0.46
0.60
0.94
1.38
-
Table 49.
Outside air damper pressure drop (inches
w.c.) — air-cooled (continued)
CFM
Damper Position
#1
#2
#3
#4
#5
#6
18000
0.56
0.65
0.74
1.28
1.92
-
50, 55 Ton
10000
0.03
0.04
0.09
0.18
0.23
0.55
14000
0.09
0.12
0.20
0.35
0.50
1.36
18000
0.31
0.36
0.50
0.79
1.10
-
20000
0.45
0.51
0.70
1.05
1.57
-
22000
0.58
0.66
0.75
1.30
1.95
-
24000
0.75
0.88
1.10
1.75
2.50
-
(60, 70, 75 Ton) Units
14000
0.03
0.04
0.12
0.25
0.35
1.05
18000
0.19
0.21
0.32
0.52
0.75
1.75
22000
0.45
0.51
0.70
1.05
1.57
-
26000
0.70
0.80
1.02
1.58
2.30
-
28000
0.88
1.03
1.30
2.20
-
-
30000
1.05
1.22
1.55
2.65
-
-
(90 to 130 Ton) Units
27000
0.31
0.36
0.50
0.79
1.10
2.40
32000
0.55
0.64
0.72
1.25
1.88
-
36000
0.75
0.88
1.10
1.75
2.50
-
40000
1.00
1.18
1.50
2.50
-
-
43000
1.20
1.42
1.92
-
-
-
46000
1.40
1.58
2.29
-
-
-
Compressor Startup (All
Systems)
N
NO
OT
TIIC
CE
E
C
Co
om
mp
prre
esssso
orr F
Fa
aiillu
urre
e!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w iin
nssttrru
uccttiio
on
n b
be
ello
ow
w cco
ou
ulld
d rre
essu
ulltt iin
n
cco
om
mp
prre
esssso
orr ffa
aiillu
urre
e..
U
Un
niitt m
mu
usstt b
be
e p
po
ow
we
erre
ed
d a
an
nd
d ccrra
an
nkkcca
asse
e h
he
ea
atte
errss
e
en
ne
errg
giizze
ed
d a
att lle
ea
asstt 8
8 h
ho
ou
urrss B
BE
EF
FO
OR
RE
E cco
om
mp
prre
esssso
orrss
a
arre
e sstta
arrtte
ed
d..
1. Ensure that the “System” selection switch at the
remote panel is in the “Off” position.
2. Before closing the disconnect switch, ensure that
the compressor discharge service valve for each
circuit is back seated.