118
RT-SVX072A-EN
Table 52.
eFlex
™
™
staging sequence and compressor data (continued)
1
X
1800
4860
2
X
X
1500
5460
3
X
X
X
2400
5580
50 Ton eFlex™ Variable Speed Compressor
Stage
Comp 1A VZH170
Comp 2A
Comp 2B
VZH
Min Spd
Max Spd
1
X
1620
4200
2
X
X
1500
4740
3
X
X
X
2340
4800
55 Ton eFlex™ Variable Speed Compressor
Stage
Comp 1A VZH170
Comp 2A
Comp 2B
VZH
Min Spd
Max Spd
1
X
1740
4560
2
X
X
1800
5280
3
X
X
X
2520
5280
60 Ton eFlex™ Variable Speed Compressor
Stage
Comp 1A VZH170
Comp 2A
Comp 2B
VZH
Min Spd
Max Spd
1
X
1920
4740
2
X
X
1500
5700
3
X
X
X
2520
5820
70 Ton eFlex™ Variable Speed Compressor
Stage
Comp 1A VZH170
Comp 2A
Comp 2B
VZH
Min Spd
Max Spd
1
X
2220
5220
2
X
X
1500
6000
3
X
X
X
2220
6000
75 Ton eFlex™ Variable Speed Compressor
Stage
Comp 1A VZH170
Comp 1B
Comp 2A
Comp 2B
VZH
Min Spd
Max Spd
1
X
2520
5160
2
X
X
1500
4500
3
X
X
X
1500
5040
4
X
X
X
X
1500
5880
Electronic Expansion Valves
All Intellipak1 with Symbio systems use electronic
expansion valves (EXV's) to control superheat. These
valves are factory set to 12°F of superheat to balance
efficiency and compressor reliability at all operating
conditions.
This setting can be adjusted through the Symbio
controller display, but this only recommended to be
done at the discretion of Trane Product Support
Pressure curves included in this document are based
on outdoor ambient between 65° & 105°F, relative
humidity above 40 percent. Measuring the operating
pressures can be meaningless outside of these ranges.