HFCF Model Designation

 

 
 
 
 
 
 

Digit 1

 

H = Horizontal unit; V = Vertical unit;

 

Digit 2

 

F = Fan Coil Unit

 

Digit 3

 

C = Concealed

 

Digit 4

 

F=Design Sequence

 

Digit 5,6

  Size / Nominal Airflow

 

02 =200 CFM   
03 =300 CFM   
04 =400 CFM       
05 =500 CFM       
06 =600 CFM         

 

08 =800 CFM     
10 =1000 CFM   
12 =1200 CFM   
14 =1400 CFM   

Digit 7

 

Connection Side

 

L = Left Connection

 

                      R =Right Connection

 

Digit 8

 

Coil Rows

 

2 = 2 rows cooling

 

3 = 3 rows cooling

 

4 = 4 rows cooling

 

A = 2 rows cooling

1row heating

 

B = 3 rows cooling

1row heating

 

Digit 9

 

Electric Heater 

Size

 

 

N = None A = 0.5KW Heater (02) B = 1.0KW Heater(03) C =1.4KW Heater(04) D = 1.6KW Heater(05)   

 

E =1.8KW Heater(06) F = 2.8KW Heater(08) G = 3.2KW Heater(10) H = 3.6KW Heater(12) J = 4.6KW 
Heater(14)

 

Digit 10

       

Motor Type

 

N = Normal

 

H = High Static 
A =DCBL Normal

w/ LCD thermostat

 

B =DCBL High Static

w/ LCD thermostat

 

C =Hermetic Motor Normal Type 
D =Hermetic Motor High Static Type 

Digit 11

       

Voltage/Hz/Phase

 

1 = 220/50/1

 

                      2

230/60/1

 

                      3=115/60/1

 

Digit 12

   

Control Package

 

N =None 

 

 

 

 

 

A =2-pipe, with 2-way    Valve 

 

 

 

 

 

B =2-pipe, with 3-way    Valve 

 

 

 

 

 

C =4-pipe, with 2-way    Valves 

 

 

 

 

 

D =2-pipe, with 2-way    Valve & LCD Thermostat 

 

 

 

 

 

E =2-pipe, with 2-way    Valve & LCD Thermostat(VWV System) 

 

 

 

 

 

F =2-pipe, with 3-way    Valve & LCD Thermostat 

 

 

 

 

 

G =4-pipe, with 2-way    Valves & LCD Thermostat 

 

 

 

 

 

H =2-pipe

with 2-way Valve & ZN510 w/ Zone Sensor   

 

 

 

 

J =2-pipe

with 3-way Valve & ZN510 w/ Zone Sensor   

 

 

 

 

K =4-pipe

with 2-way Valves & ZN510 w/ Zone Sensor   

 

 

 

 

L =2-pipe

with 2-way Valve & ZN520 w/ Zone Sensor   

 

 

 

 

M =2-pipe

with 3-way Valve & ZN520 w/ Zone Sensor   

 

 

 

 

N =4-pipe

with 2-way Valves & ZN520 w/ Zone Sensor   

 

 

 

 

H  F  C  F  0  3  L  3  0  N  1  0  A  0  A  0  0  A 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1  2  3  4  5  6  7  8  9  10  11  12  13  14  15  16  17  18 

Содержание HFCF-SVX01A-EN

Страница 1: ...Installation Operation Maintenance Chilled Water Fan Coil Unit Airflow 200 1400CFM HFCF SVX01A EN...

Страница 2: ...ections Figure 2 Typical Installation Figure 3 Duct Work Dimension Data and Weights 9 Figure 4 HFCF Without Reture Plenum Figure 5 HFCF With Bottom Return Plenum Figure 6 HFCF With Rear Return Plenum...

Страница 3: ...e motor The motor lead out wires are enclosed by flexible metal conduit and providing protection against damage Coil The coil can have 2 3 or 4 rows with copper tubes mechanically bonded into slit alu...

Страница 4: ...tor Type N Normal H High Static A DCBL Normal w LCD thermostat B DCBL High Static w LCD thermostat C Hermetic Motor Normal Type D Hermetic Motor High Static Type Digit 11 Voltage Hz Phase 1 220 50 1 2...

Страница 5: ...mm Non flammable Close Cell Insulation Extended 310mm N STD Galvanized Steel w 10mm Non flammable Close Cell Insulation P STD Galvanized Steel w 10mm Non flammable Close Cell Insulation Extended 200mm...

Страница 6: ...drainage and operation 5 Ducting connected to units where applicable should not exceed the external static pressure rating of the unit 6 Condensate protection for the chilled water valves and piping m...

Страница 7: ...wiring diagram decals on each unit Also see Figure 7 for wiring diagrams A grounding point which must be properly connected to the building grounding system has been provided with a mark on the verti...

Страница 8: ...Dimension Data and Weights Figure 2 Typical Installation Figure 3 Duct Work 8...

Страница 9: ...3 1820 1983 1882 2 4 37 40 43 38 41 44 45 48 51 46 51 52 6 111 10 145 24 270 14 211 12 43 A B C 29 11 18 14 View A 543 520 248 248 198 D Outlet water Collar 3 4 inch female pipe thread FPT Inlet water...

Страница 10: ...Wiring Diagram Figure 7 Model HFCF Wiring Diagrams 10...

Страница 11: ...prepared for weight leveling and service access Unit is mounted securely to the ceiling support rods Ductwork connections are complete Coil connections are complete and tight Condensate drain pan con...

Страница 12: ...tout 85 auto reset is provided to de energize electric heat in the event of an overheat condition In addition to the automatic reset cutout the unit also equipped with another high temperature cutout...

Страница 13: ...Figure 8 Fan Board Assembly Maintenance...

Страница 14: ...source To clean permanent filters remove the filter media and wash it in water to remove dust dirt and lint allow to dry thoroughly before re installing in the unit Change Entire Fan Board The entire...

Страница 15: ...oling capacity Followings are the cleaning steps 1 Disconnect the power and motor wire and stop the fan 2 Remove the whole fan seat and clean from the air inlet 3 Clean the coil fin using rigid nylon...

Страница 16: ...e office or e mail us at comfort trane com Literature Order Number Date Supersedes HFCF SVX01A EN March 2008 New Trane has a policy of continuous product and product data improvement and reserves the...

Отзывы: