background image

 

 

 

 

 

 

 

 

 

 

Periodic Maintenance 
Checklist 

The following checklist is 

provided as a recommended maintenance 
schedule. Detailed instructions for specific 
maintenance procedures are given after the 
checklist. 

 

WARNING: Disconnect electrical 
power source and secure in 
disconnected position before 
servicing the unit. Failure to do 
so may result in personal injury 
or death from electrical shock.

 

 

Every month:

 

 Inspect the unit air filter. Clean or 

replace clogged filter element. 

 Check the drain pan to be sure that it 

is clean and free to carry the flow of 
condensate through the drain line. 

 

Every year:

 

 Inspect the unit casing for corrosion. 

Clean or repair to provide unit protection. 

 Inspect the fan wheel and housing for 

damage. Rotate the fan wheel manually to 
be sure no obstructions block its 
movement. 

 Inspect the coil fins for excessive dirt or 

damage. Remove dirt and straighten fins. 

 Clean and tighten all electrical 

connections. 

 Drain and treat the whole system to 

control pipe scaling. 

 

CAUTION: The use of untreated or 
improperly treated water in this 
equipment may result in scaling, erosion, 
corrosion, algae or slime. The services of 
a qualified water treatment specialist 
should be engaged to determine what 
treatment if any, is advisable. The Trane 
Company assumes no liability for the 
results of the use of untreated or 
improperly treated water.

 

 

 

 

 

 

 

 

Maintenance

 

 

 

 

 

 

Maintenance Procedures

 

 

Change/Clean Filters

 

Change or clean air filters at least twice a year. 
Filters will require more frequent care under 
high load conditions or dirty air. A clogged air 
filter reduces airflow, cooling capacity and 
increases energy usage. Permanent (cleanable), 
or replaceable media filters are acceptable for 
all units. 

 

To change filters with replaceable media: 

 

1. Disconnect electrical power source. 
2. Loosen two screws and brackets at the 

rear of return plenum. 

3. Pull out the filter and frame from the 

return plenum. 

4. Remove two screws from the frame. 
5. Replace media in the frame. 

6. Follow the opposite procedure to re-install 
  the filter frame 

7.  Re-connect  the electrical  power  source. To 
clean  permanent  filters,  remove  the  filter 
media and wash it in water to remove dust, dirt 
and  lint;  allow  to  dry  thoroughly  before  re-
installing in the unit. 

 

Change Entire Fan Board

 

The entire fan board can be changed by 
completing the following steps: 

 

1. Turn off the electrical power source and then 

disconnect the motor wires. Allow the rotating 
fan wheel to stop. 

2. Disconnect the grounding wire. 
3. Remove the return plenum, if applicable. 
4. Loosen the screws fastened on the keyholes 

at four corners of the fan board, as shown 
on Figure 8-1. 

5. Remove other screws from the upper side of 

the fan board, if applicable, as shown on 
Figure 8-2. 

6. Lift up the fan board about 14mm and then 

pull the entire fan board from the unit through 
the keyholes. 

 

14 

 

 

 

 

 

 

 

 

 

 

CAUTION: Due to the dimensions and weights of 
the fan board, at least two installers is 
recommended to do this step for safety.

 

 

7. Follow the opposite procedures to reinstall the 

new fan board. 

 

Clean up debris on the coil and the inside of unit 
casing before installing the fan board. Also check for 
debris on the fan wheel before start-up. 

 

Change Fan Housing/Fan Wheel

 

The fan housing/fan wheel can be replaced, without 
removing the entire fan board from the unit, by 
completing the following steps: 

 

1. Turn  off  the  electrical  power  source  and  then 

disconnect  the  motor wires. Allow  the  rotating 
fan wheel to stop. 

2. Remove the filter and return plenum from the unit, 

if applicable. 

3. Loosen the bolt, located in the center of the fan 

wheel, which fastens the fan wheel and motor 
shaft together. 

4.  Remove  the  four  screws  that  fasten  the  fan 

housing and fan board together, as shown on 
Figure 8-3. 

5

Unscrew the nuts fixing fan blade and motor 

shaft in the middle of fan blade. 

6. Pull out the fan housing about 20mm from the fan 

board and then remove the fan housing and 
wheel from the motor shaft. 

7. Once the fan housing is separated from the 

fan board and motor shaft, the fan wheel can 
then be taken out of the fan housing by the 
following steps. 

 Remove two screws on top panel of the fan 

housing, as shown on Figure 8-4. 

 Lift up the flexible top panel and then 

remove the fan wheel out of the fan housing. 

8. After replacing the fan housing or fan wheel, 

follow the opposite procedures to re-install. 

 

 

Содержание HFCF-SVX01A-EN

Страница 1: ...Installation Operation Maintenance Chilled Water Fan Coil Unit Airflow 200 1400CFM HFCF SVX01A EN...

Страница 2: ...ections Figure 2 Typical Installation Figure 3 Duct Work Dimension Data and Weights 9 Figure 4 HFCF Without Reture Plenum Figure 5 HFCF With Bottom Return Plenum Figure 6 HFCF With Rear Return Plenum...

Страница 3: ...e motor The motor lead out wires are enclosed by flexible metal conduit and providing protection against damage Coil The coil can have 2 3 or 4 rows with copper tubes mechanically bonded into slit alu...

Страница 4: ...tor Type N Normal H High Static A DCBL Normal w LCD thermostat B DCBL High Static w LCD thermostat C Hermetic Motor Normal Type D Hermetic Motor High Static Type Digit 11 Voltage Hz Phase 1 220 50 1 2...

Страница 5: ...mm Non flammable Close Cell Insulation Extended 310mm N STD Galvanized Steel w 10mm Non flammable Close Cell Insulation P STD Galvanized Steel w 10mm Non flammable Close Cell Insulation Extended 200mm...

Страница 6: ...drainage and operation 5 Ducting connected to units where applicable should not exceed the external static pressure rating of the unit 6 Condensate protection for the chilled water valves and piping m...

Страница 7: ...wiring diagram decals on each unit Also see Figure 7 for wiring diagrams A grounding point which must be properly connected to the building grounding system has been provided with a mark on the verti...

Страница 8: ...Dimension Data and Weights Figure 2 Typical Installation Figure 3 Duct Work 8...

Страница 9: ...3 1820 1983 1882 2 4 37 40 43 38 41 44 45 48 51 46 51 52 6 111 10 145 24 270 14 211 12 43 A B C 29 11 18 14 View A 543 520 248 248 198 D Outlet water Collar 3 4 inch female pipe thread FPT Inlet water...

Страница 10: ...Wiring Diagram Figure 7 Model HFCF Wiring Diagrams 10...

Страница 11: ...prepared for weight leveling and service access Unit is mounted securely to the ceiling support rods Ductwork connections are complete Coil connections are complete and tight Condensate drain pan con...

Страница 12: ...tout 85 auto reset is provided to de energize electric heat in the event of an overheat condition In addition to the automatic reset cutout the unit also equipped with another high temperature cutout...

Страница 13: ...Figure 8 Fan Board Assembly Maintenance...

Страница 14: ...source To clean permanent filters remove the filter media and wash it in water to remove dust dirt and lint allow to dry thoroughly before re installing in the unit Change Entire Fan Board The entire...

Страница 15: ...oling capacity Followings are the cleaning steps 1 Disconnect the power and motor wire and stop the fan 2 Remove the whole fan seat and clean from the air inlet 3 Clean the coil fin using rigid nylon...

Страница 16: ...e office or e mail us at comfort trane com Literature Order Number Date Supersedes HFCF SVX01A EN March 2008 New Trane has a policy of continuous product and product data improvement and reserves the...

Отзывы: