AFDG/AFDU Startup Procedure
36
AFDG-SVU01L-EN
a. To reset the drive to the Danfoss defaults:
i. Disconnect power to the drive, and wait for the
display to shut down.
ii. While powering up the drive, press and hold the
following keys:
Status
,
Main
, and
OK
.
iii. After 5 seconds, release the keys.
b. Set Trane default settings (refer to
c. Set the job specific settings (refer to
Default Settings
for a list of items that are programmed in
the drive at the factory for use with Trane® chillers. In the
event that the drive needs to be reset, these parameters
will need to be reprogrammed into the drive.
Note:
The Trane commissioning technician should verify
these default settings to ensure they are correct in
the drive.
Table 11. Trane default settings
Group Parameter Description
Setting
0
03
Regional Settings
International (0)
0
20
Display line 1.1
small
DC link voltage (1630)
0
21
Display line 1.2
small
Analog input (1662)
0
22
Display line 1.3
small
Heat sink temp (1634)
0
23
Display line 2 large Power Kw (1610)
0
24
Display line 3 large Freq Hz (1613)
0
40
Hand on key
Disabled (0)
0
41
Off key
Disabled (0)
0
60
Main Menu password 999
0
61
Access to main menu
w/o password
Read only (1)
1
03
Torque
characteristics
Variable torque (1)
1
23
Motor frequency
60 Hz
1
39
Motor poles
Poles (2)
1
71
Delay start
0 sec
1
73
Flying start
Disabled (0)
3
03
Maximum Reference 60 Hz
3
41
Ramp 1 ramp up
time
10 sec
3
42
Ramp 2 ramp down
time
20 sec
4
12
Motor speed low
limit
38 Hz
4
14
Motor speed high
limit
60 Hz
5
12
Terminal 27 digital
input
Coast inverse (2)
5
(a)
(a) There are actually two relays under parameter 5-40 (Relay 1 and Relay
2). When entering 5-40, the required setting on Relay 1 = Alarm (9) as
shown here but then you also need to scroll down to Relay 2 and confirm
that Relay 2 = Run (5). The relays are NOT interchangeable. Relay 1
must always be set to Alarm (9); Relay 2 must always be set to Run (5).
40
Function Relay
Alarm (9)
6
10
Terminal 53 low
voltage
2 volts
6
14
Terminal 53 low Ref./
Feedb. value
38 Hz
6
15
Terminal 53 High
Ref./Feedb. value
60 Hz
14
20
Reset Mode
Automatic reset x 2
14
21
Automatic Restart
Time
60 sec