Overview

8

 AFDG-SVU01L-EN

Overview

AFDG/AFDU Information

The AFDG/AFDU air-cooled Adaptive Frequency Drive is a 
pulse width modulated (PWM) design. It is designed for 
460/480/575 volt application. This drive converts AC power 
to DC power and back to AC power. The incoming 460/480/
575 volts are converted to a constant 650 Vdc by a rectifier 
bridge (SCRs and diodes), and into a section of capacitors 
that are used to store the DC voltage. The DC output feeds 
the inverter IGBTs that switch at predetermined time to 
change the DC input voltage to a symmetrical AC output 
voltage of desired magnitude and frequency. The output 
frequency range is 38 to 60 hertz.

The DC voltage is fixed at 700 Vdc. A variable output is 
accomplished by PWM control within the inverter by the 
IGBTs which are basically transistors that turn on and off 
in response to the gate driver. 

A combination of two distinct operating modes make up 
the AFDG/AFDU control within the chiller’s UC800 control. 
First by controlling the inlet vanes, and second by 
modulating impeller speed from 38 to 60 hertz. The IGBTs 
control the speed in response to the UC800 compressor 
control signal. Circuit breakers, surge capacitors and 
ground faults are standard on all AFDG/AFDU units.

Some of the basic principles of the drive are:

Minimum efficiency of 97 percent at rated load and 
60 Hz.

Unit displacement power factor of 0.96 at all loads.

Low starting current.

The current never exceeds the rated load amps.

The AFDG/AFDU varies the motor speed in response to 
the speed command from the UC800 control.

The CenTraVac™ Control Panel has full control of the unit 
operation, including the start/stop functions. If you 
encounter a fault condition or an alarm on the drive, the 
Tracer® AdaptiView™ display will indicate “alarm” and an 
“alarm message.”

Содержание AFDG

Страница 1: ...all and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly...

Страница 2: ...ent that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Страница 3: ...t damage System contains oil and refrigerant and may be under positive pressure Recover refrigerant to relieve pressure before opening the system See unit nameplate for refrigerant type Do not use non...

Страница 4: ...binet Wire Routing 19 Wire Routing 19 Wire Sizing 20 Grounding the Cabinet 20 UC800 AFD Operation 25 Adaptive Frequency Drive Control 25 Introduction 25 Chiller and AFD Sequence of Operation 25 Compre...

Страница 5: ...mote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For variable frequency driv...

Страница 6: ...ment could result in death or serious injury Safety Precautions 1 This equipment should be adjusted and serviced by qualified electrical maintenance personnel familiar with the construction and operat...

Страница 7: ...tors Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury Disconnect all electric power including remote disconnects and discharge all motor st...

Страница 8: ...ransistors that turn on and off in response to the gate driver A combination of two distinct operating modes make up the AFDG AFDU control within the chiller s UC800 control First by controlling the i...

Страница 9: ...quirement on SSRLs of 730 780 850 890 945 and 1050 F0 Drive Bus Bars on SSRLs of 730 780 850 890 945 and 1050 G0 D Drive Module on SRRLs of 190 240 302 361 and 443 at 460V and 155 192 242 290 344 and...

Страница 10: ...nce AA Original Design of Tracer AdaptiView Chiller Control with TR200 Drive Digit 12 Starter Type A Unit Mounted Digit 13 Agency Listing 0 UL and CUL Listed Standard on All Units Digit 14 Special Opt...

Страница 11: ...sure is installed away from oil coolants or other airborne contaminants Do not install the drive above 3300 feet 1000 meters without derating output power For every 3300 feet 1000 meters above 3300 fe...

Страница 12: ...RONT VIEW 1 400 18 660 RECOMMENDED MOUNTING HOLES 2 580 3 28 17 30 1 400 23 74 18 700 2 580 3 760 3 760 23 82 VIEW A A 23 42 MAX DOOR OPENING 23 42 MAX DOOR OPENING 109 MAX DOOR SWING 109 MAX DOOR SWI...

Страница 13: ...D 13 92 12 28 6 50 4 84 5X MAGNETIC CORE CHOKES A BOTTOM VIEW 17 30 25 04 3 35 1 400 2 580 1 400 2 580 3 760 3 760 23 82 6 50 14 05 3 740 3 23 25 04 63 24 31 62 31 62 1 280 1 280 2 470 2 470 3 740 1 4...

Страница 14: ...8 43 T1 10 10 GND 16 90 MIN 22 50 MAX L1 L2 L3 2X1 TERMINAL STRIP 11 73 TOP VIEW 1 85 3 90 9 10 12 80 2 80 7 90 1 88 7 90 2 80 15 60 120VAC CONTROL LOW VOLTAGE WIRING 126 22 2 50 18 74 2 50 18 86 6 54...

Страница 15: ...N 22 50 MAX L1 L2 L3 11 73 2 91 2X1 TERMINAL STRIP 10 10 GND 18 43 T1 16 56 T2 14 69 T3 Adaptive Frequency Drive for Chillers 69 50 5 83 2X1 TERMINAL STRIP SERVICE ACCESS DOOR CIRCUIT BREAKER 1 13 30...

Страница 16: ...osed and safely be contained within the starter enclosure However the components may sustain damage 1 57 3X 10 00 19 37 17 86 14 09 6 39 7 72 47 41 44 26 1 57 30 00 2 50 1 29 63 41 INDICATES CONDUCTOR...

Страница 17: ...approximately 24 inches 61 cm to verify proper center of gravity lift point To avoid dropping of unit reposition lifting point if unit is not level Important AFDG remote mounted and AFDU unit mounted...

Страница 18: ...eye Use of two chain hoists one for each lift eye or use of a single hoist with a spreader bar are permissible methods for lifting the drive Table 3 Drive weights for AFDU unit mounted Voltage Drive P...

Страница 19: ...iring should be copper and should be sized according to applicable codes to handle the drive s continuous rated input current Refer to submittals for power lug sizes and location along with control wi...

Страница 20: ...en the ground connections to 375 in lb 42 4 N m Note The AFDU unit mounted ships grounded to the chiller WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death...

Страница 21: ...20 for drive component list Motor Leads CTs From 575V Line Local Control Panel LCP To Motor Input Power and Control Wiring AFDG SVU01L EN 21 Note Wiring from the drive to the motor is required to be r...

Страница 22: ...n mode choke Figure 10 AFDG remote mounted open assembly no doors F4 Units F3 Units are similar but have only two inverters Input Power and Control Wiring 22 AFDG SVU01L EN Units with Ceramic bearings...

Страница 23: ...Figure 11 AFDU unit mounted component layout Motor Leads Circuit Breaker Control Power Transformer Panel Cooling Fan Input Power and Control Wiring AFDG SVU01L EN 23...

Страница 24: ...r Module AFD Starter Fault Speed Signal Drive Module Common Mode Choke CTs cal ntrol nel CP Units with ceramic bearings will not get common mode chokes Units with ceramic bearings will not get common...

Страница 25: ...timal operating condition is found the algorithm can avoid the surge in the future When surge is detected a surge recovery routine makes adjustments to move out of surge reestablish stabile operating...

Страница 26: ...he UC800 Startup The starting speed for AFD under UC800 control will vary depending upon the pressure ratio acrossthe compressor The UC800 predicts the condensing pressure during startup and sets the...

Страница 27: ...ol algorithm will periodically readjust this boundary This re optimization will occur when any of three different criteria are met 1 After startup stabilization the control will re optimize unless the...

Страница 28: ...the new surge boundary Surge Detection Surge detection control logic monitors changes in compressor motor current A surge occurrence leaves a characteristic motor current signature as shown in Figure...

Страница 29: ...C800 to provide a speed reference to the drive The UC800 also provides both Fault and Up to Speed transition complete contact closure inputs for variable frequency drive starters At start of the compr...

Страница 30: ...ommunication Potential Transformers Line Side of Starter Circuit Breaker Starter Module to Variable Speed Drive Interface HFC Stop Relay 2K11 2K1 2K1 Start Relay Starter Module 3 Phase Current Transfo...

Страница 31: ...ion Potential Transformers Line Side of Starter Circuit Breaker Starter Module to Variable Speed Drive Interface HPC Stop Relay 2K11 2K1 2K1 Start Relay Starter Module 3 Phase Current Transformers Loa...

Страница 32: ...o 60 active or historic alarms A technician can interact with an individual device or a group of devices for advanced troubleshooting For more information on Tracer TU visit your local Trane Service c...

Страница 33: ...S Current Unbalance Trip Point 15 100 30 Percent Current Unbalance Grace Period 10 255 90 Seconds Maximum Acceleration Time 6 64 6 Seconds Set to 30 Acceleration Shutdown Action Shutdown Transition Sh...

Страница 34: ...the power cannot be inadvertently energized For variable frequency drives or other energy storing components provided by Trane or others refer to the appropriate manufacturer s literature for allowab...

Страница 35: ...Use the up down arrow keys to access the parameter number and then press the OK key 5 Use the up down arrow keys to change the parameter and then press the OK key to change the setting Table 10 Job sp...

Страница 36: ...small Heat sink temp 1634 0 23 Display line 2 large Power Kw 1610 0 24 Display line 3 large Freq Hz 1613 0 40 Hand on key Disabled 0 0 41 Off key Disabled 0 0 60 Main Menu password 999 0 61 Access to...

Страница 37: ...Data CT Meter Scale 0 RLA Stop Delay 3 KW Motor NP RLA Volts Hz Voltage Transformer Ratio 20 Prestart Checks Date Checked Current Unbalance Trip Point 30 Drive Grounded Acceleration Time 30 Motor Rot...

Страница 38: ...terminal connections inside the drive enclosure Ensure all are clean and tight and not rubbing against each other anywhere WARNING Live Electrical Components Failure to follow all electrical safety pr...

Страница 39: ...power including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For varia...

Страница 40: ...40 AFDG SVU01L EN Wiring Schematics For reference an as built schematic wiring diagram and a field wiring connection diagram are located inside the main control panel door of the chiller...