Basic Installation and Operation Guide
TE Series Digital Solid State Soft Starters 18 – 1250A
39 |
P a g e
F011 = Initial Voltage of Ramp 1
Factory Setting = 60%
Range = 0 - 100%
Sets the initial voltage of ramp 1 when
F010 = 1 or 3
. The initial
torque level should be set to provide just enough torque to make
the motor shaft begin to rotate while preventing torque shock
damage to mechanical components.
F012 = Initial Current of Ramp 1
Factory Setting = 200%
Range = 0 - 600%
Sets the initial current of ramp 1 when
F010 = 2 or 4.
The initial
torque level should be set to provide just enough torque to make
the motor shaft begin to rotate while preventing torque shock
damage to mechanical components.
F013 = Accel Ramp Time of Ramp 1
Factory Setting = 10 seconds
Range = 1 - 120 seconds
Sets the time between the initial torque set with
F011 or F012
and either the Max Current Limit set with
F014
or full output
voltage. Set the time to enable soft starts without stalls. Also,
consider the motor’s application. For example, centrifugal pumps
may require a shorter ramp time.
Note:
Ramp time is affected by the following conditions:
1. Current limit will extend the ramp time if the motor does not reach full
speed while in current limit mode.
2. Anti-oscillation circuit may shorten the ramp time if the motor
reaches full speed before end of ramp.
F014 = Max Current Limit of Ramp 1
Factory Setting = 350%
Range = 200 - 600%
Sets the maximum motor current that the
TE Series
starter will
allow during Ramp 1. This limit applies to both voltage and
current ramping. Current will be limited to this setting until either
the motor reaches full speed or the over load protection feature
trips (
F003
).