Basic Installation and Operation Guide
TE Series Digital Solid State Soft Starters 18 – 1250A
78 |
P a g e
Appendix 5 - Soft Starter Settings Record
The following chart may be used to record the changes made to the factory settings.
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F001
M
o
to
r an
d
O
v
e
rlo
a
d
In
fo
.
Motor Nameplate FLA
FLA must be programmed for
starter to function.
50-100% of Max Amp Rating.
Upper limit of range automatically
adjusts downward as Service factor
is increased.
1 amp
0
F002
Motor Nameplate
Service Factor
1.00 - 1.30 SF
0.05
1.0 SF
F003
Overload Class During Start
NEMA / UL Class 5 - 20
5
Class 10
F004
Overload Class During Run
NEMA / UL Class 5 - 30
5
Class 10
F005 Overload
Reset
0 = Manual
1 = Auto
2 = Disabled Overload
1
0
(Manual)
F006-9
Reserved for factory use
F010
Startin
g
an
d St
oppi
ng M
ode
s
Ramp Type Selection
VR = Voltage Ramp
CR = Current PID Ramp
1 = Ramp 1, 2 = Ramp 2
Setting 1 = VR1 + VR2
Setting 2 = CR1 + CR2
Setting 3 = VR1 + CR2
Setting 4 = CR1 + VR2
1
1
VR1+VR2
F011
Initial Torque (VR) of Ramp 1
0-100% Line Voltage
1%
60%
F012
Initial Torque (CR) of Ramp 1
0-600% Motor Current
1% 200%
F013
Accel Ramp Time of Ramp 1
1-120 seconds
1 second
10
seconds
F014
Max Current Limit of Ramp 1
200 - 600% Motor Current
1% 350%
F015
Initial Torque (VR) of Ramp 2
0-100% Line Voltage
1%
60%
F016
Initial Torque (CR) of Ramp 2
0-600% Motor Current
1% 200%
F017
Accel Ramp Time of Ramp 2
1-120 seconds
1 second
10
seconds
F018
Max Current Limit of Ramp 2
200 - 600% Motor Current
1% 350%
F019
Jog M
odes
Voltage Jog
5 – 100% Line Voltage
1%
50%
F020
Time of Voltage Jog
1 – 20 Seconds
1 second
10
seconds
F021
Current Jog
100 – 500% Motor Current
1%
150%
F022
Kick
Mode
Kick Start Voltage
0 = Disabled, or
10 - 100% Line Voltage
1%
0
Disabled
F023
Kick Start Time
0.1 - 2 Seconds
0.1second
0.8 sec
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]