Basic Installation and Operation Guide
TE Series Digital Solid State Soft Starters 18 – 1250A
32 |
P a g e
5.5.7
Current and Ground Fault Protection Features
5.5.8
Lockouts, Reset and Internal Protection Functions
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F040
Current
an
d Gr
oun
d Fa
ult Pr
ot
ectio
n
Current Imbalance Trip
0 = Disabled, or
5 - 30% imbalance
1%
0
Disabled
5.6.7
F041
Current Imbalance Trip Delay
1 - 20 seconds
1 second
2
seconds
F042
Over Current Trip
0 = Disabled, or
100 - 300% of motor FLA
1%
0
Disabled
F043
Over Current Trip Delay
1 - 20 seconds
1 second
1 second
F044
Under Current Trip
0 = Disabled, or
10 - 90% of motor FLA
1%
0
Disabled
F045
Under Current Trip Delay
1 - 60 seconds
1 second
2
seconds
F046 Ground
Fault
Trip
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1%
0
Disabled
F047
Ground Fault Trip Delay
1 - 60 seconds
1 second
2
seconds
Table 5.5.7: Current and Ground Protection Features Group
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F048
Lock
out
s, Rese
t and
Int
e
rnal Pr
otec
tion
Coast Down (Back Spin)
Lockout Timer
0 = Disabled, or 1 - 60 minutes
1 minute
0
Disabled
5.6.8
F049
Maximum Starts per Hour
0 = Disabled, or 1 – 10 starts
1
0
Disabled
F050
Minimum Time Between
Starts
0 = Disabled, or 1 - 60 minutes
1 minute
0
Disabled
F051
Internal Protection Settings
1 – 127
See“ F051 Definition Table”
1 126
5.6.8.a
F052
Auto Reset
on Selected Faults
Fault Preferences 1 – 12
See Table 5.6.7:
”Auto-Reset Selected Faults”
1
4,
Phase
Loss only
5.6.8.b
F053
Auto Reset Attempts
0 = Disabled, or 1-10 attempts
1
0
Disabled
F054
Restart Delay Time Value
Readout (for F028)
0-999 Minutes
1
0
5.6.8.c
F055
Coast Down Timer Value
for F048
1-3600 Seconds
1
0
F056
Starts Per Hour Timer Value
for F049
1-3600 Seconds
1
0
F057
Starts Per Hour
For F049
1-10 Starts
1
0
F058
Time Value Between Starts
for F050
1-3600 Seconds
1
0
F059
Thermal Capacity to Start
for F005
0-100 % Thermal Capacity
1
0
Table 5.5.8: Lockouts, Reset and Internal Protection Group