Chapter 5 - Programming
5.1
Introduction
It is best to operate the motor at its full load starting conditions to achieve
the proper time, torque and ramp settings. Initial factory settings are set
to accommodate general motor applications and provide basic motor
protection. Advanced features must be enabled via programming. The
only parameter that MUST be set by the user is motor FLA (
F001
).
5.2
Digital Interface
The
TE Series
Soft Starter includes a digital keypad with eight LEDs,
seven command keys, and an LED display with four alphanumeric digits.
Figure 5.2: Digital Interface
Table 5.2: TE Series Display Features
Keys
Reset
Clears the Trip indication and releases the Trip Relay.
Fn
Enters or exits the Program Mode.
Up and
Down
Arrows
Navigates through the Status Display Mode, scrolls up
and down through the Function List, increases or
decreases the value of the active (flashing) digit and
scrolls through the fault history. When entering values,
holding the key down for more than 2 seconds will
activate Auto-step, which increases its rate the longer
the key is held down.
Right
and Left
Arrows
Each key press shifts the active (flashing) digit to the
right or left by one position, allowing you to change
higher values of functions without waiting to Auto-step
though large numbers.
Green
LEDs
Power
On
Control power is available at A1 and A2
At-
Speed
The motor is at full power and the Bypass Contactor
has been commanded to pull in.
The SCRs are at full conduction and current has
dropped.
Yellow
LEDs
Shunt
Trip
Power is flowing to the motor in the Off mode. See
section 5.6.8.a for additional information.
Shorted
SCR
There is no voltage drop across at least one SCR
phase assembly, indicating that at least one SCR is
shorted. See section 8 for additional information.
Over
Current
Overcurrent LED lights for three sets of fault conditions:
1) During start, the unit saw current exceed the
normal rate of increase in the first 250ms.
2) During Run, current exceeded either the OC setting
in
F042
for the delay set in
F043
. This LED will be
accompanied by
oCA, oCC
or
oCd
on the display.
3) The unit has seen a Short Circuit exceeding 10x
FLA for 12.5ms. This LED will be accompanied by
SCA, SCC
or
SCD
display.
Phase
Loss
One or more of the phase currents dropped below the
threshold during starting or running.
Over
Temp
Starter has tripped due to excess heat sink
temperature. This will automatically reset.
Overload
Starter has tripped due to the Thermal Register
reaching 0000. The Overload must reset before this
fault can be cleared.
Display
8888.
4 digit 7 segment display with a decimal point on the
right side indicating Phase A.
MOTOR FLA (F001)
must be programmed
for unit to operate!