5.6.5 Pump-Flex
Decel Mode (F025 through F028
)
Pump-Flex
deceleration is a feature of the
TE Series
Soft Starter that
slowly decreases the applied voltage to the motor when a stop command
is given, resulting in a gentle decrease in motor torque. Deceleration
provides a way to extend the stopping time so that abrupt stopping does
not occur. Deceleration is useful with centrifugal pumps, material
handlers, and conveyors where abrupt stopping could be damaging to
the equipment and/or load.
SEE APPENDIX 2 AT THE END OF THIS MANUAL
for typical Pump-
Flex
Decel feature applications and more detailed descriptions of the
following functions.
F024 = Deceleration Ramp
Factory Setting = 0 (Disabled)
Range = 0 – 2
When F024 = 0
, the deceleration feature is
disabled
.
When F024 = 1
, the deceleration feature is
enabled AND
the overload
protection feature (
F003 - F005
) remains active (power off on OL
trip).
When F024 = 2
, the deceleration feature is
enabled
and deceleration
will
continue even when an overload condition trips
.
WARNING!
Setting F024 = 2 presents significant risk of over-heating the
motor beyond its design limits which could result in motor
damage and fire hazard. Do this only in circumstances where
the potential for mechanical damage outweighs the risk of
motor damage.
F025 = Begin Decel Level (BDL)
Factory Setting = 60%
Range = 0 - 100% of line voltage
Used to drop voltage to a level where there is a noticeable effect
on motor torque during initial Decel mode.
F026 = Decel Shut Off Voltage
Factory Setting = 30%
Range = 0 to (BDL -1)%
Sets the level where the starter is turned off, corresponding to
where motor torque during Decel is no longer effective. Always
set this function lower than the setting of
F026.
F027 = Decel Ramp Time
Factory Setting = 10 seconds
Range = 1 - 60 seconds
Sets the maximum time for the deceleration ramp to go from the
Begin Decel Level setting (
F026
) to the Decel Shut Off Voltage
(
F027
).
Note:
When using the Decel function, count these cycles as additional
“starts” when determining maximum starts-per-hour of the motor.
Stop Command
(Bypass Contactor Opens)
F025: Begin Decel Level
(Immediate step down)
F026: Stop Level
(VMX Output Off)
Vo
lt
a
g
e
Time
F027: Decel Ramp Time
(Determines slope)
Figure 5.6.5:
Pump-Flex De cel Ramp Settings