TCS-NET General Purpose Interface
Installation Manual
Toshiba
– 5 –
EN
2
Introduction
Applications/Functions/Specifications
Applications
• The TCB-IFCG1TLE is provided with the following input/output ports through which the central controller* can
control the output ports and read data from the input ports. The TCB-IFCG1TLE enables reading of ON/OFF
information and sensor data of relay-connected indoor units and general devices, as well as various applied
controls including voltage control of actuators, motors, etc.
• The TCB-IFCG1TLE also enables sensor-based control of air conditioners such as air conditioner ON/OFF
control with the change in digital input values of this board.
* Full access can be made through the Modbus (TCB-IFMB640TLE) interface. However, RO1, RO2, DI3, and DI6
can be accessed or read from the TOSHIBA BMS central controller such as the 64-way central control remote
controller (TCB-SC642TLE2).
• Inputs and outputs are connected to an appropriate device in the external circuit. Digital inputs and outputs can
handle binary values and analog inputs, outputs can handle linear values.
• Compatible Air Conditioners
S-MMS, S-HRM, Mini-SMMS, DI, SDI
64 Central
Remote
controller
TCC-LINK
Modbus
(TCB-IFMB640TLE)
Modbus
Master
(controller)
This product
ON/OFF control
Binary state
Temperature measurement
Linear input
Linear control
Digital output
Digital input
Analog input
Analog input
Analog output
Indoor unit
Indoor unit
Indoor unit
Relay control coil
Drive circuit input,
etc.
Drive circuit
Motor, lighting, solenoid
valve, ventilation fan,
HA equipment
Relay contact or open
collector
Transistor, etc.
Sensors
Illuminance, sense, fire
alarm, etc.
Thermistor
Operational amplifier output,
etc.
Buffer
Sensors
Illuminance, sense, fire
alarm, etc.
Operational
amplifier input, etc.
Buffer
Drive circuit
Motor, lighting, solenoid
valve, etc.
4-EN