TCS-NET General Purpose Interface
Service Manual
9
Toshiba
4-3. Conjunction function is not available
Are the input polarity and level
specified for the trigger port
provided correctly?
Is the setting value of SW5
correct?
Are inputs to DI4 and DI1
provided correctly?
See the Installation Manual,
and set the polarity, voltage
level, and current level of the
specified trigger port.
Make the following
settings: 5 POSITION =
ON; 6 POSITION = OFF.
See the Installation Manual,
and check that the connection
is made securely and an
appropriate input current level
and polarity are provided.
NO
NO
NO
NO
YES
YES
Is the setting value of SW5
correct?
See the setting tool manual for
advanced conjunction
function, and install the
software and make the
connection correctly.
YES
Is the address for central control
of the specified air conditioner
correctly registered using the
setting tool software for
advanced conjunction function?
YES
Make the following
settings: 6 POSITION =
ON; 5 POSITION = OFF.
NO
See the setting tool manual for
advanced conjunction
function, and set the address
of the applicable air
conditioner correctly.
NO
Conjunction function
cannot be set, or air
conditioning
operation is not
available.
(Using the setting
tool software for the
advanced
conjunction function)
Conjunction
function is not
available.
DI4/DI1 fixed trigger
mode
Is the setting tool software for
advanced conjunction function
installed on the configuration PC?
Is the connection to the TCB-
IFCG1TLE made correctly? Are
values written correctly?
+00DE89308801_01EN_SVM_General_IF.book Page 9 Tuesday, January 20, 2009 6:44 PM