TCS-NET General Purpose Interface
Installation Manual
Toshiba
– 7 –
EN
3
Before Installation
Check the following package contents.
Use the following wiring materials to connect the signal lines and power lines. (Procured on site)
*¹ Use shielded wire according to the installation environment.
Normally PVC cable is recommended. The conductor diameter should be approximately 0.7 mm and its
resistance should be 60
Ω
/km. For 2-core cable, the outer diameter should be approximately 5 mm.
*² Varies with use environment and conditions.
An AC adaptor unit for this product must meet the following requirements and be procured locally.
REQUIREMENT
• Output: 15 V ±5%
• Current: 0.5 A or more
• Shall conform to applicable safety standards (including EN60950-1 or IEC 60950-1, etc), EMI standards
(EN550022 and EN61000-3), and EMS standards (including EN50024, (EN61204-3), and EN61000-4).
• Shall meet environmental conditions and required lifetime.
• DC Plug 2.1mmØ (inner diameter)
5.5mmØ (outer diameter)
10mm
(length)
Recommended product is
Model name: UI312-1508 produced by UNIFIVE TECHNOLOGY CO., LTD
Homepage addresses of UNIFIVE TECHNOLOGY CO., LTD are
http://www.unifive-us.com/, http://www.unifive.com.tw/, http://www.unifive.co.kr/, http://www.unifive.com/ or http:/
www.unifive-c.com/.
No.
Item
Quantity
Remarks
1
TCB-IFCG1TLE (TCB-IFCG2TLE)
1
2
Installation Manual
1
3
Screw
4
M4 x 12mm tapping screws
No.
Line
Description
1
TCC-LINK
Type
2-core shield wires
Wire size
1.25 mm², 1000m max.
2.00 mm², 2000m max.
(Total Length of TCC-LINK Network, includes indoor/outdoor
connection.)
Length
2
Signal
Type
Multi-core wire
Stranded wire, single wire *¹
0.08097 mm² to 3.309 mm²
(AWG28 to AWG12) Max. 20 m *²
Wire size
Length
3
Power
Specified by AC adaptor
6-EN