TCS-NET General Purpose Interface
Installation Manual
Toshiba
– 16 –
8
Input/Output Specifications
Digital Inputs and Outputs
1. Functions
The following signals can be set and their states can read through the Modbus (TCB-IFMB640TLE) interface.
However, RO1, RO2 (*1), DI3, and DI6 can be accessed from a central controller such as the 64-way central
control remote controller (TCB-SC642TLE2).
DI6, DI5, DI4, DI1, DI2 and DI3 are photocoupler input signals. Transmit these input signals through contacts, a
switch, or a sink device.
For details of these signals, see the “Connection to External Devices”.
Signal classification
Port
name
Data item
TCB-IFCG1TLE
TCB-IFCG2TLE
Digital output
Relay contact
output
DO1
DO2
DO3
DO4
Output type
“a” or “b” contact
selectable
“a” or “b” contact
selectable
Output point
4
2
Maximum contact current 1 A
1 A
Maximum contact voltage 250 VAC
30 VDC
250 VAC
30 VDC
Digital input
Type 1
DI1
DI2
DI3
DI4
DI5
DI6
Input type
Photocoupler insulation
Photocoupler insulation
Number of input points
6
1
Input resistance
100
Ω
100
Ω
Minimum input ON
current
2 mA
2 mA
Maximum allowable input
ON current
30 mA
30 mA
Maximum input OFF
current
0.05 mA
0.05 mA
Connector
Signal name
SW5
-2
SW5
-3
SW5
-4
Operation
In/
Out
RO1+
RO1-
Relay 1 ch output for
general purpose
interface
Relay contact output
Out
OFF
OFF
*
Normally open. Closed for 250 ms when Relay 1 setup
request is turned ON. (*1)
OFF ON
*
Normally open. Closed for 250 ms each time Relay 1 setup
request is turned ON or OFF. HA output type (*1)
ON
*
*
Normally open. Continuously closed when Relay 1 setup
request is ON, and opened when Relay 1 setup request is
OFF. (*2)
RO2;+
RO2-
Relay 2 ch output for
general purpose
interface
Relay contact output
Out
OFF
OFF
ON
Normally closed. Opened for 250 ms when Relay 1 setup
request is turned OFF. (*1)
OFF
OFF
OFF
Normally open. Closed for 250 ms when Relay 1 setup
request is turned OFF. (*1)
OFF
ON *
Normally open. Closed when Relay 2 setup request is ON,
and opened when Relay 2 setup request is OFF.
ON
*
*
Normally open. Closed when Relay 2 setup request is ON,
and opened when Relay 2 setup request is OFF.
RO3+
RO3-
(TCB-IFCG1TLE only)
Relay 3 ch output for
general purpose
interface
*
*
*
Relay contact output. Normally open.
Closed when Relay 3 setup request is ON, and opened
when Relay 3 setup request is OFF.
Out
RO4+
RO4-
(TCB-IFCG1TLE only)
Relay 4 ch output for
general purpose
interface
*
*
*
Relay contact output. Normally open.
Closed when Relay 4 setup request is ON, and opened
when Relay 4 setup request is OFF.
Out
15-EN
+00DE89308101_01EN_TCB-IFCG10TLE_gene_IM.book Page 16 Monday, December 15, 2008 3:49 PM