Strata CTX100 Installation
Installing the CTX100 Cabinet
2-12
Strata CTX I&M 10/02
Step 6A: Install the Optional ABCS1A Battery Charger
1. Attach the ABCS1A to the inside wall of the Power Supply (see photos below). Fit the two
holes on the ABCS1A over the metal prongs of the power supply and align the two plastic tips
of the ABCS1A over the holes on the inside wall of the power supply. Snap the ABCS1A into
place. Pull on the ABCS1A to make sure that it’s securely installed.
2. Attach the ABCS1A four-wire plug onto the power supply four-prong connector (CN-501).
Step 6B: Install the Battery Cable
1. A black jumper wire is supplied with the ABTC-3M cable. Connect the black jumper wire from
the positive terminal of one 12VDC battery to the negative terminal of the second 12VDC
battery (see
Figure 2-9
).
2. Ensure that a serviceable 10-amp fuse is installed in the in-line fuse holder of the ABTC-3M
battery cable.
3. Connect the white lead of the ABTC-3M battery cable to the open positive terminal of the
12VDC battery. Connect the black lead to the open negative terminal of the second 12VDC
battery.
Figure 2-9
Battery Wiring Diagram
WARNING!
Whenever the cabinet top cover is removed, use extreme caution. Do not
touch any internal power supply components because hazardous voltages
may be exposed. Whenever adding/removing power supply components or
checking circuit breakers and fuses, unplug the power supply AC plug from
the AC source outlet.
2-Batteries/1-Cabinet
12 Volt
Batteries
80 AMP/
HR Each
ABTC-3M Cables (9 ft.)
–
+
ABCS CN-BAT
Connnector
10A Fuse
Black jumper wire
All Jumper Wires
must be 16 AWG Wire
ABCS CN-BAT
Connnector
ABCS CN-BAT
Connnector
4-Batteries/2-Cabinets
ABTC-3M Cables (9 ft.)
10A Fuse
Expansion Cabinet
Base Cabinet
12 Volt
Batteries
80 AMP/
HR Each
–
+
–
+
ABCS CN-BAT
Connnector
ABCS CN-BAT
Connnector
2-Batteries/2-Cabinets
10A Fuse
Exp. Cabinet Power Supply
Base Cabinet Power Supply
ABTC-3M Cables (9 ft.)
12 Volt
Batteries
80 AMP/
HR each
–
+
–
+
5934
4-Batteries/1-Cabinet
12 Volt
Batteries
80 AMP/
HR Each
ABTC-3M Cables (9 ft.)
–
+
ABCS CN-BAT
Connnector
10A Fuse
Base Cabinet Power Supply
Base Cabinet Power Supply
Содержание Strata CTX100
Страница 16: ...Introduction Related Documents Media xii Strata CTX I M 10 02 ...
Страница 94: ...Strata CTX100 Installation Installing the CTX100 Cabinet 2 24 Strata CTX I M 10 02 ...
Страница 150: ...Strata CTX670 Installation Remote Expansion Cabinet Unit 3 56 Strata CTX I M 10 02 ...
Страница 188: ...PCB Installation Network Requirements 4 38 Strata CTX I M 10 02 ...
Страница 238: ...T1 Loop Back Testing 6 12 Strata CTX I M 10 02 ...
Страница 310: ...Station Apparatus 2000 series Telephones 8 48 Strata CTX I M 10 02 ...
Страница 342: ...Peripheral Installation Station Message Detail Recording SMDR 9 32 Strata CTX I M 10 02 ...