Strata CTX670 Installation
Install AC Power Components
Strata CTX I&M 10/02
3-21
Strata
CTX67
0
Inst
alla
tion
Cabinet AC Power Component Description
The table shown below identifies the cabinet parts required to distribute AC power within the
Strata CTX670 cabinets.
Table 3-1
Power Cabinet Hardware
Option
Description
RPSB2
Cabinet power strip for 120VAC primary power – provides three standard 120VAC/15A outlets
(NEMA 5-15R) and nine ft. AC power cord with standard 120VAC/15A plug (NEMA 5-15P). This
unit is field installed inside system cabinet side panels. The system can use 12 amps. (max.).
See
Figures 3-12
~
3-17
.
One RPSB2 is required for two or three cabinet systems if the local electric code allows only one
AC power cord to be connected to the system.
Note
If the local electric code allows only one AC power cord to be connected to the system,
208VAC or 240VAC must be used as primary AC power for systems with four or more
cabinets.
One RPSB2 is required for a three or four cabinet system if the local electric code allows two AC
power cords connected to the system.
Two RPSB2s are required for a five cabinet system if the local electric code allows two AC power
cords connected to the system.
BPSB240
Cabinet power strip for 208VAC or 240VAC primary power. Provides three 240VAC/20A outlets
(NEMA 6-20R) and nine ft. AC power cord with a standard 240VAC/20A plug (NEMA 6-20P).
This unit is field installed inside system cabinet side panels. The cord is rated at 16 amps. (max.).
See
Figures 3-14
~
3-17
.
One BPSB240 is required for two or three cabinet systems.
Two BPSB240s are required for four or five cabinet systems.
Three BPSB240s are required for six or seven cabinet systems.
Notes
• Local electric codes allow only one AC power cord to be connected to the system when using
208VAC or 240VAC as the primary AC power.
• If using 208VAC as primary power, the plug on the BPSB240 AC power cord
(NEMA 6-20P) may have to be changed by a certified electrician depending on local electric
codes.
BACL240
AC208V or AC240VAC nine ft., 10 amps. (max.), power supply cord. This cord must be used
when the system is powered by 208VAC or 240VAC. One cord is required for each cabinet power
supply and must be ordered separately only if using 208VAC or 240VAC as the system primary
AC power.
Note
The cord conforms with a National Electric Code standard plug (NEMA 6-20P) 208VAC/
240VAC. The power strip plug that exits the system may have to be changed to a twist-
lock type by a certified electrician to conform with local electric codes.
Содержание Strata CTX100
Страница 16: ...Introduction Related Documents Media xii Strata CTX I M 10 02 ...
Страница 94: ...Strata CTX100 Installation Installing the CTX100 Cabinet 2 24 Strata CTX I M 10 02 ...
Страница 150: ...Strata CTX670 Installation Remote Expansion Cabinet Unit 3 56 Strata CTX I M 10 02 ...
Страница 188: ...PCB Installation Network Requirements 4 38 Strata CTX I M 10 02 ...
Страница 238: ...T1 Loop Back Testing 6 12 Strata CTX I M 10 02 ...
Страница 310: ...Station Apparatus 2000 series Telephones 8 48 Strata CTX I M 10 02 ...
Страница 342: ...Peripheral Installation Station Message Detail Recording SMDR 9 32 Strata CTX I M 10 02 ...