background image

15-EN

16-EN

A

A

10

Gas side

Heat insulator provided

Indoor unit shield pipe

Cut the heat insulator of the gas pipe 
(locally procured) leaving a 10 mm 
overlap with the shield of the shield pipe.

Liquid side

Heat insulator wrapping cross section A-A

Make the slit part of heat insulator to upward.

 

Insulating the pipes

Insulate the indoor unit completely so there are no 
gaps using the heat insulator provided.

 CAUTION

Securely apply insulation all the way up to the pipe 
connecting section of the indoor unit so that there is 
no exposed area. (the pipe exposed to the outside 
causes water leak.)
When wrapping the heat insulator around pipes, 
make sure the slit aperture toward the ceiling surface.

 CAUTION

• 

Bind the auxiliary pipes (two) and system 
interconnection wire and control wiring with facing 
tape tightly. In case of leftward piping and rear 
leftward piping, bind the auxiliary pipes (two) only 
with facing tape.

System interconnection wire

Indoor unit

Auxiliary 
pipes

Installation plate

Wired remote controller 
wiring

• 

Carefully arrange pipes so that any pipe does not 
stick out of the rear plate of the indoor unit.

• 

Carefully connect the auxiliary pipes and 
connecting pipes to one another and cut off the 
insulating tape wound on the connecting pipe to 
avoid double-taping at the joint, moreover, seal the 
joint with the vinyl tape, etc.

• 

Since dew results in a machine trouble, make sure 
to insulate both the connecting pipes.
(Use polyethylene foam as insulating material.)

• 

When bending a pipe, carefully do it, not to crush it.

7

 Indoor 

unit 

fi

 xing

1

  Pass the pipe through the hole in the wall, 

and hook the indoor unit on the installation 
plate at the upper hooks.

2

  Swing the indoor unit to right and left to 

con

fi

rm that it is 

fi

rmly hooked up on the 

installation plate.

3

  While pressing the indoor unit onto the 

wall, hook it at the lower part on the 
installation plate. Pull the indoor unit 
toward you to con

fi

rm that it is 

fi

rmly 

hooked up on the installation plate.

1

2

Hook here

Installation plate

Press

(unhook)

Hook

For detaching the indoor unit from the installation 
plate, pull the indoor unit toward you while 
pushing its bottom up at the speci

fi

ed parts.

Push

Push

– 8 –

8

 Drainage

1

  Run the drain hose sloped downwards.

NOTE

Hole should be made at a slight downward slant on 
the outdoor side.

2

  Put water in the drain pan and make sure 

that the water is drained out of doors.

3

  When connecting extension drain hose, 

insulate the connecting part of extension 
drain hose with shield pipe.

Do not form the drain hose 
into a wavy shape.

Inside the 
room

Do not put the 
drain hose end 
in the drainage 
ditch.

Do not put the 
drain hose end 
into water.

Do not rise the drain hose.

Shield pipe

Extension drain hose

Drain hose

50 mm
or more

 CAUTION

Arrange the drain pipe for proper drainage from the 
unit.
Improper drainage can result in dew-dropping.

This air conditioner has the structure designed to drain 
water collected from dew, which forms on the back of 
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts 
at a height above the drain guide.

Space for pipes

Wall

Drain guide

9

 Refrigerant 

piping

 CAUTION

When the refrigerant pipe is long, provide support 
brackets at intervals of 2.5 m to 3 m to clamp the 
refrigerant pipe. Otherwise, abnormal sound may be 
generated.
Use the 

fl

 are nut attached with the indoor unit or 

R410A 

fl

 are nut.

 

Permissible piping length and 
height difference

They vary depending on the outdoor unit. For details, 
refer to the Installation Manual attached to the outdoor 
unit.

 

Pipe size

Model: RAV-

Pipe size (mm)

Gas side

Liquid side

SM30

Ø9.52

Ø6.35

SM40

Ø12.70

Ø6.35

 

Connecting refrigerant piping

Flaring

1

  Cut the pipe with a pipe cutter.

Remove burrs completely. (remaining burrs 
may cause gas leakage.)

2

 Insert 

fl

are nut into the pipe, and 

fl

are the 

pipe.

Use the 

fl

are nut provided with the unit or 

the one used for the R410A refrigerant. The 

fl

aring dimensions for R410A are different 

from the ones used for the conventional R22 
refrigerant. A new 

fl

are tool manufactured 

for use with the R410A refrigerant is 
recommended, but the conventional tool can 
still be used if the projection margin of the 
copper pipe is adjusted to be as shown in the 
following table.

1111056499_(01)_EN.indb   8

1111056499_(01)_EN.indb   8

10/13/14   9:13 AM

10/13/14   9:13 AM

Содержание RAV-SM307KRTP-E

Страница 1: ...l Type RAV SM307KRTP E RAV SM407KRTP E AIR CONDITIONER SPLIT TYPE Installation Manual For commercial use s Installation Manual English 1111056499_ 01 cover _EN indd 1 1111056499_ 01 cover _EN indd 1 10 13 14 9 57 AM 10 13 14 9 57 AM ...

Страница 2: ...ation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individu...

Страница 3: ...tion for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing...

Страница 4: ...down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked...

Страница 5: ...nied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conv...

Страница 6: ...g under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controll...

Страница 7: ...igure OK NO GOOD Not cooled well Good installation place Cooled well all over Bad installation place Screen Cutting a hole In case of installing the refrigerant pipes from the rear 1 Decide the hole position for piping at 100 mm from the arrow mark on the installation plate and drill a hole at a slight downward slant toward outdoor side 80 100 180 Ø65 mm 100 mm The centre of the pipe hole is above...

Страница 8: ...y needle nose pliers and pull out How to fix the drains cap 1 Insert hexagonal wrench dia 4 mm in a centre head 4 mm 2 Firmly insert drains cap Insert a hexagon wrench 4 mm No gap Do not apply lubricating oil refrigerant machine oil when inserting the drain cap Application causes deterioration and drain leakage from the plug CAUTION Firmly insert the drain hose and drain cap otherwise water may le...

Страница 9: ...from the installation plate pull the indoor unit toward you while pushing its bottom up at the specified parts Push Push 8 8 Drainage 1 Run the drain hose sloped downwards NOTE Hole should be made at a slight downward slant on the outdoor side 2 Put water in the drain pan and make sure that the water is drained out of doors 3 When connecting extension drain hose insulate the connecting part of ext...

Страница 10: ... or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunction 9 Open the valve fully Open the valve of the outdoor unit fully A...

Страница 11: ...m CAUTION The remote controller wire and system interconnection wires cannot be parallel to contact each other and cannot be stored in the same conduits If doing so a trouble may be caused on the control system due to noise or other factor L1 L n L 2 L Remote controller Indoor unit Indoor unit Indoor unit Indoor unit Remote controller wiring max 8 units Remote controller inter unit wiring Wiring b...

Страница 12: ... terminal 1 and 2 on terminal block respectively System interconnection wire 3 is not used 3 Connect the earth wire to the earth screw located on the underside of the electrical control box 4 Clamp the system interconnection wire with the cord clamp 5 Attach the terminal cover and the air intake grille to the indoor unit Cord clamp Earth screw System interconnection wiring Cord clamp Screw Screw E...

Страница 13: ...re making settings CAUTION Set only the CODE No shown in the following table Do NOT set any other CODE No If a CODE No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result The displays appearing during the setting process differ from the ones for previous remote controllers AMT31E there are more CODE No 1 6 1 3 2 5 4 1 Push button and...

Страница 14: ...NIT No 1 2 UNIT No 1 1 The fan of the selected unit runs 3 Adjust the power save setting by pushing TIME buttons Each push of the button changes the power level by 1 within the range from 100 to 50 The factory default is 75 Setting of power level in power saving mode 4 Determine the setting by pushing button 5 Push button to complete the setting Remote controller switch monitoring function This fu...

Страница 15: ...ocedure Connect the terminal block A B of the indoor unit connected with a remote controller to the terminal blocks A B of the indoor units of other indoor units by wiring the inter unit wire of the remote controller When the power supply has been turned on the automatic address setup starts and which indicates that address is being set up flashes on the display part in about 3 minutes During setu...

Страница 16: ...k the changed contents Address change check Before change 3 3 1 After change 2 2 2 Pushing button clears the contents of which setup was changed In this case procedure from 2is repeated Indoor UNIT No before setup change is displayed 7 After check of the changed contents push button setup is determined When button is pushed the display disappears and the status becomes the usual stop status when b...

Страница 17: ...emote controller Use the optional wired remote controller Wiring for central control The terminal block for central control wiring 3 and 4 is the same as that for optional wired remote controller Connect the central control wire to the terminals 3 and 4 on the terminal block in the same way as the optional wired remote controller For details refer to the installation manual of the applicable centr...

Страница 18: ...y connected the system will not operate or other errors may occur Centrally control the system by connecting to the TCC LINK central control system Setting central control addresses When air conditioners of the SDI DI series are connected to the TCC LINK central control system for central control using this product set the addresses of indoor units using the following procedure Completion of ELECT...

Страница 19: ...ange For 30 or more refrigeration systems when they are used together with the SMMS series the number of refrigeration systems of the SMMS series is included The line address change setting procedure for up to the 29th refrigeration system is the same as that described in step 1 on the previous page Since all line addresses are set to 1 except for group control by the automatic address setup funct...

Страница 20: ... 1 5 Push check button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal When a test run is not performed properly When a test run is not performed properly refer to the error code and the part to be checked on Troubleshooting In case of wireless remote controller Forced test operation is performed in a different way REQUIREMENT For the oper...

Страница 21: ...ce can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Part Inspection method Heat exchanger Access from inspection...

Страница 22: ...t or short circuit of the heat exchanger sensor TCJ was detected Auto reset F02 ALT Indoor unit heat exchanger sensor TC error Indoor Heat exchanger sensor TC indoor P C board Open circuit or short circuit of the heat exchanger sensor TC was detected Auto reset F04 ALT Outdoor unit discharge temp sensor TD error Outdoor Outdoor temp sensor TD outdoor P C board Open circuit or short circuit of the ...

Страница 23: ...vices outdoor unit P C board Abnormal stop due to incorrect external input into CN80 Entire stop L31 SIM Phase sequence error etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermostat OFF P01 ALT Indoor unit fan error Indoor Indoor fan motor indoor P C board Indoor AC fan error fan motor thermal relay activated...

Страница 24: ...1111056499 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1111056499_ 01 _EN indb 2 1111056499_ 01 _EN indb 2 10 13 14 9 13 AM 10 13 14 9 13 AM ...

Отзывы: