– 22 –

Wired 

remote 

controller 

display

Wireless remote controller

Sensor block display of 

receiving unit

Main defective parts

Judging 

device

Parts to be checked /

error description

Air 

conditioner 

status

Indication

Operation 

Timer Ready

GR GR OR

Flashing

F10

ALT

Indoor unit room temp. 
sensor (TA) error

Indoor

Room temp. sensor (TA), indoor P.C. board 
--- Open-circuit or short-circuit of the room 
temp. sensor (TA) was detected.

Auto-reset

F12

ALT

TS sensor error

Outdoor

TS sensor may be displaced, disconnected 
or short-circuited.

Entire stop

F13

ALT

Heat sink sensor error

Outdoor

Abnormal temperature was detected by the 
temp. sensor of the IGBT heat sink.

Entire stop

F15

ALT

Temp. sensor 
connection error

Outdoor

Temp. sensor (TE / TS) may be connected 
incorrectly. 

Entire stop

F29

SIM

Indoor unit, other P.C. 
board error

Indoor

Indoor P.C. board --- EEPROM error. 

Auto-reset

F31

SIM

Outdoor unit P.C. board

Outdoor

Outdoor P.C. board ---- In the case of 
EEPROM error.

Entire stop

H01

Outdoor unit 
compressor breakdown

Outdoor

Current detect circuit, power voltage --- 
Minimum frequency was reached in the 
current releasing control or short-circuit 
current (Idc) after direct excitation was 
detected.

Entire stop

H02

Outdoor unit 
compressor lock

Outdoor

Compressor circuit --- Compressor lock 
was detected.

Entire stop

H03

Outdoor unit current 
detect circuit error

Outdoor

Current detect circuit, outdoor unit P.C. 
board --- Abnormal current was detected in 
AC-CT or a phase loss was detected.

Entire stop

H04

Case thermostat 
operation

Outdoor

Malfunction of the case thermostat

Entire stop

H06

Outdoor unit 
low-pressure system 
error

Outdoor

Current, high-pressure switch circuit, 
outdoor P.C. board --- Pressure sensor 
error was detected or low-pressure 
protective operation was activated.

Entire stop

L03

SIM

Duplicated header 
indoor units 

Indoor

Indoor address setting error --- There are 
two or more header units in the group.

Entire stop

L07

SIM

Group line in individual 
indoor unit 

Indoor

Indoor address setting error --- There is 
at least one group-connected indoor unit 
among individual indoor units.

Entire stop

L08

SIM

Indoor group address 
not set 

Indoor

Indoor address setting error --- Indoor 
address group has not been set. 

Entire stop

L09

SIM

Indoor unit capacity 
not set

Indoor

Indoor unit capacity has not been set.

Entire stop

L10

SIM

Outdoor unit P.C. board

Outdoor

In the case of outdoor P.C. board jumper 
wire (for service) setting error.

Entire stop

L20

SIM

LAN communication 
error

Network 
adapter 
central 
control

Address setting, central control remote 
controller, network adapter ---
Duplication of address in central control 
communication.

Auto-reset

L29

SIM

Other outdoor unit error

Outdoor

Other outdoor unit error.

Entire stop

1) Communication error between IPDU 
MCU and CDB MCU.

Entire stop

2) Abnormal temperature was detected by 
the heat sink temp. sensor in IGBT.

L30

SIM

Abnormal external 
input into indoor unit 
(interlock)

Indoor

External devices, outdoor unit P.C.
board --- Abnormal stop due to incorrect 
external input into CN80.

Entire stop

L31

SIM

Phase sequence error, 
etc.

Outdoor

Power supply phase sequence, outdoor unit 
P.C. board --- Abnormal phase sequence of 
the 3-phase power supply.

Operation 
continued 
(thermostat 
OFF)

P01

ALT

Indoor unit fan error

Indoor

Indoor fan motor, indoor P.C. board ---
Indoor AC fan error (fan motor thermal relay 
activated) was detected.

Entire stop

Wired 

remote 

controller 

display

Wireless remote controller

Sensor block display of 

receiving unit

Main defective parts

Judging 

device

Parts to be checked /

error description

Air 

conditioner 

status

Indication

Operation 

Timer Ready

GR GR OR

Flashing

P03

ALT

Outdoor unit discharge 
temp. error

Outdoor

An error was detected in the discharge 
temp. releasing control.

Entire stop

P04

ALT

Outdoor unit 
high-pressure system 
error

Outdoor

High-pressure switch --- The IOL was 
activated or an error was detected in the 
high-pressure releasing control using the 
TE.

Entire stop

P05

ALT

Open phase detected

Outdoor

The power wire may be connected 
incorrectly. Check open phase and voltages 
of the power supply.

Entire stop

P07

ALT

Heat sink overheat

Outdoor

Abnormal temperature was detected by the 
temp. sensor of the IGBT heat sink.

Entire stop

P10

ALT

Indoor unit water 
over

fl

 ow detected

Indoor

Drain pipe, clogging of drainage, 

fl

 oat 

switch circuit, indoor P.C. board ---
Drainage is out of order or the 

fl

 oat switch 

was activated.

Entire stop

P12

ALT

Abnormal operation of 
the fan of the indoor unit

Indoor

Abnormal operation of the indoor fan motor, 
indoor P.C. board, or indoor DC fan (over 
current or lock, etc.) is detected.

Entire stop

P15

ALT

Gas leakage detected

Outdoor

There may be gas leakage from the pipe or 
connecting part. Check for gas leakage.

Entire stop

P19

ALT

 4-way valve error

Outdoor 
(Indoor)

4-way valve, indoor temp. sensors (TC /
TCJ) --- An error was detected due to 
temperature drop of the indoor unit heat 
exchanger sensor during heating.

Auto-reset

P20

ALT

High-pressure protective 
operation

Outdoor

High-pressure protection. 

Entire stop

P22

ALT

Outdoor unit fan error

Outdoor

Outdoor unit fan motor, outdoor unit P.C. 
board --- An error (overcurrent, locking, 
etc.) was detected in the outdoor unit fan 
drive circuit.

Entire stop

P26

ALT

Outdoor unit inverter Idc 
activated

Outdoor

IGBT, outdoor unit P.C. board, inverter 
wiring, compressor --- Short-circuit 
protection for compressor drive circuit 
devices (G-Tr / IGBT) was activated.

Entire stop

P29

ALT

Outdoor unit position 
error

Outdoor

Outdoor unit P.C. board, high-pressure 
switch --- Compressor motor position error 
was detected.

Entire stop

P31

ALT

Other indoor unit error

Indoor

Another indoor unit in the group is raising 
an alarm.

Entire stop

E03 / L07 / L03 / L08 alarm check locations 
and error description.

Auto-reset

: Lighting   : Flashing   : OFF   : The air conditioner automatically enters the auto-address setting mode.

ALT: When two LEDs are 

fl

 ashing, they 

fl

 ash alternately. SIM: When two LEDs are 

fl

 ashing, they 

fl

 ash in synchronization.

Receiving unit display OR: Orange GR: Green

1111056499_(01)_EN.indb   22

1111056499_(01)_EN.indb   22

10/13/14   9:13 AM

10/13/14   9:13 AM

Содержание RAV-SM307KRTP-E

Страница 1: ...l Type RAV SM307KRTP E RAV SM407KRTP E AIR CONDITIONER SPLIT TYPE Installation Manual For commercial use s Installation Manual English 1111056499_ 01 cover _EN indd 1 1111056499_ 01 cover _EN indd 1 10 13 14 9 57 AM 10 13 14 9 57 AM ...

Страница 2: ...ation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individu...

Страница 3: ...tion for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing...

Страница 4: ...down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked...

Страница 5: ...nied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conv...

Страница 6: ...g under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controll...

Страница 7: ...igure OK NO GOOD Not cooled well Good installation place Cooled well all over Bad installation place Screen Cutting a hole In case of installing the refrigerant pipes from the rear 1 Decide the hole position for piping at 100 mm from the arrow mark on the installation plate and drill a hole at a slight downward slant toward outdoor side 80 100 180 Ø65 mm 100 mm The centre of the pipe hole is above...

Страница 8: ...y needle nose pliers and pull out How to fix the drains cap 1 Insert hexagonal wrench dia 4 mm in a centre head 4 mm 2 Firmly insert drains cap Insert a hexagon wrench 4 mm No gap Do not apply lubricating oil refrigerant machine oil when inserting the drain cap Application causes deterioration and drain leakage from the plug CAUTION Firmly insert the drain hose and drain cap otherwise water may le...

Страница 9: ...from the installation plate pull the indoor unit toward you while pushing its bottom up at the specified parts Push Push 8 8 Drainage 1 Run the drain hose sloped downwards NOTE Hole should be made at a slight downward slant on the outdoor side 2 Put water in the drain pan and make sure that the water is drained out of doors 3 When connecting extension drain hose insulate the connecting part of ext...

Страница 10: ... or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunction 9 Open the valve fully Open the valve of the outdoor unit fully A...

Страница 11: ...m CAUTION The remote controller wire and system interconnection wires cannot be parallel to contact each other and cannot be stored in the same conduits If doing so a trouble may be caused on the control system due to noise or other factor L1 L n L 2 L Remote controller Indoor unit Indoor unit Indoor unit Indoor unit Remote controller wiring max 8 units Remote controller inter unit wiring Wiring b...

Страница 12: ... terminal 1 and 2 on terminal block respectively System interconnection wire 3 is not used 3 Connect the earth wire to the earth screw located on the underside of the electrical control box 4 Clamp the system interconnection wire with the cord clamp 5 Attach the terminal cover and the air intake grille to the indoor unit Cord clamp Earth screw System interconnection wiring Cord clamp Screw Screw E...

Страница 13: ...re making settings CAUTION Set only the CODE No shown in the following table Do NOT set any other CODE No If a CODE No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result The displays appearing during the setting process differ from the ones for previous remote controllers AMT31E there are more CODE No 1 6 1 3 2 5 4 1 Push button and...

Страница 14: ...NIT No 1 2 UNIT No 1 1 The fan of the selected unit runs 3 Adjust the power save setting by pushing TIME buttons Each push of the button changes the power level by 1 within the range from 100 to 50 The factory default is 75 Setting of power level in power saving mode 4 Determine the setting by pushing button 5 Push button to complete the setting Remote controller switch monitoring function This fu...

Страница 15: ...ocedure Connect the terminal block A B of the indoor unit connected with a remote controller to the terminal blocks A B of the indoor units of other indoor units by wiring the inter unit wire of the remote controller When the power supply has been turned on the automatic address setup starts and which indicates that address is being set up flashes on the display part in about 3 minutes During setu...

Страница 16: ...k the changed contents Address change check Before change 3 3 1 After change 2 2 2 Pushing button clears the contents of which setup was changed In this case procedure from 2is repeated Indoor UNIT No before setup change is displayed 7 After check of the changed contents push button setup is determined When button is pushed the display disappears and the status becomes the usual stop status when b...

Страница 17: ...emote controller Use the optional wired remote controller Wiring for central control The terminal block for central control wiring 3 and 4 is the same as that for optional wired remote controller Connect the central control wire to the terminals 3 and 4 on the terminal block in the same way as the optional wired remote controller For details refer to the installation manual of the applicable centr...

Страница 18: ...y connected the system will not operate or other errors may occur Centrally control the system by connecting to the TCC LINK central control system Setting central control addresses When air conditioners of the SDI DI series are connected to the TCC LINK central control system for central control using this product set the addresses of indoor units using the following procedure Completion of ELECT...

Страница 19: ...ange For 30 or more refrigeration systems when they are used together with the SMMS series the number of refrigeration systems of the SMMS series is included The line address change setting procedure for up to the 29th refrigeration system is the same as that described in step 1 on the previous page Since all line addresses are set to 1 except for group control by the automatic address setup funct...

Страница 20: ... 1 5 Push check button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal When a test run is not performed properly When a test run is not performed properly refer to the error code and the part to be checked on Troubleshooting In case of wireless remote controller Forced test operation is performed in a different way REQUIREMENT For the oper...

Страница 21: ...ce can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Part Inspection method Heat exchanger Access from inspection...

Страница 22: ...t or short circuit of the heat exchanger sensor TCJ was detected Auto reset F02 ALT Indoor unit heat exchanger sensor TC error Indoor Heat exchanger sensor TC indoor P C board Open circuit or short circuit of the heat exchanger sensor TC was detected Auto reset F04 ALT Outdoor unit discharge temp sensor TD error Outdoor Outdoor temp sensor TD outdoor P C board Open circuit or short circuit of the ...

Страница 23: ...vices outdoor unit P C board Abnormal stop due to incorrect external input into CN80 Entire stop L31 SIM Phase sequence error etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermostat OFF P01 ALT Indoor unit fan error Indoor Indoor fan motor indoor P C board Indoor AC fan error fan motor thermal relay activated...

Страница 24: ...1111056499 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1111056499_ 01 _EN indb 2 1111056499_ 01 _EN indb 2 10 13 14 9 13 AM 10 13 14 9 13 AM ...

Отзывы: