How to set the SW01

1

  Remove the front panel.

• 

Before removing the front panel, direct the 
horizontal louver to the direction shown in the 

fi

gure below.

• 

Remove the screws securing the front panel, 
and detach it from the indoor unit.

3

1

2

2

  Remove the earth wire, TC, TCJ sensor, 

and motor lead (louver motor, fan motor).

Electrical control 
box 

fi

xing screw

TCJ sensor

TC sensor

Fan motor 
connector 
insert position

Earth wire

Electrical control 
box 

fi

xing Screw

3

  Remove the screws and detach the 

electrical control box.

4

  Remove the electrical control box cover 

and set bit1 of SW01 on the board to ON.

(Do not touch SW02 as it is used for other 
setting.)

ON

1

2

ON

1

2

Factory default After setting

SW01: OFF

SW02: OFF

SW01: ON

SW02: OFF

5

  Assemble the removed parts by reversing 

steps 1 to 3.

Insert the sensors and motor lead (louver motor, 
fan motor) into the original positions.

 CAUTION

Connect the sensor and the motor lead certainly 
back to the previous position. If they are not properly 
connected, the system will not operate or other errors 
may occur.

 

Centrally control the system by connecting to the TCC-LINK central control system.

Setting central control addresses

When air conditioners of the SDI, DI series are connected to the TCC-LINK central control system for central 
control using this product, set the addresses of indoor units using the following procedure.

Completion of 

ELECTRIC WORK construction

The system performs the address setup 

automatically after power-on.

Change line addresses.

If automatic address setup has not been performed 

successfully, set addresses manually.

* Refer to 

“Manual address setup procedure”

.

System power ON

Automatic address setup

Line address manual setting / change

Are indoor units under group control?

Are all indoor units under central control set to 

header units (group address = 1)?

Set indoor units under central control to header units again,

and set those that are out of central control to follower units again.

Set central control addresses

* Refer to 

“Manual address setup procedure”

.

* Refer to the manual of the central control system.

End

No

No

Yes

Yes

1111056499_(01)_EN.indb   17

1111056499_(01)_EN.indb   17

10/13/14   9:13 AM

10/13/14   9:13 AM

Содержание RAV-SM307KRTP-E

Страница 1: ...l Type RAV SM307KRTP E RAV SM407KRTP E AIR CONDITIONER SPLIT TYPE Installation Manual For commercial use s Installation Manual English 1111056499_ 01 cover _EN indd 1 1111056499_ 01 cover _EN indd 1 10 13 14 9 57 AM 10 13 14 9 57 AM ...

Страница 2: ...ation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individu...

Страница 3: ...tion for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing...

Страница 4: ...down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked...

Страница 5: ...nied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conv...

Страница 6: ...g under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controll...

Страница 7: ...igure OK NO GOOD Not cooled well Good installation place Cooled well all over Bad installation place Screen Cutting a hole In case of installing the refrigerant pipes from the rear 1 Decide the hole position for piping at 100 mm from the arrow mark on the installation plate and drill a hole at a slight downward slant toward outdoor side 80 100 180 Ø65 mm 100 mm The centre of the pipe hole is above...

Страница 8: ...y needle nose pliers and pull out How to fix the drains cap 1 Insert hexagonal wrench dia 4 mm in a centre head 4 mm 2 Firmly insert drains cap Insert a hexagon wrench 4 mm No gap Do not apply lubricating oil refrigerant machine oil when inserting the drain cap Application causes deterioration and drain leakage from the plug CAUTION Firmly insert the drain hose and drain cap otherwise water may le...

Страница 9: ...from the installation plate pull the indoor unit toward you while pushing its bottom up at the specified parts Push Push 8 8 Drainage 1 Run the drain hose sloped downwards NOTE Hole should be made at a slight downward slant on the outdoor side 2 Put water in the drain pan and make sure that the water is drained out of doors 3 When connecting extension drain hose insulate the connecting part of ext...

Страница 10: ... or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunction 9 Open the valve fully Open the valve of the outdoor unit fully A...

Страница 11: ...m CAUTION The remote controller wire and system interconnection wires cannot be parallel to contact each other and cannot be stored in the same conduits If doing so a trouble may be caused on the control system due to noise or other factor L1 L n L 2 L Remote controller Indoor unit Indoor unit Indoor unit Indoor unit Remote controller wiring max 8 units Remote controller inter unit wiring Wiring b...

Страница 12: ... terminal 1 and 2 on terminal block respectively System interconnection wire 3 is not used 3 Connect the earth wire to the earth screw located on the underside of the electrical control box 4 Clamp the system interconnection wire with the cord clamp 5 Attach the terminal cover and the air intake grille to the indoor unit Cord clamp Earth screw System interconnection wiring Cord clamp Screw Screw E...

Страница 13: ...re making settings CAUTION Set only the CODE No shown in the following table Do NOT set any other CODE No If a CODE No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result The displays appearing during the setting process differ from the ones for previous remote controllers AMT31E there are more CODE No 1 6 1 3 2 5 4 1 Push button and...

Страница 14: ...NIT No 1 2 UNIT No 1 1 The fan of the selected unit runs 3 Adjust the power save setting by pushing TIME buttons Each push of the button changes the power level by 1 within the range from 100 to 50 The factory default is 75 Setting of power level in power saving mode 4 Determine the setting by pushing button 5 Push button to complete the setting Remote controller switch monitoring function This fu...

Страница 15: ...ocedure Connect the terminal block A B of the indoor unit connected with a remote controller to the terminal blocks A B of the indoor units of other indoor units by wiring the inter unit wire of the remote controller When the power supply has been turned on the automatic address setup starts and which indicates that address is being set up flashes on the display part in about 3 minutes During setu...

Страница 16: ...k the changed contents Address change check Before change 3 3 1 After change 2 2 2 Pushing button clears the contents of which setup was changed In this case procedure from 2is repeated Indoor UNIT No before setup change is displayed 7 After check of the changed contents push button setup is determined When button is pushed the display disappears and the status becomes the usual stop status when b...

Страница 17: ...emote controller Use the optional wired remote controller Wiring for central control The terminal block for central control wiring 3 and 4 is the same as that for optional wired remote controller Connect the central control wire to the terminals 3 and 4 on the terminal block in the same way as the optional wired remote controller For details refer to the installation manual of the applicable centr...

Страница 18: ...y connected the system will not operate or other errors may occur Centrally control the system by connecting to the TCC LINK central control system Setting central control addresses When air conditioners of the SDI DI series are connected to the TCC LINK central control system for central control using this product set the addresses of indoor units using the following procedure Completion of ELECT...

Страница 19: ...ange For 30 or more refrigeration systems when they are used together with the SMMS series the number of refrigeration systems of the SMMS series is included The line address change setting procedure for up to the 29th refrigeration system is the same as that described in step 1 on the previous page Since all line addresses are set to 1 except for group control by the automatic address setup funct...

Страница 20: ... 1 5 Push check button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal When a test run is not performed properly When a test run is not performed properly refer to the error code and the part to be checked on Troubleshooting In case of wireless remote controller Forced test operation is performed in a different way REQUIREMENT For the oper...

Страница 21: ...ce can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Part Inspection method Heat exchanger Access from inspection...

Страница 22: ...t or short circuit of the heat exchanger sensor TCJ was detected Auto reset F02 ALT Indoor unit heat exchanger sensor TC error Indoor Heat exchanger sensor TC indoor P C board Open circuit or short circuit of the heat exchanger sensor TC was detected Auto reset F04 ALT Outdoor unit discharge temp sensor TD error Outdoor Outdoor temp sensor TD outdoor P C board Open circuit or short circuit of the ...

Страница 23: ...vices outdoor unit P C board Abnormal stop due to incorrect external input into CN80 Entire stop L31 SIM Phase sequence error etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermostat OFF P01 ALT Indoor unit fan error Indoor Indoor fan motor indoor P C board Indoor AC fan error fan motor thermal relay activated...

Страница 24: ...1111056499 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1111056499_ 01 _EN indb 2 1111056499_ 01 _EN indb 2 10 13 14 9 13 AM 10 13 14 9 13 AM ...

Отзывы: