FILE NO. SVM-13072
11. REPLACEMENT OF THE SERVICE P.C. BOARD
11-1-1. RAV-SM564AT
*
P
*
, SM804AT
*
P
*
(MCC-1645)
! WARNING
Don’t open the inverter cover before 1 minute after power has been turned off because an electric shock may be occurred.
Replacement steps:
1
Model name
J800
J801
J802
J803
○
:
Connected
×:
Cut
Service P.C. Board
○
○
○
○
RAV-SM564AT*P*
×
○
○
○
RAV-SM804AT*P*
○
×
○
○
2
Jumper wires
Jumper wires
“J800
〜
J803”
Cut the jumper wires of the service board, as instructed in the table below.
The jumper setting of J800
〜
J803 differs from original supplied P.C.Board, therefore be sure to configure the jumpers
as in the table below. If the model is not specified, the equipment will not operate.
Jumper wires
“J804
〜
J805”
Set the jumper wires J804
〜
J805 of the service board to the same as settings of the P.C.board before replacement.
– 92 –
SVM-13072.indb 92
SVM-13072.indb 92
11/01/13 1:53 PM
11/01/13 1:53 PM
Содержание RAV-SM1104ATJP-E
Страница 116: ...FILE NO SVM 13072 Inverter assembly SM56 116 SVM 13072 indb 116 SVM 13072 indb 116 11 01 13 1 54 PM 11 01 13 1 54 PM ...
Страница 120: ...FILE NO SVM 13072 Inverter assembly SM80 120 SVM 13072 indb 120 SVM 13072 indb 120 11 01 13 1 54 PM 11 01 13 1 54 PM ...
Страница 127: ...FILE NO SVM 13072 127 SVM 13072 indb 127 SVM 13072 indb 127 11 01 13 1 54 PM 11 01 13 1 54 PM ...