– 14 –
FILE NO. SVM-13072
1. SPECIFICATIONS
1-1. Outdoor Unit
<Digital Inverter>
Model name
Outdoor unit
RAV-SM
564AT
*
P
*
804AT
*
P
*
Power supply
1 phase 220-240V, 50Hz
1 phase 220V, 60Hz
(Power exclusive to outdoor is required.)
Compressor
Type
Hermetic compressor
Motor
(kW)
1.1 1.6
Pole
4
4
Refrigerant charged
(kg)
1.1
1.7
Refrigerant control
Pulse motor valve
Inter
connecting pipe
Standard length
(m)
7.5
7.5
Min. length
(m)
5
5
Max. total length
(m)
30
30
Additional refrigerant charge
under long piping connector
20g/m
(21m to 30m)
40g/m
(21m to 30m)
Height
difference
Outdoor lower
(m)
30
30
Outdoor higher
(m)
30
30
Outer dimension
Height
(mm)
550
550
Width
(mm)
780
780
Depth
(mm)
290
290
Appearance
Silky shade (Muncel 1Y8.5/0.5)
Total weight
(kg)
40
44
Heat exchanger
Finned tube
Fan unit
Fan
Propeller fan
Standard air flow high
(m3/min.)
40
45
Motor
(W)
43
43
Connecting pipe
Gas side
(mm)
12.7
15.9
Liquid side
(mm)
6.4
9.5
Sound pressure level
Cooling/Heating (dB·A)
46/48
48/52
Sound power level
Cooling/Heating (dB·A)
63/65
65/69
Outside air temperature, Cooling
°C (Dry bulb temp.)
46 to -15
Outside air temperature, Heating
°C (Wet bulb temp.)
15 to -15
SVM-13072.indb 14
SVM-13072.indb 14
11/01/13 1:53 PM
11/01/13 1:53 PM
Содержание RAV-SM1104ATJP-E
Страница 116: ...FILE NO SVM 13072 Inverter assembly SM56 116 SVM 13072 indb 116 SVM 13072 indb 116 11 01 13 1 54 PM 11 01 13 1 54 PM ...
Страница 120: ...FILE NO SVM 13072 Inverter assembly SM80 120 SVM 13072 indb 120 SVM 13072 indb 120 11 01 13 1 54 PM 11 01 13 1 54 PM ...
Страница 127: ...FILE NO SVM 13072 127 SVM 13072 indb 127 SVM 13072 indb 127 11 01 13 1 54 PM 11 01 13 1 54 PM ...