– 41 –
FILE NO. SVM-13072
3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by current transformer
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
I
1
I
1 – 0.5
Current [A]
Frequency down
Normal operation
Hold
Hold
Model
SM56
SM80
COOL HEAT COOL HEAT
I1 value [A]
10.1
12.0 14.5
14.0
Model
SM110
SM140
COOL HEAT COOL HEAT
I1 value [A]
21.2
21.2
21.2
21.2
4. Outdoor fan control
Allocations of fan tap revolutions [rpm]
Model
W1
W2
W3
W4
W5
W6
W7
W8
W9
WA
WB
WC
WD
WE
WF
SM56
200
300
350
410
480
500
530
560
640
670
700
750
800
840
950
SM80
200
300
350
410
480
500
530
560
640
670
700
750
840
980
1050
SM110
200
210
250
320
390
460
530
600
660
730
770
850
870
900
900
SM140
200
210
250
320
390
460
530
600
660
730
770
850
870
900
900
4-1. Cooling fan control
1) An outdoor fan is controlled by TL sensor, TO sensor and compressor frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TL sensor temperature after then.
+
1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
Rotational frequency hold
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
SM56, 80 : WE tap
SM110, 140 : WD tap
TL
55˚C
38˚C
35˚C
58˚C
Temp.
range
SM56
34.2 Hz or lower 34.2Hz to 58.8Hz 58.8Hz or higher
SM80
46.8 Hz or lower 46.8Hz to 83.4Hz 83.4Hz or higher
Min.
Max.
Min.
Max.
Min.
Max.
38°C
≤
TO
W6
WB
W8
WE
WA
WE
29°C
≤
TO < 38°C
W5
WA
W7
WE
W9
WE
15°C
≤
TO < 29°C
W3
W7
W5
W9
W7
WB
5°C
≤
TO < 15°C
W2
W5
W4
W7
W6
W9
0°C
≤
TO < 5°C
W1
W3
W3
W5
W4
W7
–4°C
≤
TO < 0°C
W1
W2
W2
W4
W3
W5
TO < –4°C
OFF
OFF
OFF
W3
W1
W4
TO error
OFF
WB
OFF
WE
W1
WE
Temp.
range
SM110
SM140
34.2 Hz or lower 34.2Hz to 52.2Hz 52.2Hz or higher
Min.
Max.
Min.
Max.
Min.
Max.
38°C
≤
TO
W6
WD
W8
WD
WA
WD
29°C
≤
TO < 38°C
W5
WC
W7
WC
W9
WD
15°C
≤
TO < 29°C
W3
W7
W5
W9
W7
WB
5°C
≤
TO < 15°C
W2
W5
W4
W7
W6
W9
0°C
≤
TO < 5°C
W1
W3
W3
W5
W4
W7
–4°C
≤
TO < 0°C
W1
W2
W2
W4
W3
W5
TO < –4°C
OFF
W2
OFF
W4
OFF
W4
TO error
OFF
WD
OFF
WD
OFF
WD
SVM-13072.indb 41
SVM-13072.indb 41
11/01/13 1:53 PM
11/01/13 1:53 PM