FILE NO. SVM-13072
Check
code
[F31]
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[EEPROM error]
[H01]
[Compressor break down]
[H02]
[Compressor lock]
Check outdoor P.C. board.
Defect
→
Replace
Check wire connection
and correct it.
Correct power supply line.
Check outdoor P.C. board.
Defect
→
Replace
Does an abnormal overload happen?
Is power supply voltage correct?
50 Hz : AC 198 to 264 V
60 Hz : AC 198 to 242 V
Is wire connection correct?
Compressor lead
(P.C. board side, Compressor side),
Reactor lead, Power supply lead
YES
YES
YES
NO
NO
NO
Check wire connection
and correct it.
Correct power supply line.
Is compressor under correct condition?
Is there refrigerant stagnation?
Does PMV correctly operate?
Is power supply voltage correct?
50 Hz : AC 198 to 264 V
60 Hz : AC 198 to 242 V
Is wire connection correct?
Compressor lead
(P.C. board side, Compressor side),
Reactor lead, Power supply lead
Compressor lock
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
Check TE, TS sensors and PMV.
Defect
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Remove and improve
the cause of overload.
– 63 –
SVM-13072.indb 63
SVM-13072.indb 63
11/01/13 1:53 PM
11/01/13 1:53 PM
Содержание RAV-SM1104ATJP-E
Страница 116: ...FILE NO SVM 13072 Inverter assembly SM56 116 SVM 13072 indb 116 SVM 13072 indb 116 11 01 13 1 54 PM 11 01 13 1 54 PM ...
Страница 120: ...FILE NO SVM 13072 Inverter assembly SM80 120 SVM 13072 indb 120 SVM 13072 indb 120 11 01 13 1 54 PM 11 01 13 1 54 PM ...
Страница 127: ...FILE NO SVM 13072 127 SVM 13072 indb 127 SVM 13072 indb 127 11 01 13 1 54 PM 11 01 13 1 54 PM ...