– 9 –
RAV-SM801AT-E
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa)
(kg/cm²G)
Pd
Ps
Pd
Ps
3.28
0.86
33.4
8.8
3.59
1.00
33.6
10.2
1.85
0.83
18.9
8.5
2.53
0.62
25.8
6.3
3.42
1.07
34.9
10.9
1.99
0.23
20.3
2.3
Pipe surface temperature (°C)
Discharge
Suction
Indoor heat Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TE)
84
11
10
45
82
17
16
51
42
8
6
23
75
3
42
2
80
20
54
17
89
–19
34
–18
Compressor
revolutions per
second (rps)
*
83
76
35
95
50
120
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
28/–
24/18
15/–
–10/
(70%)
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Indoor unit
Outdoor unit
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
TCJ
sensor
Air heat exchanger
Strainer
TC sensor
Refrigerant pipe
at gas side
Ø15.9
Packed valve
Refrigerant pipe
at liquid side
Ø9.5
Packed valve
Packed valve
Outer dia. ØA
Packed valve
Outer dia. ØB
Max.
50m
Min.
5m
TS
sensor
Accumulator
(1000cc)
TD
sensor
TO sensor
TE
sensor
4-way valve
(STF-0213Z)
Rotary
compressor
(DA150A1F-20F)
Heat exchanger
Ø8 ripple,
2 rows, 20 steps
FP1.3, flat fin
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
Distributor
Cooling
Heating
Ps
Pd
2-step
muffler
Ø25 × 200L