– 63 –
No.
Part name
Compressor
Procedure
1) Perform works of items 1 of
, 1 of
,
and
.
2) Recover refrigerant gas.
3) Remove the partition board.
(ST1T Ø4 × 8, 3 pcs)
4) Take off screws of the motor base and the
bottom plate. (ST1T Ø4 × 8, 2 pcs)
5) Remove the noise-insulator.
6) Remove the terminal cover, and then
disconnect the lead wires of the com-
pressor.
7) Using a burner, remove the pipes con-
nected to the compressor.
NOTE :
Pay attention to that flame does not involve 4-
way valve or PMV.
(If doing so, a malfunction may be caused.)
8) Take off screws of the bottom plate and
the heat exchanger. (ST1T Ø4 × 8, 1 pc)
9) Take off the fixing screws of the bottom
plate and the valve clamping plate.
(ST1T Ø4 × 8, 2 pcs)
10) Pull out the refrigerating cycle with the
heat exchanger.
11) Take off compressor bolts fixing the
compressor to the bottom plate. (3 pcs)
Remarks
Reactor
1) Perform woks of item 1 of
and 1 of
.
2) Take off screw fixing the reactor.
(ST1T Ø4 × 8)
Partition board
Compressor lead
Case thermo
Heat exchanger
Screw
Compressor bolt
(3 pcs)
Screws
(2 pcs)
Valve support
board
Remove
(Discharge pipe)
Remove
(Suction pipe)
Remove
(Discharge pipe)
Remove
(Suction pipe)
Partition board
Reactor