– 45 –
NO
NO
YES
NO
YES
YES
* For SM56, SM80, replace control P.C. board.
Are connections of
wire/connector normal?
Are wirings of power and
current sensor normal?
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2
W
?)
Is compressor normal?
Is not earthed?
Is not winding opened?
Compressor trouble
®
Replace
Compressor trouble
®
Replace
Compressor trouble
®
Replace
Check and correct circuit wires.
Check and correct circuit wiring
such as wiring to compressor.
Check IPDU P.C. board.
Defect
®
Replace
Check IPDU.
Defect
®
Replace
* For SM56, SM80, replace control P.C. board.
YES
YES
NO
NO
NO
YES
[P29 error]/[16 error]