8-5. Other Function
1. Recovery method of refrigerant
RAV-SM561AT-E, RAV-SM801AT-E
• When recovering refrigerant in case of reinstallation of the indoor or outdoor unit, etc., use the refrigerant
recovery switch on the terminal block of the outdoor unit.
WARNING
Never touch these switches. Otherwise the air
conditioner may not operate normally.
<Work procedure>
1. Turn on the power supply.
2. Using the remote controller, set FAN operation to
the indoor unit.
3. Pushing the refrigerant recovery switch on the
terminal block of the outdoor unit starts the
forced cooling operation. (Max. 10 minutes), and
then the refrigerant is recovered by operation of
the valve.
4. After recovery of the refrigerant, push the refrig-
erant recovery switch together with closing the
valve. The operation stops.
5. Turn off the power supply.
DANGER
Take care for an electric shock because the
control P.C. board is electrified.
CN804
Optional
connector
SW802
Refrigerant
recovery
SW
SW801
Outdoor unit cycle control
P.C. board
RAV-SM1101AT-E, RAV-SM1401AT-E
• When recovering refrigerant in case of reinstallation of the indoor or outdoor unit, etc., use the refrigerant
recovery switch SW802 on the cycle control P.C. board of the outdoor unit.
<Work procedure>
1. Turn on the power supply.
2. Using the remote controller, set FAN operation to
the indoor unit.
3. Pushing the refrigerant recovery switch SW802
on the cycle control P.C. board of the outdoor unit
starts the forced cooling operation. (Max. 10
minutes), and then the refrigerant is recovered by
operation of the valve.
4. After recovery of the refrigerant, push the refrig-
erant recovery switch SW802 together with
closing the valve. The operation stops.
5. Turn off the power supply.
DANGER
Take care for an electric shock because the
control P.C. board is electrified.
2. Applicable Control of Outdoor Unit
You can response to the following items by attaching the parts sold separately “Application
control kit” (TCB-PCOS1E).
<Demand control>
• It saves the capacity of the outdoor unit by outside Demand signal to correspond to the temporary peak cut.
• The capacity saving can be adjusted with three steps, 75%, 50%, and operation stop.
<Night operation control (Sound reduction)>
Sound is controlled to 45dB or less in inputting a timer point contact.
<Compressor operation output>
The check of the compressor operation time required of a maintenance etc.