background image

48-EN

47-EN

– 24 –

EN

Wired 

remote 

controller 

display

Wireless remote controller 

Sensor block display of 

receiving unit

Main defective parts

Judging 

device

Parts to be checked / error description

Air 

conditioner 

status

Indication

Operation Timer 

Ready 

GR GR OR

Flashing

F13

ALT

Heat sink sensor 

error

Outdoor

Abnormal temperature was detected by the 

temp. sensor of the IGBT heat sink.

Entire stop

F15

ALT

Temp. sensor 

connection error

Outdoor

Temp. sensor (TE/TS) may be connected 

incorrectly.

Entire stop

F29

SIM

Indoor unit, other 

P.C. board error

Indoor

Indoor P.C. board --- EEPROM error

Auto-reset

F30

SIM

Occupancy sensor 

trouble

Indoor

Abnormality was detected from occupancy 

sensor.

Operation 

continued

F31

SIM

Outdoor unit P.C. 

board

Outdoor

Outdoor P.C. board ---- In the case of EEPROM 

error.

Entire stop

H01

Outdoor unit compressor

breakdown

Outdoor

Current detect circuit, power voltage --- Minimum 

frequency was reached in the current releasing 

control or short-circuit current (Idc) after direct 

excitation was detected

Entire stop

H02

Outdoor unit 

compressor lock

Outdoor

Compressor circuit --- Compressor lock was 

detected.

Entire stop

H03

Outdoor unit current 

detect circuit error

Outdoor

Current detect circuit, outdoor unit P.C. board ---

Abnormal current was detected in AC-CT or a phase

loss was detected.

Entire stop

H04

Case thermostat 

operation

Outdoor

Malfunction of the case thermostat

Entire stop

H06

Outdoor unit low-

pressure system error Outdoor

Current, high-pressure switch circuit, outdoor 

P.C. board --- Pressure sensor error was 

detected or low-pressure protective operation 

was activated.

Entire stop

L03

SIM

Duplicated indoor 

indoor units 

Indoor

Indoor address setting error --- There are two or 

more header units in the group.

Entire stop

L07

SIM

Group line in

individual indoor unit Indoor

Indoor address setting error --- There is at 

least one group-connected indoor unit among 

individual indoor units.

Entire stop

L08

SIM

Indoor group address

not set 

Indoor

Indoor address setting error --- Indoor address 

group has not been set.

Entire stop

L09

SIM

Indoor unit capacity 

not set

Indoor

Indoor unit capacity has not been set.

Entire stop

L10

SIM

Outdoor unit P.C. 

board

Outdoor

In the case of outdoor P.C. board jumper wire 

(for service) setting errorm

Entire stop

L20

SIM

LAN communication 

error

Network 

adapter 

central 

control

Address setting, central control remote controller, 

network adapter --- Duplication of address in 

central control communication

Auto-reset

L29

SIM

Other outdoor unit 

Outdoor

Other outdoor unit error

Entire stop

1) Communication error between IPDU MCU 

and CDB MCU
2) Abnormal temperature was detected by the 

heat sink temp. sensor in IGBT.

L30

SIM

Abnormal external 

input into indoor unit 

(interlock)

Indoor

External devices, outdoor unit P.C. board --- 

Abnormal stop due to incorrect external input 

into CN80

Entire stop

L31

SIM

Phase sequence 

error, etc.

Outdoor

Power supply phase sequence, outdoor unit 

P.C. board --- Abnormal phase sequence of the 

3-phase power supply

Operation 

continued 

(thermost at 

OFF)

P01

ALT

Indoor unit fan error

Indoor

Indoor fan motor, indoor P.C. board --- Indoor 

AC fan error (fan motor thermal relay activated) 

was detected.

Entire stop

P03

ALT

Outdoor unit

discharge temp. error Outdoor

An error was detected in the discharge temp. 

releasing control.

Entire stop

P04

ALT

Outdoor unit high-

pressure system 

error

Outdoor

High-pressure switch --- The IOL was activated 

or an error was detected in the high-pressure 

releasing control using the TE.

Entire stop

Wired 

remote 

controller 

display

Wireless remote controller 

Sensor block display of 

receiving unit

Main defective parts

Judging 

device

Parts to be checked / error description

Air 

conditioner 

status

Indication

Operation Timer 

Ready 

GR GR OR

Flashing

P05

ALT

Open phase detected Outdoor

The power wire may be connected incorrectly. 

Check open phase and voltages of the power 

supply.

Entire stop

P07

ALT

Heat sink overheat

Outdoor

Abnormal temperature was detected by the 

temp. sensor of the IGBT heat sink.

Entire stop

P10

ALT

Indoor unit water 

over

fl

 ow detected

Indoor

Drain pipe, clogging of drainage, 

fl

 oat switch 

circuit, indoor P.C. board --- Drainage is out of 

order or the 

fl

 oat switch was activated.

Entire stop

P12

ALT

The fan error of the 

indoor unit

Indoor

Abnormal operation of the indoor fan motor, 

indoor P.C. board, or indoor DC fan (over current 

or lock, etc.) is detected.

Entire stop

P15

ALT

Gas leakage 

detected

Outdoor

There may be gas leakage from the pipe or 

connecting part. Check for gas leakage.

Entire stop

P19

ALT

4-way valve error

Outdoor 

(Indoor)

4-way valve, indoor temp. sensors (TC/TCJ) 

--- An error was detected due to temperature 

drop of the indoor unit heat exchanger sensor 

when heating.

Auto-reset

P20

ALT

High-pressure 

protective operation

Outdoor

High-pressure protection

Entire stop

P22

ALT

Outdoor unit fan 

error

Outdoor

Outdoor unit fan motor, outdoor unit P.C. board 

--- An error (overcurrent, locking, etc.) was 

detected in the outdoor unit fan drive circuit.

Entire stop

P26

ALT

Outdoor unit inverter  

Idc activated

Outdoor

IGBT, outdoor unit P.C. board, inverter wiring,

compressor --- Short-circuit protection for compressor

drive circuit devices (G-Tr/IGBT) was activated.

Entire stop

P29

ALT

Outdoor unit position  

error

Outdoor

Outdoor unit P.C. board, high-pressure switch --- 

Compressor motor position error was detected.

Entire stop

P31

ALT

Other indoor unit 

error

Indoor

Another indoor unit in the group is raising an alarm. Entire stop
E03/L07/L03/L08 alarm check locations and error 
description

Auto-reset

 : Lighting   : Flashing   : OFF 

 : The air conditioner automatically enters the auto-address setting mode.

ALT: When two LEDs are 

fl

ashing, they 

fl

ash alternately.  SIM: When two LEDs are 

fl

ashing, they 

fl

ash in synchronization. Receiving unit 

display OR: Orange   GR: Green

Содержание RAV-HM1101UTP-E

Страница 1: ...NDITIONER SPLIT TYPE Installation Manual Indoor Unit Model name For commercial use English R32 RAV HM561UTP E RAV HM801UTP E RAV HM901UTP E RAV HM1101UTP E RAV HM1401UTP E RAV HM1601UTP E 4 way Cassette type ...

Страница 2: ...rigerant HFC R32 which does not destroy the ozone layer Be sure to check the refrigerant type for outdoor unit to be combined and then install it Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the i...

Страница 3: ... person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified service person who is allowed to do the refrigerant handling and pi...

Страница 4: ... breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Only a qualified installer 1 or qualified service person 1 is allowed to undertake work at heights using a stand of ...

Страница 5: ... unit This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Selection of installation location When the air conditioner is installed in a small room provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level Do not install in a location where fla...

Страница 6: ...rry out the electrical work of the air conditioner Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks To connect the electrical wires repair the electrical parts or undertake other electrical jobs wear gloves to provide protection for electricians and from heat insulating shoe...

Страница 7: ... to turn it off in the event that trouble has occurred in the air conditioner If the fan grille is damaged do not approach the outdoor unit but set the circuit breaker to the OFF position and contact a qualified service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed After the installation work follow the Owner s Manual to explain...

Страница 8: ...safety maintenance and check Place where drained water will not cause any problem Avoid installing in the following places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring Should the unit be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a fa...

Страница 9: ... thick Ceiling height Model Possible installed ceiling height HM56 HM80 Type Up to 3 8 m HM90 HM110 HM140 HM160 Type Up to 4 6 m When the height of the ceiling exceeds the distance of the item Standard 4 way in Table as below the hot air is difficult to reach the floor Therefore it is necessary to change the setup value of the high ceiling switch or discharge direction The high ceiling setting is ...

Страница 10: ...n After the location of the indoor unit installation has been determined open the ceiling and install hanging bolts The dimensions of the ceiling opening and hanging bolt pitches are given in the outline drawing and the attached installation pattern When a ceiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their conne...

Страница 11: ...el according to Installation Manual attached with it after piping wiring work has completed Check that installation of indoor unit and ceiling opening part is correct and then install it REQUIREMENT Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage Remove th...

Страница 12: ...ply a heat insulation so as not to cause a dew dropping Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site Piping Hard vinyl chloride pipe VP25 Outer dia Ø32 mm Heat insulator Foam polyethylene Thickness 10 mm or more Flexible hose Use the attached flexible hos...

Страница 13: ...f check by pulling out the float switch connector be sure to return the connector to the original position 1 2 Power terminals CN34 RED Black Red White Black Pull out connector CN34 Red from P C board Single phase 220 240V Perform heat insulating As shown in the figure cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit without gap Cover the d...

Страница 14: ...e pipe with the attached heat insulator without any gap between the indoor unit The seam must be faced upward ceiling side Flare nut Indoor unit Heat insulation pipe Accessory Banding band locally procured Heat insulator of the pipe Union 7 Electrical connection WARNING Use the specified wires for wiring connect the terminals Securely fix them to prevent external forces applied to the terminals fr...

Страница 15: ...for each indoor unit in the simultaneous twin simultaneous triple and simultaneous double twin systems Wiring diagram Single system Simultaneous twin system Simultaneous triple and double twin system Communication type TU2C Link can be used with these models If the indoor unit and the connected remote controller remote sensor are all TU2C Link models TU2C Link communication will be performed autom...

Страница 16: ... 2 3 A B Heat insulation to wiring connecting port Adhered surface Notched section Power supply terminal block Cord clamp Remote controller terminal block Side D Space 8 5 mm Select side C or D for the power cable clamping position referring to the following table according to the cable type and diameter Cable clamp can be attached on either right or left side When twin system are connected clamp ...

Страница 17: ...until the remote controller becomes available Approx 1 minutes SETTING flashes SETTING goes out Remote controller is available Power on Normal settings were made when the indoor unit was shipped from factory Change the indoor unit settings as required Use the wired remote controller to change the settings The settings cannot be changed using the wireless remote controller sub remote controller or ...

Страница 18: ...re 5 1 0001 2 0002 3 0003 5 0005 4 0004 SET DATA When 4 or 5 is selected dew drop may occur during cooling mode y When the setting has been determined lights up Installing indoor unit on high ceiling When an indoor unit is installed on a ceiling higher than the standard height make the high ceiling setting for fan speed adjustment Follow to the basic operation procedure 1 2 3 4 5 6 For the CODE No...

Страница 19: ...emote controller sensor 0000 Not in use Factory default 0001 In use When flashes the remote controller sensor is defective Select the set data 0000 not in use or replace the remote controller Communication type When connecting to the central control device dedicated to TCC Link it is necessary to change to TCC Link Follow to the basic opreration procedure 1 2 3 4 5 6 7 y Specify FC for the Code No...

Страница 20: ...m setup Example of address setup change After setup of automatic address After setup change of manual address The above address is set by the automatic addressing when the power is turned on However line addresses and indoor addresses are set randomly For this reason change the setting to match line addresses with indoor addresses Manual address setting 1 Push and hold menu button and setting butt...

Страница 21: ...es 4 5 4 5 Indicators Operation green Timer green and Ready orange in the wireless receiver section flash in approx 10 seconds and the air conditioner starts operation If any of these indicators does not flash repeat procedures 2 to 5 7 Upon completion of the test run push ON OFF button to stop operation Overview of test run operations using the wireless remote controller T Cooling test run ON OFF...

Страница 22: ...nger It may differ from the actual discharge temperature 2 For outdoor unit data refer to the Installation Manual and Service Manual of the outdoor unit 10Maintenance CAUTION Before maintenance be sure to turn off the leakage breaker Cleaning of air filter Clogging of the air filter reduce cooling heating performance Cleaning of panel and air filter Preparation 1 Turn off the air conditioner by th...

Страница 23: ...s the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Parts Possible installed ceiling height Heat exchanger Access from inspection opening and remove the access panel E...

Страница 24: ...short circuit of the heat exchanger sensor TC was detected Auto reset F04 ALT Outdoor unit discharge temp sensor TD error Outdoor Outdoor temp sensor TD outdoor P C board Open circuit or short circuit of the discharge temp sensor was detected Entire stop F06 ALT Outdoor unit temp sensor TE TS error Outdoor Outdoor temp sensors TE TS outdoor P C board Open circuit or short circuit of the heat excha...

Страница 25: ...stop due to incorrect external input into CN80 Entire stop L31 SIM Phase sequence error etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermost at OFF P01 ALT Indoor unit fan error Indoor Indoor fan motor indoor P C board Indoor AC fan error fan motor thermal relay activated was detected Entire stop P03 ALT Out...

Страница 26: ...Place Issued Masaru Takeyama GM Quality Assurance Dept 5 April 2022 Thailand NOTE This declaration becomes invalid if technical or operational modifi cations are introduced without the manufacturer s consent Declaration of Conformity Manufacturer Toshiba Carrier Thailand Co Ltd 144 9 Moo 5 Bangkadi Industrial Park Tivanon road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand TCF holder TOSH...

Страница 27: ...ity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester seri...

Страница 28: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1115350191 ...

Отзывы: