background image

36-EN

35-EN

– 18 –

EN

„

 

Group control

Simultaneous twin system

A combination with an outdoor unit allows simultaneous 
ON / OFF operation of the indoor units. The following 
system patterns are available.
- Two indoor units for the twin system

 

Twin system

Outdoor unit

Indoor unit

Indoor unit

Remote

controller

Finish of address setup by power-ON

 

y

For wiring procedure and wiring method, follow to the 
“Electrical connection” in this manual.

 

y

When the power supply has been turned on, the 
automatic address setup starts and which indicates 
that address is being set up 

fl

ashes on the display 

part.

 

During setup of automatic address, the remote 
controller operation is not accepted.

Required time up to the 

fi

nish of automatic 

addressing is approx. 5 minutes.

4

0

03

01

02

Electrical control box

Refrigerant 

pipe

Drain

pipe

 

„

How to cancel louver lock

Set the wind direction to 

“0000”

 of the louver lock 

setup procedure above.

0000

Setting data

 

y

When the setting is canceled,   goes out.

  Other operations are the same as those in 

“How to set up louver lock (No swing)”.

 

„

To select horizontal wind 
direction

The louver positions at cooling can be changed from 
the smudge reducing position to the cold draftless 
position.

Follow to the basic operation procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 

 

7

 ).

 

y

Specify 

[45]

 for the Code NO. in Procedure 

4

.

 

y

Select the following data for the SET DATA in 
Procedure 

5

.

Wind 

direction 

SET DATA

Wind direction setting

0000

Smudge reducing position

(Air direction to reduce ceiling 

contamination) [Factory default]

0002

Cold draft position

(Air direction to control cold air fall)

 

„

Remote controller sensor

The temperature sensor of the indoor unit senses 
room temperature usually. Set the remote controller 
sensor to sense the temperature around the remote 
controller.
Select items following the basic operation procedure 
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 

 

7

).

 

y

Specify 

[32]

 

for the Code No. in Procedure 

4

.

 

y

Select the following data for the set data in 
Procedure 

5

.

Set data

Remote controller sensor

0000

Not in use (Factory default)

0001

In use

When 

 

fl

 ashes, the remote controller sensor is 

defective.
Select the set data [0000] (not in use) or replace the 
remote controller.

 

„

Communication type

When connecting to the central control device 
dedicated to TCC-Link, it is necessary to change to 
TCC-Link.

Follow to the basic opreration procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 

 

7

).

 

y

Specify 

[FC]

 for the Code No. in Procedure 

4

.

 

y

Select the set data [0000] (TCC-Link) in Procedure 

5

.

Set data

Communication type

0000

TCC-Link

0004

TU2C-Link (Factory default)

 

„

Fan speed setting when 
thermostat-OFF in cooling 
mode

Set the fan speed when the room temperature reaches 
the set temperature in the cooling mode.

Follow to the basic opreration procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 

 

7

).

 

y

Specify 

[9A]

 for the Code No. in Procedure 

4

.

 

y

Select the following data for the set data in 
Procedure 

5

.

Set data

Fan speed when thermostat-OFF 

in cooling mode

0000

Remote controller setting

0001

Extremely low speed (UL)

(Factory default)

 

„

8°C operation

Pre-heating operation can be set for cold regions 
where room temperature drops to below zero.

Follow to the basic opreration procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 

 

7

).

 

y

Specify 

[d1]

 for the Code No. in Procedure 

4

.

 

y

Select the following data for the set data in 
Procedure 

5

Set data

8°C Operation setting

0000

None (Factory default)

0001

8°C Operation setting

 

„

Installing optional parts

When installing optional parts, data setup may be 
required with remote controller.
Be sure to set the data, according to Installation 
Manual for optional parts.

 

„

Information

The following functions require a connection with 
the RBC-AMTU

 

½½½

 and RBC-AMSU

 

½½½

 remote 

controller. For details, refer to the manual included with 
the remote controller.

 

y

Individual unit selection during group operation

 

y

Individual setting of louver position (wind direction)

 

y

Swing type setting

 

y

Louver lock (no swing) setting

 

y

Energy saving operation (Power saving operation)

 

y

Noti

fi

cation of 

fi

lter cleaning time

 

„

Others

The following functions can be used with this model.
Refer to the Service Manual for more information.

 

y

Rotation / backup operation

 

y

Free cooling

 

y

Secondary heating

 

y

Power shift

Содержание RAV-HM1101UTP-E

Страница 1: ...NDITIONER SPLIT TYPE Installation Manual Indoor Unit Model name For commercial use English R32 RAV HM561UTP E RAV HM801UTP E RAV HM901UTP E RAV HM1101UTP E RAV HM1401UTP E RAV HM1601UTP E 4 way Cassette type ...

Страница 2: ...rigerant HFC R32 which does not destroy the ozone layer Be sure to check the refrigerant type for outdoor unit to be combined and then install it Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the i...

Страница 3: ... person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified service person who is allowed to do the refrigerant handling and pi...

Страница 4: ... breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Only a qualified installer 1 or qualified service person 1 is allowed to undertake work at heights using a stand of ...

Страница 5: ... unit This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Selection of installation location When the air conditioner is installed in a small room provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level Do not install in a location where fla...

Страница 6: ...rry out the electrical work of the air conditioner Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks To connect the electrical wires repair the electrical parts or undertake other electrical jobs wear gloves to provide protection for electricians and from heat insulating shoe...

Страница 7: ... to turn it off in the event that trouble has occurred in the air conditioner If the fan grille is damaged do not approach the outdoor unit but set the circuit breaker to the OFF position and contact a qualified service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed After the installation work follow the Owner s Manual to explain...

Страница 8: ...safety maintenance and check Place where drained water will not cause any problem Avoid installing in the following places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring Should the unit be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a fa...

Страница 9: ... thick Ceiling height Model Possible installed ceiling height HM56 HM80 Type Up to 3 8 m HM90 HM110 HM140 HM160 Type Up to 4 6 m When the height of the ceiling exceeds the distance of the item Standard 4 way in Table as below the hot air is difficult to reach the floor Therefore it is necessary to change the setup value of the high ceiling switch or discharge direction The high ceiling setting is ...

Страница 10: ...n After the location of the indoor unit installation has been determined open the ceiling and install hanging bolts The dimensions of the ceiling opening and hanging bolt pitches are given in the outline drawing and the attached installation pattern When a ceiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their conne...

Страница 11: ...el according to Installation Manual attached with it after piping wiring work has completed Check that installation of indoor unit and ceiling opening part is correct and then install it REQUIREMENT Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage Remove th...

Страница 12: ...ply a heat insulation so as not to cause a dew dropping Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site Piping Hard vinyl chloride pipe VP25 Outer dia Ø32 mm Heat insulator Foam polyethylene Thickness 10 mm or more Flexible hose Use the attached flexible hos...

Страница 13: ...f check by pulling out the float switch connector be sure to return the connector to the original position 1 2 Power terminals CN34 RED Black Red White Black Pull out connector CN34 Red from P C board Single phase 220 240V Perform heat insulating As shown in the figure cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit without gap Cover the d...

Страница 14: ...e pipe with the attached heat insulator without any gap between the indoor unit The seam must be faced upward ceiling side Flare nut Indoor unit Heat insulation pipe Accessory Banding band locally procured Heat insulator of the pipe Union 7 Electrical connection WARNING Use the specified wires for wiring connect the terminals Securely fix them to prevent external forces applied to the terminals fr...

Страница 15: ...for each indoor unit in the simultaneous twin simultaneous triple and simultaneous double twin systems Wiring diagram Single system Simultaneous twin system Simultaneous triple and double twin system Communication type TU2C Link can be used with these models If the indoor unit and the connected remote controller remote sensor are all TU2C Link models TU2C Link communication will be performed autom...

Страница 16: ... 2 3 A B Heat insulation to wiring connecting port Adhered surface Notched section Power supply terminal block Cord clamp Remote controller terminal block Side D Space 8 5 mm Select side C or D for the power cable clamping position referring to the following table according to the cable type and diameter Cable clamp can be attached on either right or left side When twin system are connected clamp ...

Страница 17: ...until the remote controller becomes available Approx 1 minutes SETTING flashes SETTING goes out Remote controller is available Power on Normal settings were made when the indoor unit was shipped from factory Change the indoor unit settings as required Use the wired remote controller to change the settings The settings cannot be changed using the wireless remote controller sub remote controller or ...

Страница 18: ...re 5 1 0001 2 0002 3 0003 5 0005 4 0004 SET DATA When 4 or 5 is selected dew drop may occur during cooling mode y When the setting has been determined lights up Installing indoor unit on high ceiling When an indoor unit is installed on a ceiling higher than the standard height make the high ceiling setting for fan speed adjustment Follow to the basic operation procedure 1 2 3 4 5 6 For the CODE No...

Страница 19: ...emote controller sensor 0000 Not in use Factory default 0001 In use When flashes the remote controller sensor is defective Select the set data 0000 not in use or replace the remote controller Communication type When connecting to the central control device dedicated to TCC Link it is necessary to change to TCC Link Follow to the basic opreration procedure 1 2 3 4 5 6 7 y Specify FC for the Code No...

Страница 20: ...m setup Example of address setup change After setup of automatic address After setup change of manual address The above address is set by the automatic addressing when the power is turned on However line addresses and indoor addresses are set randomly For this reason change the setting to match line addresses with indoor addresses Manual address setting 1 Push and hold menu button and setting butt...

Страница 21: ...es 4 5 4 5 Indicators Operation green Timer green and Ready orange in the wireless receiver section flash in approx 10 seconds and the air conditioner starts operation If any of these indicators does not flash repeat procedures 2 to 5 7 Upon completion of the test run push ON OFF button to stop operation Overview of test run operations using the wireless remote controller T Cooling test run ON OFF...

Страница 22: ...nger It may differ from the actual discharge temperature 2 For outdoor unit data refer to the Installation Manual and Service Manual of the outdoor unit 10Maintenance CAUTION Before maintenance be sure to turn off the leakage breaker Cleaning of air filter Clogging of the air filter reduce cooling heating performance Cleaning of panel and air filter Preparation 1 Turn off the air conditioner by th...

Страница 23: ...s the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Parts Possible installed ceiling height Heat exchanger Access from inspection opening and remove the access panel E...

Страница 24: ...short circuit of the heat exchanger sensor TC was detected Auto reset F04 ALT Outdoor unit discharge temp sensor TD error Outdoor Outdoor temp sensor TD outdoor P C board Open circuit or short circuit of the discharge temp sensor was detected Entire stop F06 ALT Outdoor unit temp sensor TE TS error Outdoor Outdoor temp sensors TE TS outdoor P C board Open circuit or short circuit of the heat excha...

Страница 25: ...stop due to incorrect external input into CN80 Entire stop L31 SIM Phase sequence error etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermost at OFF P01 ALT Indoor unit fan error Indoor Indoor fan motor indoor P C board Indoor AC fan error fan motor thermal relay activated was detected Entire stop P03 ALT Out...

Страница 26: ...Place Issued Masaru Takeyama GM Quality Assurance Dept 5 April 2022 Thailand NOTE This declaration becomes invalid if technical or operational modifi cations are introduced without the manufacturer s consent Declaration of Conformity Manufacturer Toshiba Carrier Thailand Co Ltd 144 9 Moo 5 Bangkadi Industrial Park Tivanon road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand TCF holder TOSH...

Страница 27: ...ity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester seri...

Страница 28: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1115350191 ...

Отзывы: